Installation
Step 1: Install mounting bracket to
wall
NOTE: Make sure that, when mounted, the
eye wash unit will measure 33-45 inches from
the top of the sprayheads to the finished floor.
For usage as an eye/face wash, the top of the
sprayheads of the S19-630 must be 33–45
inches from where the user stands per ANSI
Z358.1. The unit must also be placed a
minimum of 6" away from the nearest wall or
obstruction.
1. Install three suitable wall anchors for use
with 3/8" bolts (supplied by installer) into
the wall at the desired location (see
Figure 1a for eye wash dimensions and
Figure 1b for bracket dimensions).
2. Bolt the mounting bracket to the wall
using three 3/8" bolts (supplied by
installer).
Step 2: Assemble eye/face
body wash unit
1. Assemble the component parts as
shown in Figure 2 on page 4.
• Be sure to apply pipe sealant to
all pipe joints.
Step 3: Connect water supply
1. Connect the water supply to the
unit (piping supplied by
installer).
2. Mount the safety sign to the wall
using the sign-mounting
hardware supplied by installer.
3. Open the water supply line. Test
for leaks and adequate water
flow.
3
Installation
S19-630
Bradley Corporation • 215-085 Rev. K; EN 06-532D
4/30/07
10-3/4"
(273mm)
8-3/4"
(222mm)
15"
(381mm)
33-45"
(838-1143mm)
TO FINISHED
FLOOR
Figure 1a
2"
(51mm)
2"
(51mm)
4"
(102mm)
2"
(51mm)
4-
3
/
8
"
(111mm)
7/
8
"
(22mm)