05
www.breeze.com.vn | [email protected]
We bring better air to life
USER’S MANUAL
CDF/CDFS SERIES
Vibration Isolator Installation
Operating / free height
BUILDING CONTRUCTOR
EQUIPMENT OR HANG
EQUIPMENT OR HANG
EQUIPMENT OR HANG
1
2
3
EQUIPMENT OR HANG
4
EQUIPMENT OR HANG
5
EQUIPMENT FOOT OR
MOUNTING BRA
TURN/ADJUST
BOLT TO REACH
1
2
3
4
5
HANGER ISOLATOR
MOUNTED ISOLATOR
Vibration Isolator Guideliness
•
Choose proper isolator
•
Adjust deflection based on the selected isolator.
•
Maintain the operating / free height at the same level through step 2.
(The entire assembly must be levelled)
•
Check all the deflection and operating/free height is properly maintained.
EQUIPMENT OR HANG
INCORRECT
EQUIPMENT OR HANG
CORRECT
EQUIPMENT OR HANG
INCORRECT
BUILDING CONTRUCTOR
EQUIPMENT OR HANG
CORRECT
EQUIPMENT OR HANG
INCORRECT
Common Sources of Vibration
1. Impeller Unbalance
2. Drive Pulley Misalignment
3. Incorrect Belt Tension
4. Bearing Misalignment
5. Mechanical Looseness
6. Faulty Belts
7. Drive Component Unbalance
8. Poor Inlet/Outlet Conditions
9. Foundation Stiffness
On start-up and during operation, the unit should operate smoothly with minimal
vibration. It is possible that a higher degree of vibration may be experienced. Excessive
vibration if left unchecked, can cause a multitude of problems, including structural and/or
component failure. The most common sources of vibration are listed.
4.4 Vibration