43
DX3
Series
Figure 3.31
•
Gas Connection (Type 1 Hose Gas Connector shown)
•
Side View
Figure 3.32
•
Gas Connection (Type 1 Hose Gas Connector shown)
•
End View
NOTE:
Do not exceed 14 Inches W.C. to the appliance.
*The tube heater expands and contracts during operation. Follow the installation instructions to ensure
allowances are made for this movement. To ensure your safety, and comply with the terms of the
warranty, all units must be installed in accordance with these instructions.
Ball Valve / Inlet Tap
Hose connections must be installed inline
in the same direction as heater expansion
Burner Control Box
End View
Ball Valve / Inlet Tap
7”-14”
Type 1 Hose Gas Connector, formed into a U-bend
Adapter
Drip Leg/
Sediment Trap
Heater Movement*
Elbow
Burner
Control Box
Side View
Adapter
Elbow