                                                                       9                                                                    Installer Guide

The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer 
Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These 
settings are indicated below with comments. More detail on each setting follows this table.

1.  Touch and hold down the 

SYSTEM

 and 

CONFIG

 TouchPads for 3 seconds.

2.  Release both buttons and the first installer setting will be displayed.
3.  Change settings as required using the 

UP

 or 

DOWN

 portion of the SpeedBar

®

.

4.  Touch 

NEXT

 or 

BACK

 to move to the next or previous setting, touch 

RETURN

 to exit.

No.   Installer Setting 

Factory   

Setting 

Comments

     (

Notes follow this table)

   Default 

Options

 

(More information follows this table)

 1    Residential or 

RES 

RES

 

 Select for Residential profile

     or Commercial Profile 

      

COMM

 

 Select for Commercial profile

 2    Programming Mode 

7 PROG 

7 PROG

 

 Select for 7 day programming mode

    

[note 1]

 

      

52 PROG

 

 Select for 5-2 day programming mode

       

 

      

NO PROG

 

 Select for non-programmable mode

 3    Clock Format 

12 HR 

12 HR

 

 Select for 12 hour clock

       

 

      

24 HR

 

 Select for 24 hour clock

 4    Temperature Scale 

F DEG 

F DEG

 

 Select for Fahrenheit display

       

 

      

C DEG

 

 Select for Celsius display

 5    Auto Changeover 

oF AUTO 

oF AUTO

 

 Disables Auto Changeover mode

       

 

      

ON AUTO

 

 Enables Auto Changeover mode

       

 

      

11CONV

 

 Select for 1H/1C Conventional system

       

 

      

22CONV

 

 Select for 2H/2C Conventional system

 6    System Type 

11CONV 

11HP

 

 Select for 1H/1C Heat Pump system

       

 

      

22HP

 

 Select for 2H/2C Heat Pump system

       

 

      

32HP

 

 Select for 3H/2C Heat Pump system

 7    1st Stage Differential 

0.5 DIF1 

0.5, 1.0

 or  

 Select a 1st stage temperature differential of .5°,

       

 

      

2.0 DIF1

 

 1° or 2° F (.25°, .5° or 2° C)

 8    2nd Stage Differential 

2.0 DIF2 

1.0, 2.0, 3.0, 

   Select a 2nd stage temperature differential of 1°, 

    

[note 2]

 

      

4.0, 5.0

 or  

 2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C)

       

 

      

6.0 DIF2

 9    3rd Stage Differential 

2.0 DIF3 

1.0, 2.0, 3.0, 

  Select a 3rd stage temperature differential of 1°, 2°, 

    

[note 2]

 

      

4.0, 5.0

 or  

3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3°C) 

       

 

      

6.0 DIF3

10  1st Stage Fan Control 

HG FAN 1 

HG FAN 1

 

Select for 1st stage Gas heating

  

[note 3]

 

  

HE FAN 1

 

Select for 1st stage Electric heating

11  Emergency Heat] 

HE EMER 

HE EMER

 

Select for Electric Emergency Heat

   

Fan Control 

[note 4]

 

  

HG EMER

 

Select for Gas Emergency Heat

12  Reversing Valve 

REVO 

REVO

 

Select for cool active Reversing Valve (O terminal)

   

(O/B Terminal) 

[note 5]

    

REVB

 

Select for heat active Reversing Valve (B terminal)

4

Installer Settings

Содержание 7320

Страница 1: ... 2 Cool Heat Pump Up to 2 Heat 2 Cool Conventional with wireless Humidity Control Warning For installation by experienced service technicians only This thermostat is compatible with Single stage heat cool conventional and heat pump systems Conventional systems up to 2 stages of heating and 2 stages of cooling Heat pump systems up to 3 stages of heating and 2 stages of cooling Electrical and contro...

Страница 2: ... appliances concealed pipes chimneys and outside walls Installer Guide 2 Install your new Braeburn thermostat in 4 basic steps 1 Install the Sub Base 2 Provide Power 3 Connect Your Wires 4 Attach Thermostat to Sub Base Install the Sub Base Remove the sub base from the body of the thermostat Mount the sub base as shown below Warning Disconnect power before beginning installation 2 Installation and ...

Страница 3: ...ing this thermostat to a Wi Fi network a 24 VAC common C wire is required Batteries Installed as Shown Terminal Function Description Rc Input 24 Volt AC Cooling Transformer Dual Transformer Systems Only Rh Input Power Connection 24 Volt AC Heating Transformer C Input 24 Volt AC Transformer Common W2 AUX Output W2 2nd Stage Conventional Heat AUX Auxiliary Heat Heat Pump W1 E Output W1 1st Stage Con...

Страница 4: ... cooling transformer 4 If needed for system Provide disconnect and overload protection as required 2 HEAT 2 COOL Single or Dual transformer Set System Type to 22CONV Rh 24 Volt AC Power heating transformer note 2 Rc 24 Volt AC Power cooling transformer note 2 W1 Heat Relay Stage 1 W2 Heat Relay Stage 2 Y1 Compressor Relay Stage 1 Y2 Compressor Relay Stage 2 note 4 G Fan Relay C 24 Volt AC Transfor...

Страница 5: ...oling W2 Auxiliary Heat Relay 2nd stage heating note 3 E Emergency Heat Relay note 3 G Fan Relay C 24 Volt AC Transformer Common note 1 L Optional System Fault Monitor note 4 2 HEAT 2 COOL No Auxiliary Heat Set System Type to 32HP Rh 24 Volt AC Power Rc Connected to Rh with supplied Jumper Wire O B Changeover Valve note 2 Y1 Compressor 1 Relay 1st stage heating cooling Y2 Compressor 2 Relay 2nd st...

Страница 6: ...body with the sub base 2 Carefully push the thermostat body against the sub base until it snaps in place NOTE Additional options are configured in the Installer Settings section S1 S2 A Economizer Fresh Air or Output Control K Share a WireTM Module note 2 NOTES Additional Wiring Options 1 Can be used to connect a Braeburn indoor or outdoor wired remote sensor 2 Can be used to share a wire on exist...

Страница 7: ...Indicator Displays information about the status of the system Hold Mode Indicator Indicates if the thermostat is in HOLD mode Low Battery Indicator Indicates when the batteries need to be replaced Wi Fi Wireless Indicator Indicates when connected to Wi Fi wireless flashes when connection has been lost Fan Indicator Indicates when the system fan is running Quick Reference Instructions Stored in slo...

Страница 8: ...Selects programming mode or press for 3 seconds to select SpeedSet mode HOLD Enters Exits the HOLD mode program bypass DAY TIME Sets the current time and day of the week BACK Moves back in setting and programming modes NEXT Moves forward in setting and programming modes RETURN Returns to normal mode from program or settings modes CONFIG Enters the User and Installer settings modes HUMID Displays o...

Страница 9: ...r clock 4 Temperature Scale F DEG F DEG Select for Fahrenheit display C DEG Select for Celsius display 5 Auto Changeover oF AUTO oF AUTO Disables Auto Changeover mode ON AUTO Enables Auto Changeover mode 11CONV Select for 1H 1C Conventional system 22CONV Select for 2H 2C Conventional system 6 System Type 11CONV 11HP Select for 1H 1C Heat Pump system 22HP Select for 2H 2C Heat Pump system 32HP Sele...

Страница 10: ...5 Select a Dead Band of 2 3 4 or 5 F Dead Band note 10 BAND 1 2 or 3 C for Auto Changeover mode 23 Compressor Balance NO BALC NO BALC Disables Balance Points Point notes 4 10 0 50 BALC Select a Compressor Balance Point of 0 50 F 18 10 C 24 Auxiliary Heat Balance NO BALA NO BALA Disables Balance Points Point notes 4 10 70 40 BALA Select a Auxiliary Heat Balance Point of 70 40 F 21 4 C 25 Economizer...

Страница 11: ... selected the system automatically switches between heating and cooling modes There is a 5 minute delay when switching from heating to cooling or cooling to heating in auto changeover mode NOTE Also see Auto Changeover Dead Band in option 22 6 System Type Selects the system type for your installation NOTE Changes made to this option will reset options 7 through 14 back to their default values depe...

Страница 12: ...SENS NOTE This option does not apply to the Braeburn outdoor sensor When an outdoor sensor is connected wired or paired wireless the thermostat automatically recognizes it and no further configuration is necessary 21 Lockout Security Level Selects the level of keypad lockout when the thermostat is locked Level 2 locks the entire thermostat including the front reset button Level 1 locks everything ...

Страница 13: ... humidity set point limit to auto AUTO or manual MAN When AUTO is selected humidity control is provided automatically based on the outdoor temperature Selecting MAN allows you to manually control the level of humidity 30 Dehumidification note 12 For use with an external dehumidifier Select between dehumidification disabled OFF a normally inactive NI or normally active NA relay depending on the req...

Страница 14: ...You cannot mix wired and wireless remote sensors of the same type i e mixing an indoor wireless remote sensor and an indoor wired remote sensor Replacing a Thermostat If you are replacing a thermostat that is paired with an existing wireless sensor you will need to clear the remote sensor and pair it again with the newly installed thermostat 1 Install the new thermostat 2 On the wireless remote se...

Страница 15: ...L mode of operation if the outside temperature is below 50º F 10º C This could possibly damage the controlled cooling system and may cause personal injury This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling When testing the system make sure to take this delay into account NOTE The compressor delay can be bypassed by pre...

Страница 16: ...asures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Equipment interface module thermostats and outdoor sensor To comply with FCC and Industry Canada RF exposure limits for ...

Отзывы: