Troubleshooting/Specifications
Problem
Cause
Correction
Engine is running, but no AC
output is available.
1. One of the circuit breakers is open.
2. Poor connection or defective cord set.
3. Connected device is bad.
4. Red LED light is steady. Generator is
overloaded or overheated.
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is in
good condition.
4. See
Generator
Capacity
. Press
MAIN RESET button on control
panel.
Engine runs well at no-load but
“bogs down” when loads are
connected.
1. Generator is overloaded.
1. See
Generator Capacity
.
Engine will not start; starts and
runs rough or shuts down when
running.
1. Engine switch is in off position.
2. Low oil indicator light comes on. Low
oil level.
3. Dirty air cleaner.
4. Out of fuel.
5. Spark plug wire not connected to
spark plug.
6. Flooded with fuel.
1. Turn engine switch to on position.
2. Fill crankcase to proper level or
place generator on level surface.
3. Clean or replace air cleaner.
4. Fill fuel tank.
5. Connect wire to spark plug.
6. Wait 5 minutes and re-crank engine.
Engine shuts down and CO
shutdown system LED blinks red
(•• ••).
1. Generator improperly located.
1. Move generator to an open,
outdoor area. Air out premises (e.g.
open windows and doors) before
reoccupying. See
Carbon Monoxide
(CO) Shutdown System.
For all other issues, see a Briggs & Stratton authorized dealer.
Specifications
Rated Wattage* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,800
Starting Wattage** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,400
Current at 230 Volts AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.2 Amps
Current at 12 Volts DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.0 Amps
Current at 5 Volts DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Amps
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Hz
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single Phase
Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 cc (10.44 cu. in.)
Spark Plug Gap . . . . . . . . . . . . . . . . . . . . . . . . 0.6-0.7 mm (0.024-0.028 in.)
Fuel Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.0 Liters (1.0 U.S. Gallons)
Oil Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.4 Liters (13.5 Ounces)
Sound Pressure @ 7 m§ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 dBA
* Generator rated in accordance with CSA (Canadian Standards Association) standard C22.2 No. 100-14, Motors and Generators.
** Per Briggs & Stratton 628K.
§ Measured sound values in accordance to AS/NZS 3010:2017 Electrical installations - Generating sets.