RS485 card (optional)
A and Bon the right side of ports are RS485 output, A is"+", Bis"-".
4.6.4 Maintenance switch
Maintenance switch is for UPS on-line maintenance, follow below procedures:
•
Open the cover plate of the maintenance switch on the UPS rear panel, the
UPS will automatically transfer to bypass to supply power to the load.
•
Make the maintenance switch at "BYPASS".
•
Disconnect all input/ battery breakers.
•
Wait until the display screen is extinguished completely and on standing for 10
mins, make sure there is no hazard of electrical shock inside the UPS, and you
can do on-line maintenance for the UPS.
•
After finishing on-line maintenance, close the input breaker first, then make the
maintenance switch at "UPS" end, and then install the cover plate of the
maintenance switch.
Note:
Make sure the system bypass is normal and not to start frequency conversion,
otherwise it may cause power failure or even damage to loads.
If the UPS has no output and needs manual on-line maintenance, disconnect all
input breaker and ensure the UPS display screen is extinguished, then put the
maintenance switch to "BYPASS" by hand, otherwise it may cause damage to the
UPS.