SERIES 62 Solenoid Pilot Valve 

Operation & Maintenance Manual

Manual Number OM-62-001 • Date: March 24, 2014 8:28 AM • Page 1 of 2

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.
The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Description

The Bray Series 62 solenoid pilot spool valves have an aluminum 

body and mounting interface pattern conforming to NAMUR.  

The Bray Series 62 is IP65, NEMA 4, 4x.
The Bray Series 62 solenoid can be used either with Sin-

gle Acting/Spring Return or Double Acting/Direct Acting  

actuators. Double Acting/Direct Acting actuators use the 

5/2 configuration (Fig. 1-2) and requires no adapter kit. Sin-

gle Acting/Spring Return actuators use the 3/2 configuration  

(Fig. 3-4) and require the use of a conversion kit to convert 

4-Way to 3 -Way, part number 62-1250-22500-536 (sold sep-

arately).  This  kit  includes  an  airflow  plate,  O-ring  seal  and  

longer screws.

Installation

Valves are designed to be operated within the technical charac-

teristics  specified  on  the  nameplate.  Bray  reserves  the  right  to 

change or modify product design without prior notice.
These  valves  are  designed  to  operate  with  filtered  air  or  inert  

gas  (e.g.  Nitrogen).  Do  not  exceed  the  maximum  allowable 

pressure of 130 psi (9 bar), and minimum operating pressure of  

22 psi (1.5 bar). Operating ambient temperature range is a +5°F to 

+140° F (-15° C to +60° C). Installation and maintenance of the 

solenoid valve must be carried out by qualified personnel only.
Before mounting the solenoid spool valve assembly on the  

actuator it must be configured for the required function. 

 For 5/2 Double Acting/Direct Acting 4-Way:

 no con-

version kit is required. The solenoid spool valve assembly 

mounts directly to the actuator with 2 each (#10-32 -1 1/8” or 

m5 x 0.8, 28mm depending on actuator drilling) screws and 

O-rings as shown in figures 1 and 2.

 For 3/2 Single Acting/Spring Return 3-Way:

 the 4-way to 

3-way conversion kit (flow plate, O-ring and 2 each (#10-32 

-1 3/8” or m5 x 0.8, 28mm depending on actuator drilling) 

longer screws, part # 62-1250-22500-536 (sold separately) 

may be used. Install the conversion kit as shown between the 

solenoid pilot valve and actuator as shown in figures 1 and 2. 

It however is not uncommon to use a 4-way solenoid to op-

erate a Single Acting actuator, in a “spring to close air assist” 

configuration. In this configuration no adapter kit is required.

Pneumatic Connections

 Connect supply pipes in accordance with the markings on 

the nameplate

 

5/2  Double  Acting/Spring  Return  configuration:

  

Supply pressure to Port 1 (¼”NPT). Exhaust both Ports 3 

and 5 (1/4”NPT).

 

3/2 Single Acting/Spring Return configuration:

 Supply 

pressure to Port 1 (¼”NPT), Exhaust to Port 3 (¼” NPT).  

It is recommended to protect Port 5 (when not used) with a 

vented pipe plug or screen, do not plug completely.

Manual override

The solenoid is equipped with a Manual Override:
To engage Override; depress the red manual override button and 

rotate 90° clockwise, the override will lock in place, causing the 

spool valve to activate. The button can also be pressed to activate 

the spool momentarily. (Please refer to Figs 1, 2, and 3 on page 2 

for the location of the manual override button). 
To  disengage  Override;  rotate  the  red  manual  override  button 

counterclockwise 90°, the manual override button will pop out 

and the spool will deactivate and be returned to the normal posi-

tion. (Please refer to Figs 1, 2, and 3 on page 2 for the location of 

the manual override button).

In order to prevent injury or damage and to ensure correct 

remote operation of the pilot solenoid valve, the Manual 

Override  must  be  returned  to  the  disengaged  position  by 

rotating  it  90°  counterclockwise,  to  normal  (disengaged) 

before returning to remote operation of the pilot solenoid.

General Recommendations concerning pneumatic 

 

connections: 

connect  pipes  with  the  required  functions  in  

accordance  with  this  documentation  and  port  markings  on  the 

valve. Make sure no foreign matter enters the system. Use of a 

coalescing filter regulator is recommended.
Correctly  support  the  supply  piping  to  avoid  subjecting  the  

solenoid spool valve assembly to mechanical stress, when  

tightening, avoid using the valve as a lever. Use proper tools and 

locate wrenches as close as possible to the connection point. To 

avoid damage of the equipment 

DO NOT OVER TIGHTEN

 pipe 

connections.

Electrical Connections

 IP65/NEMA 4,4X 3 wire flying lead (2+ ground/earth)

 

Red power, Yellow/green: ground/earth

 DIN: 3 prong DIN Connector 
 General recommendations for electrical connections:

 

electrical connections are only to be made by trained  

personnel and in accordance with the applicable regulations 

and standards.