I E16x442 Rev: 00
Page 62 of 73
Parameter Group P12.xx of Monitor E1665
Voter 3 and Logic Output LO3
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P12.00
Operation mode
Range: 0 .. 5
Setting
0 : Voter inactive
1 : Voter always active (over entire speed range)
2 : Voter only active, if n > SPV3
3 : Voter only active, if n < SPV3
4 : Voter inactive, output LO3 low, if n > SPV3
5 : Voter inactive, output LO3 high, if n > SPV3
P12.01
Input Truth Level
Range: 0 .. 1
Setting
0 : high level at inputs is assigned to trip condition
1 : low level at inputs is assigned to trip condition
P12.02
Voting Logic
Range: 0 .. 3
Selectable Voting Logics are:
1oo2 : trip is released if 1of 2 inputs signalizes trip condition
2oo2 : trip is released if 2 of 2 inputs signalize trip condition
2oo3 : trip is released if 2 of 3 inputs signalize trip condition
3oo3 : trip is released if 3 of 3 inputs signalize trip condition
Setting
0 : 1oo2 (only inputs 1 and 2 of voter 3 are monitored)
1 : 2oo2 (only inputs 1 and 2 of voter 3 are monitored)
2 : 2oo3 (all three inputs of voter 3 are monitored)
3 : 3oo3 (all three inputs of voter 3 are monitored)
P12.03
Truth Time until Trip
Range: 0 .. 11
If the trip signal is shorter than the
minimum truth time, the signal is
not valid (anti bouncing filter). If the
signal is longer than the maximum
truth time, the signal is valid and
trip is released.
Note:
Signal truth times in between min.
and max. may release trip.
Maximum response time until out-
put of Trip-Lines go to trip status is
maximum truth time + 3 millisec-
onds.
Setting
Trip after
min.
max.
0
3 msec
5 msec
1
6 msec
9 msec
2
12 msec
16 msec
3
24 msec
28 msec
4
48 msec
52 msec
5
96 msec
102 msec
6
192 msec
202 msec
7
384 msec
400 msec
8
768 msec
800 msec
9
1.570 sec
1.600 sec
10
3.140 sec
3.200 sec
11
6.280 sec
6.400 sec
P12.04
Trip by Voter3 latched
Range: 0 .. 1
Setting
0 : trip by voter 3 is not latched
1 : trip by voter 3 is latched until reset