Bradley S19-320B Скачать руководство пользователя страница 4

4

S19-320B, S19-320E

 

Installation

11/17/08 

Bradley Corporation • 

215-693B Rev. F; ECN 07-512A

Installation

Supplies Required:

•  Teflon tape or pipe sealant
•  Black, white and green AWG 14 wire to connect alarm to 

electric power supply

•  1/2" conduit and 1/2" x 3/4" adapter bushing for electric 

power supply wiring

Step 1: Install the flow switch in the water 
supply line

NOTE: The flow switch will attach to the mounted alarm via 
a 6-foot waterproof cable. Keep the location for mounting 
the alarm in mind when choosing the flow switch location.

1.  Choose a location for mounting the flow switch in a 

horizontal run of the water supply line. The inlet and 
outlet ports of the flow switch must be a minimum of 
6 inches from any tees or elbows in the water supply 
line.

2.  Mount the flow switch assembly in the water supply 

line.

•  The switch body must be in the vertical position with 

the water pipe horizontal.

•  The water flow must be in the direction marked by 

the arrow on the flow switch body.

•  Use teflon tape or pipe sealant (supplied by 

installer) on all water pipe connections.

Step 2: Mount alarm assembly to unit

NOTE: Point the alarm speaker in the direction from which 
help is most likely to come.

1.  Choose a location for mounting the alarm assembly. 

The alarm should be mounted at least 7 feet above 
ground level for best visibility.

•  The alarm may be mounted directly to the drench 

shower piping using the supplied U-bolts and nuts.

•  The alarm can also be bolted to a flat surface such 

as a wall (hardware for this type of installation is 
NOT supplied).

Step 3: Connect alarm to flow switch

1.  Connect the flow switch to the alarm by plugging the 

prewired cable into the socket provided in the flow 
switch junction box. The plug and socket have an 
alignment pin and groove which makes for error-free 
hook-up.

NOTE: To prevent water condensation from dripping onto 
the flow switch, make sure the cable is not taut.

2.  Tighten the locking collar on the female cable socket 

by rotating it clockwise after plugging in. This makes a 
good watertight connection.

Step 4: Complete electrical supply 
connections

1.  Connect the 24 volt AC power to the Alarm System 

(using the red and black wires only) in the 6- or 12-foot 
power cable provided. Test the alarm system.

Alarm

To 

Water 

Supply

Flow 

Switch

To 

Electric 

Power

Отзывы: