background image

PC0011 Mood Lighting (ML) 
DALI/DMX 512 Controller 
Quick Start Guide 

1.

 

To securely mount the device on a flat surface, M4 screws and nuts 
can be applied at the slots at the side of the enclosure. (Not provided 
in the box)  
 

2.

 

If  connecting multiple ML Controllers to the same  PanL Hub port  in a 
daisy chain configuration, set the ID switch. Refer to the section - 

ID 

Switch Configuration

 for details. 

 

3.

 

Connect  RJ45  cable and add  a terminator.  Refer to the  section 

PanL 

Hub Connection

 for details. 

 

4.

 

If using 

DMX

, refer to 

PanL DMX Setup

 for details.  

 

5.

 

If using 

DALI

, refer to 

PanL DALI Setup

 for details.  

 

 

For multiple PanL ML Controller connections to a single PanL Hub port, the ID 
switch must be configured to be unique. Using a Philip head screw driver, set 
a unique number for each device between 0-7 (do not use 8-9). For example, 
if connecting 3 PanL ML Controllers to a PanL Hub port, you may set it as 0, 
1, and 2. PanL ML Controllers connected to different PanL Hub ports can share 
the same unique number. 
 

The PanL ML Controller is designed to be connected to a PanL Hub for power 
and  data  via  the  P1  or  P2  RJ45  ports.  When  a  single  PanL  ML  Controller  is 
connected to a  PanL Hub port, the maximum length of the RJ45 cable  shall 
not  exceed  100  meters.  Connect  the  terminator  (provided  in  the  PanL  Hub 
package) to the unconnected P1 or P2 port. 

 

 

 

 
For  multiple  PanL  ML  Controller  connections  to  a  single  PanL  Hub  port,  the 
first connection to PanL Hub and the subsequent connections in between the 
PanL ML Controller devices must not exceed 50 meters in cable length, each. 
The total combined cable lengths must not exceed 100 meters. Connect the 
terminator  provided  in  PanL  Hub  box  to  the  last  unconnected  PanL  ML 
Controller  P1 or P2 port. 

 

           

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

  

 

 

  

 

 

 

 

 

 

 

 

Product Features 

  

PanL ML Controller 

PanL ML Controller Setup 

ID Switch Configuration 

Please  visit 

http://panlshop.com/warranty

  or  scan  the 

QR  code

  for  warranty 

registration with the UUID and Product Key below:  

 

 

STICKER AREA 

PanL DMX Setup 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect a RJ45 cable from the PanL ML Controller port labelled DMX 512 to 
the  first  DMX  decoder  and  connect  a  DMX  terminator  to  the  last  unused 
decoder  port  as  illustrated  in  the  example  below.  The  PanL  ML  Controller 
supports up to 512 DMX channels. Depending on the number of channel(s) 
per  decoder  used,  the  cumulative  channels  must  not  exceed  512  for  all 
connected decoders. Please refer to the  D

ecoder’s datasheet

 for any cable 

length specifications.  

  

 

 

 

 

 

 

 

 

 

 

 

1

 

Power Indicator  

RJ45  Ports 

  Connect  to  PanL  PH44/80  Hub,  another  PanL 

Device or Terminator

 

ID Switch 

 Refer to the

 ID Switch Configuration

 section for 

more details

 

LED Status Indicator - Refer to the

 DALI/DMX ML Controller 

LED Status Indicator 

section for more details 

USB 

 Reserved for factory use only

 

SWD 

 Reserved for factory use only 

Reset Button  

DMX Connection 

 Refer to the 

PanL DMX Setup

 

DALI Connection 

 Refer to the 

PanL DALI Setup

 

 

PanL Hub Connection 

PanL DALI Setup 

Connect the DALI bus wires to the two DA terminals on PanL ML Controller 
and tighten the screws for a secure connection. The DALI bus is polarity free 
and  so the two wires  may  be  connected to either port. The recommended 
maximum length of the bus is 300 meters when AWG16 standard 2core wire 
in single cable or cable conduit is used.  PanL ML Controller supports up to 
64 DALI drivers. An external DALI bus power supply is required as illustrated 
below: 

 

 

 

 

 

 

 

 

 

 

 

 