Equivalent Vent Length (EVL) 

The longer the run of pipe in your installation, the more restriction 
there is in the system. Therefore, larger diameter pipe should be 
used. 

 

Use 4” pipe if you have more than 

15 feet

 of equivalent vent 

length. 

 

Horizontal runs shall not exceed 10’ of EVL. 

 

Recommended vertical runs to be a minimum of 8’. 

 

To calculate EVL, use the following conversions: 

90º elbow or “T”  

= 5 equivalent feet 

45º elbow 

 

= 3 equivalent feet 

Horizontal Pipe Run 

= 1 equivalent foot per actual foot 

Vertical Pipe Run 

= 0.5 equivalent foot per actual foot 

NOTE: At altitudes above 3,000 feet, we suggest the use of 4” 
diameter vent at an EVL of 7 feet or more. 

P2700 INSTALLATION 

A. 

HORIZONTALLY THROUGH WALL 

(refer to Figure 6) 

 

NOTE: 

See “

VENTING

” and follow L-Vent chimney manufacturer’s 

instructions. 
 
1. 

Position stove, adhering to clearances shown in Figures 1 & 2. 

 
2. 

Locate position of hole in wall; directly behind stove exhaust 
vent (refer to figure 4). 

 
3. 

Always maintain 3” clearance from combustible materials. 

 
4. 

Install L-Vent wall thimble per L-Vent manufacturer’s 
instructions. 

 
5. 

Attach enough piping to penetrate and extend at least 6” 
beyond exterior walls. An 8-foot vertical pipe run is suggested 
where possible to reduce the possibility of smoke spillage in 
the event of a loss of negative pressure. 

 
6. 

Attach cap and seal outside wall thimbles with non-hardening 
waterproof mastic. 

 
7. 

Termination should not be located so that hot exhaust gases 
can ignite trees, shrubs, or grasses or be a hazard to children. 
Exhaust gases can reach temperatures of 500ºF and cause 
serious burns if touched. 

 

 

 

 

 

 

 

 

 

 

Locate terminations: a) not less then 3 feet above any 
forced air inlet located within 10 feet; b) not less than 4 
feet below or horizontally from, or one foot above, any 
door, window or gravity air inlet into any building; c) 
not less than two feet from an adjacent building and 
not less than 7 feet above grade when located 
adjacent to a public walkway. Mobile home 
installations must use a spark arrester. 

 

 

 

INSTALLATION

7

FIGURE 6 

Содержание Luxury P2700 Series

Страница 1: ...e is not properly installed a house fire may result For your safety follow the installation directions Contact local building or fire officials about restrictions and installation inspection requireme...

Страница 2: ...which is designed for connection to an outside combustion air source The stove will not operate using natural draft or without a power source for the blower systems and fuel feed system and must not b...

Страница 3: ...can shine on the unit it is possible this can cause the temperature of the stove to rise to operational levels one of the sensors could then make the stove start on its own It is recommended that the...

Страница 4: ...Fan 11 Re Starting a Warm Stove 11 If Stove Runs Out Of Pellets 11 Damper Control 12 Refueling 12 Breckwell Maintenance Tool 12 Shutdown Procedure 12 Safety Features 12 Optional Thermostat 13 Thermos...

Страница 5: ...installations minimum 24 wide by 29 deep The stove must be placed on a continuous grouted joints noncombustible material such as ceramic tile cement board brick 3 8 millboard or equivalent or other a...

Страница 6: ...he stove WHEN OUTSIDE AIR IS NOT USED If outside air is not used it is important that combustion air is easily available to the air inlet A closeable outside air register can be used in tightly insula...

Страница 7: ...exhaust vent refer to figure 4 3 Always maintain 3 clearance from combustible materials 4 Install L Vent wall thimble per L Vent manufacturer s instructions 5 Attach enough piping to penetrate and ex...

Страница 8: ...er C VERTICALLY INTO EXISTING CHIMNEY SYSTEM Adapters are available to adapt from 3 L Vent to 6 or 8 Class A chimney Figure 8a As an alternative 3 or 4 L Vent can be run inside existing chimney to ter...

Страница 9: ...be filled with high temperature grout 8 Install the trim collar An adjustable pipe length and adapter may be needed to finish the connection to the stove ELECTRICAL INSTALLATION This stove is provided...

Страница 10: ...n to its original setting based on the Heat Level Advance setting d RESET TRIM Different size and quality pellet fuel may require adjustment of the 1 feed setting on the Heat Level Advance bar graph T...

Страница 11: ...ets to the burnpot by hand 4 DO NOT use the Fuel Feed button unless you are priming the auger after running out of pellets A dangerous condition could result NOTE During the first few fires your stove...

Страница 12: ...om of the hopper b Scrape ashes from burnpot SHUTDOWN PROCEDURE Turning your Breckwell stove off is a matter of pressing the On Off control panel switch The red light will go out The blowers will cont...

Страница 13: ...tion of this owner s manual HIGH LOW THERMOSTAT MODE When engaged in this mode the stove will automatically switch between two settings When warm enough it will switch to the 1 or low setting The room...

Страница 14: ...AL PART OF THE UNIT BEGINS TO GLOW YOU ARE OVERFIRING Immediately press the POWER switch on the control panel h KEEP ALL LOOSE OR MOVEABLE HOUSEHOLD COMBUSTIBLES SUCH AS FURNITURE DRAPES TOYS ETC AT L...

Страница 15: ...from burn pot Scrape burn pot with cleaning tool Make sure burnpot holes are not plugged e Scrape ash in firebox into the under stove bin through the opening see Figure 15 or vacuum to remove ashes WA...

Страница 16: ...s highly combustible INSPECT BEHIND THESE CLEANING PLATES AT LEAST ONCE PER TON OF PELLETS BURNED UNTIL YOU ARE FAMILIAR WITH HOW ASHES AND CREOSOTE ACCUMULATE WITH YOUR OPERATING PRACTICES Use the sm...

Страница 17: ...ved with a brush specifically designed for the type of chimney in use A qualified chimney sweep can perform this service It is also recommended that before each heating season the entire system be pro...

Страница 18: ...der the burnpot make sure the slider plate is in place to seal off the firebox floor 4 Vent pipe is incorrectly installed Check to make sure vent pipe installation meets criteria in owner s manual 5 T...

Страница 19: ...m Also check the auger tube for signs of damage such as burrs rough spots or grooves cut into the metal that could have caused a jam 7 The auger motor has failed Remove the auger motor from the auger...

Страница 20: ...r Check the voltage going to the igniter during startup It should be a full current If the voltage is lower than full current check the wiring If the wiring checks out good the board is bad SMOKE SMEL...

Страница 21: ...shaft inspection plate in the hopper so that you can see the auger shaft Gently lift the auger shaft straight up so that the end of the auger shaft comes up out of the bottom auger bushing Next remove...

Страница 22: ...d light at each setting after the stove has completed the startup cycle Make sure the times match the auger timing chart If the auger motor runs constantly the board is bad 8 Combustion blower is not...

Страница 23: ...ck for signs of fuel other than wood pellets If there are signs of corn being used find out what mixed was being used and what setting No other types of fuel have been approved for Breckwell pellet st...

Страница 24: ...FIGURE 20 ELECTRICAL DIAGRAM 24...

Страница 25: ...al A M BRICK27 Burnpot A S BURNPOT Ceramic Firelog Set imitation Optional A M LOG Circuit Board Control Panel C E 401 Combustion Blower A E 027 Convection Blower A E 033 Door Gasket C G 050 Door Glass...

Страница 26: ...tion or other circumstances beyond Breckwell s control If warranty service is needed during the warranty period contact your Authorized Breckwell Dealer Provide your name address phone number serial n...

Отзывы: