Breezair TBA 550 Скачать руководство пользователя страница 1

Breezair TBA 550
Installation Manual

Содержание TBA 550

Страница 1: ...Breezair TBA 550 Installation Manual...

Страница 2: ...the Air Cooler Components of the Air Cooler Dismantling the Air Cooler Installing the Transition Installing Electric Cables Water Connection Plumbing Connection Electrical Connection Installing the Fa...

Страница 3: ...using safe methods and equipment Never drain the cooler directly onto the roof Always use pipes to carry the drain water to a proper point Failure to do this can stain the roof and make the roof slip...

Страница 4: ...ler by the installer The air cooler will function best when clean water is supplied Water that contains dissolved salts and other impurities will cause the cooling pads to become blocked more quickly...

Страница 5: ...xtension Tube connects the Float Valve to the Solenoid Valve 9 Water Tank reservoir 10 Corner Pillar 11 Water Sensor detects conductivity of water 12 Float Valve for control of main water supply level...

Страница 6: ...NG THE VENTURI FAN IMPORTANT Ensure the motor plug has been removed from the control box before removing the venturi see page 9 for removal of plug With both arms hold each side of the Venturi fan ass...

Страница 7: ...teners in this section The best location for the cooler is where the air is fresh and clean Keep away from exhaust vents from factories and commercial kitchens Do not locate the air cooler near the gr...

Страница 8: ...e Water Tank Now pass the cables through your main conduit and connect the main conduit to the conduit adaptor under the Transition IMPORTANT Pass the wall control cable through the conduit first Term...

Страница 9: ...e to move up and down Screw the Solenoid Valve into the extension tube Check the direction of water flow with the arrow on the back of the valve See diagram Make sure Solenoid Valve seals against the...

Страница 10: ...minimised The water management devices fitted will help control the effects of poor quality water but they cannot eliminate the problem After fitting the Bleed Funnel then fit the Float Valve as shown...

Страница 11: ...e See diagram Lift the flexible cover on the Electronics Module You will see some plug points Connect the wall control cable to its correct plug point If the drain valve water sensor and solenoid valv...

Страница 12: ...in direct line of a cooling outlet Mounting the wall control in a position near any heat source or cooling outlet will affect its ability to control temperature The Wall Control cable will plug into t...

Страница 13: ...screw so it protrudes by 2 0mm Pull the wall control cable through the large hole remove the protective tape and plug the cable into the wall control Feed the excess cable back into the hole and slide...

Страница 14: ...ed then turn off power to the air cooler for a minimum of 6 seconds before starting the following procedure SET UP FOR BLEED FUNNEL If you installed the bleed funnel instead of the drain valve then yo...

Страница 15: ...Press AUTO to complete the adjustment Exit the programming mode by pressing the POWER button Commissioning The Air Cooler CORRECT WATER LEVEL With the water pump still disconnected turn on the water...

Страница 16: ...he pad frames and run the air cooler To start the air cooler press the power button on the wall control If it has not been on before it will start in Manual control mode Man will display as shown The...

Страница 17: ...OBLEM Motor Starts and Stops at Intervals CAUSE ACTION 1 Loose electrical connections Check all electrical connections 2 Fan not turning freely Determine cause and rectify 3 Weatherseal failing to ope...

Страница 18: ...k plug connection and connected to electronic module orientation See diagram on pg 9 3 Water sensor not operating Check sensor Clean sensor PROBLEM Unit Will Not Run Wall Control Display Fault CAUSE A...

Страница 19: ...es 7 Insufficient water pressure to Check that the water pressure is raise the water level to the sufficient to fill the tank to the sensor within 8 minutes sensor within 8 minutes if water sensor ins...

Страница 20: ...information is extracted from booklet 839479 B 18...