background image

 

 

14698_r00 

7/18 

 
 
Once  the  heat  exchanger  has  been  suitably  cooled  (temperature 
measured  by  the  SR  heating  circuit  probe  lower  than  the  T

ON

  re-

ignition  temperature),  the  system  can  start  operating  normally 
again. 

 

Destratification gradient 

Spacious rooms can be subject to air stratification phenomena: hot 
air  tends  to  rise  above  creating  a  considerable  temperature 
difference between the comfort zone and the room ceiling. 

 

 

 

Higher temperature 

Lower temperature 

Comfort zone 

 

 

Fig. 7 – Air stratification phenomenon 

 

If  the  hot  air  generator  is  installed  in  a  high  position  and  an  SA 
local  room  temperature probe  is  used,  the  following  directions  will 
have to be observed for a correct room temperature adjustment: 

1)  place the SA probe next to the comfort zone for a correct 

room temperature detection (fig. 8a), or 

2)  use  the 

destratification  gradient  (0 

÷

  10°C),  which  will  be 

deducted  from  the  temperature  measured  where  the  hot 
air  generator  is  installed  in  order  to  calculate  the 
temperature of the comfort zone (fig. 8b). 

 

 

 

Comfort zone 

8a 

Generator 

Probe (SA) 

 

 

 

Comfort zone 

8b 

Generator 

Probe (SA) 

Destratification 
gradient 

 

 

Fig. 8 – Solutions for a correct temperature adjustment 

 

The  destratification  gradient  factory  setting  is  zero  (0°C):  different 
parameter values can be set up on request. 

 

!!!!

 

IMPORTANT NOTE 
This  parameter  can  be  modified  through  BRAHMA  serial  interface  type  810  and 
management software.

 

 

Outside temperature probe function 

As already mentioned before, the outside ambient temperature can 
contribute  to  the  system  temperature  adjustment  process:  in  fact, 
through a remote controller it is possible to reserve the SA input of 
the  control  unit  no.  "n"  (in  case  of  a  cascade  system)  to  this 
function,  enabling  all  units  to  adjust  the  modulation  power 
according to the outside temperature measured. 
 
TC340(P1) - OPERATION 
In  this  case,  the  device  is  used  for  the  ignition,  the  flame  control 
and  (if  available)  the  modulation  of  premix  burners  equipped  with 
fan with PWM control. 
To  better  understand  the  operation  of  the  system,  please  refer  to 
the operating cycle diagrams in the next pages. 
At  the  first  start-up,  the  device  is  in  stand-by  status  and  the  fan 
control is disabled (point 1). 
In case of heat demand (TC boiler thermostat closing, point 2), the 
device  performs  the  start-up  cycle,  carrying  out  the  TP  pre-purge 
time  at  TP1_speed  and  then  the  TP2  second  pre-purge  time  and 
the TS safety time at start-up speed (TP2_TS_speed, point 3). 
In  case  of  flame  signal  failure  at  the  end  of  the  safety  time,  the 
system goes to lockout; else, the system goes on (point 4) carrying 
out  the  modulation  delay  time  lasting  for  DELAY_RP_STAB  at 
RP_STAB_speed in order to settle the burner flame. 
At  the  end  of  this  phase  (which  can  be  set  up  to  "0"  if  it  is  not 
necessary),  the  device  enters  the  real  operation  stage  (point  5, 
running position), setting up the fan speed to the RP_speed value, 
which  can  be  increased  (point  7)  or  decreased  (point  9) 
dynamically through the IN(+) and IN(-) adjustment inputs within a 
range  limited  by  the  RP_MAX_speed  and  RP_MIN_speed  values 
(as  soon  as  these  two  values  are  reached,  as  shown  on  points  8 
and 10, the adjustment inputs do not affect the PWM output signal 
value). 
In running status, the output modulation power can be increased to 
a  predetermined  RP_T2_speed  value  by  means  of  the  T2 
adjustment input (point 6): this function can be used if the burner is 
provided with two flame stages or if you wish to obtain a temporary 
modulation “boost”. 
As soon as the heat demand stops (point 11), during operation the 
system can: 

− 

go to stand-by position; 

− 

proceed to post-purge at POST_speed (in case of option P or 

PT).

 

The  following  table  shows  the  modulation  parameters  of  the 
device, which can be pre-set and modified through serial interface. 
Upon  request  it  is  possible  to  mount  a  vertical  module  with 
microcontroller  technology  which  enables  to  set  up  three  of  the 
above-mentioned modulation parameters through a trimmer; these 
parameters  can  be  factory-set  and  can  be modified  through  serial 
interface and management software. 
 

No. 

Parameter 

Range 

Description 

TP1_speed 

1

÷

100 % 

PWM percentage during the first pre-purge time (TP1) 

TP2_TS_speed 

1

÷

100 % 

PWM percentage during the second pre-purge time (TP2) and the safety time (TS) 

RP_STAB_speed 

1

÷

100 % 

PWM percentage during the flame settlement time 

RP_STAB_delay 

0

÷

255 s 

Flame settlement time duration 

RP_speed 

1

÷

100 % 

PWM percentage during operation (RP), further to a flame settlement delay 

RP_MIN_speed 

1

÷

100 % 

Min. suppliable PWM percentage in case of decrease through the IN(-) input in running status  

RP_MAX_speed 

1

÷

100 % 

Max. suppliable PWM percentage in case of increase through the IN(+) input in running status  

VARIATION_delay 

0

÷

255 s 

Modulation ramp time to vary the PWM from 0% to 100% during operation 

RP_T2_speed 

1

÷

100 % 

PWM percentage during operation (RP) in case of T2 closing (boost function) 

10 

POST_speed 

1

÷

100 % 

PWM percentage during the post-purge time (if available) 

11 

POST_delay 

0

÷

255 s 

Post-purge time duration 

Содержание TC340

Страница 1: ... version for fan assisted appliances output for the control of an auxiliary electronic ignition transformer prearranged for the control of the EV2 second valve stage by means of two independent contacts taking the power supply from the EV1 first valve stage version for fan assisted appliances burner power modulation by means of a current modulator version for fan assisted appliances or through a P...

Страница 2: ...ute are insufficient in case a brushless fan is used premix versions 4 This parameter can be modified through BRAHMA serial interface type 810 and management software Max contact rating 240V 50Hz Hot air blower FAN 3 5 A cos ϕ 0 4 Burner motor EF 0 5 A cos ϕ 0 4 Remote ignition device ACC1 0 8 A cos ϕ 0 4 First valve stage EV1 0 4 A cos ϕ 0 4 6 Second valve stage EV2 0 4 A cos ϕ 0 4 6 Current modu...

Страница 3: ...damper STF This input option S enables to check the status of the fire damper contact in case this contact is open anomaly condition the ignition cycle is interrupted and the device goes to stand by position signalling the failure through a LED The behaviour of the device in case the fire damper contact is open can be customized upon request Overall dimensions Fig 3 shows the overall dimensions of...

Страница 4: ...ditional BRAHMA device type TC340 in case of cascade systems The control unit starts the ignition cycle by checking the air pressure switch status fan assisted version or the number of revolutions per minute of the EF burner motor premix version In case no signal is detected the system starts the EF fume extractor at its max speed as soon as the air pressure switch goes to air flow position fan as...

Страница 5: ... the power supplied to the EF fume extractor to the FAN hot air blower and to the current modulator s according to the min and max pre set values Fig 5 shows the three types of temperature adjustment available in the system Outside temp probe SE available Temperature adjustment by an OUTSIDE PROBE The system type TC340 directly manages the temperature adjustment by calculating the required percent...

Страница 6: ...vironment and the FAN hot air blower can therefore be activated If the heat exchanger temperature exceeds the TV ventilation temperature threshold during the switch on delay time the activation of the FAN hot air blower will be anticipated as the system will have already reached suitable conditions for the environment heating A similar operation is carried out during the heat exchanger cooling pha...

Страница 7: ...e at start up speed TP2_TS_speed point 3 In case of flame signal failure at the end of the safety time the system goes to lockout else the system goes on point 4 carrying out the modulation delay time lasting for DELAY_RP_STAB at RP_STAB_speed in order to settle the burner flame At the end of this phase which can be set up to 0 if it is not necessary the device enters the real operation stage poin...

Страница 8: ...Option 16 G GP air pressure switch checking Option G available in the devices type TC340A enables the control unit to start the ignition cycle without checking the air pressure switch option GP available in the devices type TC340P and TC340P1 allows the air pressure switch checking during the pre purge stage and at start up only Option 17 Jnn pre ignition time The transformer is switched on at the...

Страница 9: ... letter recycling without lockout Standard mode 11 R immediate lockout see OPERATING CYCLE VARIATIONS paragraph Flame failure in running status No letter recycling Standard mode 12 V immediate lockout Post purge of the burner motor EF No letter no post purge Standard mode Pnn the post purge is settable upon request and cannot be interrupted in case of heat demand restoration see OPERATING CYCLE VA...

Страница 10: ...D with flame signal on X at the end of the safety time 23 Wnn during operation after nn seconds from the end of the safety time FAN hot air blower switch on delay tFA for TC340A and TC340P versions only 24 RAnn hot air blower switched on after nn seconds from the end of the safety time FAN hot air blower switch off delay tFS for TC340A and TC340P versions only 25 RSnn hot air blower switched off a...

Страница 11: ... 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 F1 F2 2 1 2 1 PE FAN2 PE Key to symbols GA1 Chronothermostat type ENCRONO GA1 SR Heating circuit probe EF Burner motor SA Room temperature probe optional FAN Hot air blower APS Air pressure switch FAN2 Second hot air blower STF Fire damper ACC1 Remote auxiliary ignition transformer SL LED signalling ACC2 Inbuilt ignition transformer RESET Reset push button EV1 First ...

Страница 12: ... 5 6 1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 F1 F2 2 1 2 1 PE FAN2 PE Key to symbols GA1 Chronothermostat type ENCRONO GA1 STF Fire damper EF Burner motor SA Room temperature probe optional FAN Hot air blower SL LED signalling ACC1 Remote auxiliary ignition transformer RESET Reset push button EV1 First valve stage EX Connection for cascade appliances SR Heating circuit probe IO...

Страница 13: ...2 1 2 1 2 3 1 FAN2 PE PE Key to symbols GA1 Chronothermostat type ENCRONO GA1 SA Room temperature probe optional EF Burner motor APS Air pressure switch FAN Hot air blower STF Fire damper ACC1 Remote auxiliary ignition transformer SL LED signalling ACC2 Inbuilt ignition transformer RESET Reset push button EV1 BRAHMA valve type VCM01 0 P 0 P 24VDC EX Connection for cascade appliances SP VCM01 valve...

Страница 14: ... P3 J3 M Nota 2 PE PE J13 IN IN Key to symbols TC Heat demand room thermostat N1 Three point adjuster T2 Adjustment thermostat BOOST function SL LED signalling EF Burner motor RESET Reset push button ACC1 Remote auxiliary ignition transformer EX Connection for cascade appliances ACC2 Inbuilt ignition transformer ION Ionization electrode EV1 First valve stage NOTES 2 Vertical module for setting up ...

Страница 15: ...CASCADE CONNECTION OF SEVERAL DEVICES THROUGH OpenTherm Nota 1 N L PE J12 J12 J12 MASTER SLAVE 1 SLAVE 2 SLAVE n NOTES 1 The cascade connection is possible also by a contact chronothermostat This configuration is not used in TC340P1 versions ...

Страница 16: ...9 Modulator MOD power supply connector 2 pin connector type LUMBERG 3114 series terminals type LUMBERG 3111 01 L series J10 Heating circuit probe SR and room temperature probe SA 6 pin connector type LUMBERG 3114 series terminals type LUMBERG 3111 01 L series J11 Air pressure switch APS or PWM control brushless fan low voltage signals 7 pin connector type LUMBERG 3114 series terminals type LUMBERG...

Страница 17: ...OTES the EV2 second valve stage if available depending on option no 23 may be activated in a different moment in comparison to what appears in the diagrams in these specific cases option X the modulation circuit may not be available depending on the type of device and on option no 28 at the end of the heat demand a post purge on the EF burner motor may be performed depending on option no 13 ...

Страница 18: ...OTES ABOUT PRODUCT DISPOSAL The device contains electronic components and cannot therefore be disposed of as normal household waste For the disposal procedure please refer to the local rules in force for special waste BRAHMA S p A Via del Pontiere 31 37045 Legnago VR ITALY Tel 39 0442 635211 Fax 39 0442 25683 http www brahma it E mail brahma brahma it 19 11 10 Subject to amendments without notice ...

Отзывы: