Brant Radiant Heaters DES3-20-50 Скачать руководство пользователя страница 5

5

DES3 

Series

LIGHTING INSTRUCTIONS
1. PURGE MAIN GAS SUPPLY LINE.

2. ROTATE HEATER’S MANUAL GAS

    VALVE KNOB TO “ON” POSITION.

3. CLOSE ELECTRICAL CIRCUIT.

4. IF HEATER FAILS TO LIGHT, TURN

    OFF GAS AND WAIT 5 MINUTES

    BEFORE REPEATING ABOVE.

INSTRUCTIONS POUR L’ALLUMAGE
1. PURGER LA CONDUITE D’ALIMENTATION
    EN GAZ PRINCIPALE.
2. TOURNER LE BOUTON DU ROBINET
    DE GAS A COMMANDE MANUELLE
    JUSQU’A CE QU’IL SE TROUVE EN
   POSITION DE MARCHE (“ON”)
3. FERMER LE CIRCUIT ELECTRIQUE.
4. SI L’APPAREIL DE CHAUFFAGE NE
    S’ALLUME PAS, ATTENDRE 5 MINUTES 
    AVANT DE SUIVRE DE NOUVEAU LES 
    INSTRUCTIONS CI-DESSUS.

TO SHUT DOWN
1. ROTATE HEATER’S MANUAL GAS

    VALVE KNOB TO “OFF” POSITION.

2. OPEN ELECTRICAL CIRCUIT.

POUR ETEINDRE L’APPAREIL
1. TOURNER LE BOUTON DU ROBINET

    DE GA  A COMMANDE MANUELLE

    DE L’APPAREIL DE CHAUFFAGE

     US U’A CE  U’IL DE TROUVE EN

    POSITION D’ARRET  “OFF” .

2. OUVRIR LE CIRCUIT ELECTRI UE.

BRANT RADIANT HEATERS LIMITED

34 SCOTT AVENUE, PARIS ON. N3L 3R1

TELEPHONE  51

442

2

3

WWW.BRANTRADIANT.COM

SERVICE ACCESS PANEL

IGNITER & FLAME SENSE COMPARTMENT

 

1.

 Disconnect gas & electricity.

2.

 Remove cover by lifting top 

    cover upward and outward.

CAUTION:

  

HOT SURFACE.

KEEP COVER IN PLACE. REMOVE FOR SERVICE ONLY.

MODEL /MODELE NO.

DES-40-125N(-3)

INPUT BTU/H

125,000 

FOR USE WITH

NATURAL GAS

RADIATEUR A INFRAROUGE A FAIBLE INTENSITE

VOLTS A.C.

STARTING AMPS.

RUNNING AMPS.

120~60Hz

1.7

1.1

MANIFOLD PRESSURE

MIN. INLET PRESSURE

ORIFICE SIZE

3.5” WC

5.0” WC

#3 D.M.S

HEATER TYPE

VERSION

MIN. MOUNTING ANGLE:

COMBUSTION CHAMBER:

4” BC TITANIUM

FOR INDOOR USE

BRANT RADIANT HEATERS LIMITED
34 SCOTT AVE., PARIS, ONTARIO
TEL: 1-519-442-7823 WWW.BRANTRADIANT.COM

ANSI Z83.20b - 2011 CSA 2.32b - 2011 Low - Intensity Infrared Htr. 
ANS Z83.20b - 2011 CSA - 2011 Low - Intensity Infrared Htr.

SERIAL NO. 

0870 XXXX XXXX 0001

RE-VERBER-RAY LOW INTENSITY INFRARED HEATER

FOR INDOOR INSTALLATION ONLY. NOT FOR USE IN RESIDENTIAL DWELLING.
INSTALLATION À L’EXTÉRIEUR SEULEMENT. NE PAS INSTALLER DANS UN LOGEMENT.

MAX. MOUNTING ANGLE:

0 DEGREES

45 DEGREES

FOR STAINLESS STEEL UPGRADES THE 

COMBUSTION TUBE IS UPGRADED TO 409 

STAINLESS STEEL.

C1

10/11

S3

16” Burner 

Tube

Primary Combustion 

Chamber

Secondary Combustion 
Chamber (if applicable)

F/N: LLTB026

F/N: LLTB024R

F/N: LLTB025

SERVICE ACCESS PANEL

SERVICE ACCESS PANEL

COMPARTIMENT VENTILATEUR

FAN COMPARTMENT

1. 

Disconnect gas & electricity.

2. 

Remove top cover 

    (2 thumbsscrews).

3. 

Remove six (6) 1/4” screws.

4. 

Lift and remove panel.

1.

 Débrancher le gaz et l’electricité.

2.

 Retirer les 2 vis à main du couvercle 

    supérieur. 

3.

 Retirer les 6 vis 1/4 po. 

4.

 Soulever et retirer le panneau.

GARDER LE COUVERCLE EN PLACE. NE L’ENLEVER QUE POUR L’ENTRETIEN.

Fan 

Compartment

Controls 

Compartment

Rating 

Plate

MODEL /MODELE NO.

DES-40-125N(-3)

INPUT BTU/H

125,000 

FOR USE WITH

NATURAL GAS

RADIATEUR A INFRAROUGE A FAIBLE INTENSITE

VOLTS A.C.

STARTING AMPS.

RUNNING AMPS.

120~60Hz

1.7

1.1

MANIFOLD PRESSURE

MIN. INLET PRESSURE

ORIFICE SIZE

3.5” WC

5.0” WC

#3 D.M.S

HEATER TYPE

VERSION

MIN. MOUNTING ANGLE:

COMBUSTION CHAMBER:

4” BC TITANIUM

FOR INDOOR USE

BRANT RADIANT HEATERS LIMITED
34 SCOTT AVE., PARIS, ONTARIO
TEL: 1-519-442-7823 WWW.BRANTRADIANT.COM

ANSI Z83.20b - 2011 CSA 2.32b - 2011 Low - Intensity Infrared Htr. 
ANS Z83.20b - 2011 CSA - 2011 Low - Intensity Infrared Htr.

SERIAL NO. 

0870 XXXX XXXX 0001

RE-VERBER-RAY LOW INTENSITY INFRARED HEATER

FOR INDOOR INSTALLATION ONLY. NOT FOR USE IN RESIDENTIAL DWELLING.

INSTALLATION À L’EXTÉRIEUR SEULEMENT. NE PAS INSTALLER DANS UN LOGEMENT.

MAX. MOUNTING ANGLE:

0 DEGREES

45 DEGREES

FOR STAINLESS STEEL UPGRADES THE 

COMBUSTION TUBE IS UPGRADED TO 409 

STAINLESS STEEL.

C1

10/11

SA

MP

LE

1.0

 Introduction • 

Safety Signs and Labels  

Lighting Instruction 

Label

Tube Indicator Label

Содержание DES3-20-50

Страница 1: ...ntideflagrant Lorsqu il y a risque de contact avec des vapeurs inflammables consulter le commissaire local des incendies la compagnie d assurance incendie ou tout autre authorit comp tente pour approb...

Страница 2: ...ntrol Box Suspension 19 Reflector Assembly 20 Baffle Assembly and Placement 22 Final Heater Assembly 23 Venting 24 Optional Unvented Operation 31 Combustion Air Requirements 32 Separated Combustion Sy...

Страница 3: ...HRT 60 7 2 DES3 60 150 N or LP 150 000 60 5 32 5 265 17 to 35 Titan Alum HRT 60 7 2 DES3 60 175 N or LP 175 000 60 5 32 5 265 17 to 35 Titan Alum HRT 60 7 2 DES3 60 200 N or LP 200 000 60 5 32 5 265...

Страница 4: ...rews 4 Lift and remove panel KEEP COVER IN PLACE REMOVE FOR SERVICE ONLY F N LLTCL001L C R Clearance to Combustibles Labels Safety Labels and Their Locations Top Panel Bottom Panel F N LLLOGO1 Logo La...

Страница 5: ...r SERIAL NO 0870 XXXX XXXX 0001 RE VERBER RAY LOW INTENSITY INFRARED HEATER FOR INDOOR INSTALLATION ONLY NOT FOR USE IN RESIDENTIAL DWELLING INSTALLATION L EXT RIEUR SEULEMENT NE PAS INSTALLER DANS UN...

Страница 6: ...ath Read and understand the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Applications This is not an explosion proof heater No tube heat...

Страница 7: ...e floor Suspended or elevated heaters shall be located in spaces where they shall not be subject to damage by aircraft cranes movable scaffolding or other objects Provisions shall be made to assure ac...

Страница 8: ...in conjunction with this heater without careful consideration for and avoidance of inadvertent discharge hazards For further information consult NFPA 13 Always observe applicable provinces and local...

Страница 9: ...6 92 45 63 8 10 92 with 1 side shield 0 50 8 6 92 with 2 side shields 0 30 30 6 92 20 ft from burner 0 11 11 6 44 DES3 50 60 70 200 N P 0 41 41 6 94 45 63 8 10 94 with 1 side shield 0 54 8 6 94 with...

Страница 10: ...luate the mounting conditions vent locations gas supply and wiring When designing an infrared radiant heating system consider the following Has the building s heat loss been evaluated Does the design...

Страница 11: ...being mounted outside of the factory recommended mounting heights Model BTU Range Recommended Mounting Height ft Coverage Area Straight Config LxW Coverage Area U Tube Config LxW Distance Between Hea...

Страница 12: ...hanging points do not allow for the recommended spacing then additional hangers P N TP 19B may be necessary The spacing between the burner control box mounting brackets and the first hanger should be...

Страница 13: ...ension Point NOTE A yellow band identifying the combustion chamber s is located in the middle of the tube models 150 200 MBH Remove paper band before starting up heater Stainless Steel Tube Clamp 150...

Страница 14: ...t it is securely attached NOTE Threaded rod and turnbuckles may be used 6 Attach hangers to chains Adjust chain lengths until radiant tubing is level and equal weight distribution is achieved Chains m...

Страница 15: ...45 degree angle with two suspension points using two Brass Knuckles P N BK fittings 1 double loop chains and S hooks U Tubes can be mounted from a single suspension point using a Single Mounting Brac...

Страница 16: ...identification tag Figure 3 7 Attach Tube Clamps Hanger Welded Seam Faces Down Swaged End Tube Clamp Radiant Tube IMPORTANT 150 000 to 200 000 BTU h models must be installed with a stainless steel tub...

Страница 17: ...ds exhaust end NOTE If it is difficult to mate the tubes they may be installed incorrectly 4 Center tube clamps over the seam where two radiant tube sections connect If necessary rotate tube clamps so...

Страница 18: ...orrections require two 2 TR 60 packages Figure 3 10 Elbow and U Bend Clearances Dimension A U Bend can be set in both directions 12 Figure 3 11 U Bend and Elbow Dimensions Chart 3 4 Overall Dimensions...

Страница 19: ...ons for hanging the burner control box 2 Fasten beam clamp screw hook or other type of suspension anchor to hanging point 3 Attach S hook and chain assembly P N THCS to anchor Check that it is securel...

Страница 20: ...r level The reflector assembly depends on the heater configuration proximity to combustibles and space surrounding the heater Before you begin assembly determine if the use of reflector accessories ar...

Страница 21: ...rom becoming lodged PG between the radiant tube and reflector Required when mounting heaters below 8 ft Chart 3 5 Common Optional Accessories Reflector Accessory Description Part Number Reflectors can...

Страница 22: ...he tabs to the center of the keyhole and rotate the baffle 90 degrees to lock the baffle sections together 5 Repeat this process with all remaining baffle sections to complete assembly Figure 3 17 Ass...

Страница 23: ...20 Foot 50 Foot 60 Foot 30 Foot 40 Foot Stainless steel clamp location on 150 200 MBH models P N TP 220 Aluminized steel secondary combustion chamber location on 150 200 MBH models Stainless steel cla...

Страница 24: ...resistant galvanized steel of a thickness that meets the National Fuel Gas Code Minimum thickness for connectors varies depending on the pipe diameter Never vent the DES3 Series with PVC or plastic pi...

Страница 25: ...follow the vent manufacturer s clearance to combustibles The equivalent length for a 4 inch 90 elbow is 5 feet Avoid using more than two 90 directional changes in the venting system Horizontal sectio...

Страница 26: ...diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only be 2 inches greater than the vent pipe diameter If...

Страница 27: ...An appliance vented as a Category I is considered a fan assisted appliance and the vent system does not have to be gas tight It is recommended that the venting system is installed with a tee drip leg...

Страница 28: ...ise length e g If the vertical vent height is 10 feet the horizontal run is greater than 7 1 2 feet The vent terminates below 5 feet of the vent connection on the unit Seal vent pipes with high temper...

Страница 29: ...to prevent blockage by snow and protect building materials from degradation by flue gasses The vent cap must be a minimum of 6 inches from the sidewall of the building Vent must be a minimum of 36 in...

Страница 30: ...of the vent carrying system reduces the maximum common vent capacity by 10 Refer to NFPA 54 IFEC tables 11 2 and 11 3 for capacity The vent connector capacities allow for the use of two 90 directional...

Страница 31: ...ing both to function simultaneously The minimum clearance between the air intake and the exhaust terminal is 4 ft NOTE When installing in a U tube configuration use extra caution to separate vent gase...

Страница 32: ...ves degreasers paints paint removers lubricants pesticides etc are present in the atmosphere High humidity Contaminants such as sawdust welding smoke etc Negative building pressure Unusually tight con...

Страница 33: ...ints with metallic tape or silicone sealant Wrap the tape two full turns around the vent pipe Slope air intake pipe inch per foot upward or downward away from the unit Do not draw air from attic space...

Страница 34: ...therwise Contact the factory for further determination of air infiltration rates Figure 3 25 Outside Combustion Air Vertical Intake Side View Roof Listed Exhaust Cap 18 in Min Combustion Air Intake Ca...

Страница 35: ...he atmosphere High humidity Contaminants such as sawdust welding smoke etc Negative building pressure Unusually tight construction where there is an air infiltration rate of less than 0 40 per hour Ga...

Страница 36: ...appliances being connected to the supply line Check that the main gas supply line is of proper diameter to supply the required fuel pressures If utilizing used pipe verify that its condition is clean...

Страница 37: ...material an intermediate connection device that allows for the heater expansion must be used The gas outlet must be in the same room as the appliance is installed and must be accessible It may not be...

Страница 38: ...injury or death Test in accordance with CAN CSA codes 7 14 18cm 36cm 9 14 23cm 36cm 9 14 23cm 36cm Correct Method Wrong Method Side View Front View Side View Front View 9 14 23cm 36cm 9 14 23cm 36cm 9...

Страница 39: ...re allowances are made for this movement To ensure your safety and comply with the terms of the warranty all units must be installed in accordance with these instructions 3 0 Installation Gas Supply B...

Страница 40: ...he pressure NOTE All factory installed gas connections have passed an approved leak test For leak testing on pressures above 1 2 PSI When leak testing with pressures above 1 2 PSI 14 inches W C the un...

Страница 41: ...3 125 000 2 50 8 50 15 3 150 000 2 1 2 63 5 50 15 3 175 000 2 3 4 69 9 50 15 3 200 000 2 3 4 69 9 60 18 3 125 000 2 50 8 60 18 3 150 000 2 1 2 63 5 60 18 3 175 000 2 3 4 69 9 60 18 3 200 000 2 3 4 69...

Страница 42: ...NFPA 70 or Canadian Electrical code CSA C22 1 Part 1 9 9 The unit is properly mounted to a permanent structure able to bear the weight of the unit 9 9 The proper mounting height is observed for the ap...

Страница 43: ...nnel may install or service this equipment Not for residential use Do not use this heater in the home sleeping quarters attached garages etc Installation of a commercial tube heater system in resident...

Страница 44: ...when wiring tube heaters NOTE The transformer relay selected must be capable of handling the combined start up amperage per relay branch 24VAC Thermostat B R G To Heater Branch 2 To Heater Branch 1 P...

Страница 45: ...TCH ELECTRODE ASSEMBLY BK BK BK BK R W O W G W BK GAS VALVE BK W 45 DES3 Series 3 0 Installation Wiring Before field wiring this appliance Check existing wiring replace if necessary NOTE If any of the...

Страница 46: ...ld interfere with the proper air circulation or that violate the listed clearance to combustibles 9 9 Manual gas shut off is ON 9 9 Electrical power is ON 9 9 Thermostat is set to desired temperature...

Страница 47: ...he control senses and monitors burner flame through the electrode If sense of flame is lost the control immediately disrupts power to the gas valve and then re cycles the unit identical to the startin...

Страница 48: ...r physically damaged No Yes Replace igniter Yes No Find the source of the electrical problem Check the gap on the igniter Is the gap between 3 16 in and 1 4 in No Adjust gap Yes No Yes No During the i...

Страница 49: ...safety differential pressure switch The switch is a normally open switch and is located in the air chamber Temporarily place a jumper across the terminal of the switch Does the igniter spark Yes Yes...

Страница 50: ...s pressure ok Yes Make sure gas lines were purged of air and or correct pressure problems The following can cause the heater to shut down Improper grounding High winds Taking combustion air from the a...

Страница 51: ...lace electrode if needed No Check the gap on the igniter Is the gap between 1 8 in and 3 16 in Adjust gap No 5 0 Troubleshooting Guide Flame Current Check Single Spark Sense To measure flame current d...

Страница 52: ...sts for leakage damage fatigue corrosion and obstructions If dirt becomes a problem installation of outside air intake ducts for combustion is recommended Combustion air intake system when applicable...

Страница 53: ...53 DES3 Series This page was intentionally left blank...

Страница 54: ...cs TP 17 Sight Glass Kit TP 113 Tension Spring TP 19B 4 in Wire Hanger w Tension Spring TP 201B V 3 Mid Burner Color Code TAN TP 20C 10 ft Aluminum Reflector TP 204 Gas Orifice consult factory TP 20D...

Страница 55: ...3001 Divider Panel TP 3060 Pressure Switch Mounting Bracket TP 3002A Left End Panel TP 3072 Low BTU Burner Color Code GREEN TP 3003A Right End Panel TP 3093 8 32 Cage Nut Qty 4 TP 3004 Main Control Bo...

Страница 56: ...r consequential and incidental damages is expressly disclaimed Brant Radiant Heaters Limited s liability in all events is limited to and shall not exceed the purchase price paid Warranty Disclaimer Br...

Страница 57: ..._______________________________ ___________________________________________________________________________________ ___________________________________________________________________________________...

Страница 58: ...idential use This heater is NOT approved for use in any residential application This includes but is not limited to attached garages solariums living quarters etc Installation in residential spaces ma...

Отзывы: