S59-4016 Series 

Navigator

®

 Thermostatic 

Mixing Valve

S59-4016D 

½

" NPT/Sweat Connections

S59-4016X 

½

" PEX Connections

S59-4016N 

¾

" NPT Connections 

S59-4016S 

¾

" Sweat Connections

S59-4016Y 

¾

" PEX Connections

Table of Contents

Supplies and Tools Required   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .3
Installation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .3
Maintenance and Troubleshooting   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .4
Assembly of Components and Parts List  .  .  .  .  .  .  .  .  .  .  .  .  .  .5

Temperature Range: 59 – 140°F 
Maximum Pressure: 125 PSIG
Inlet Temperature, Hot: 120 – 180°F
Inlet Temperature, Cold: 33 – 80°F
Minimum Temperature Differential (from valve set point): 10°F

S59-4016N

S59-40016Y

®

ASSE 1017, 1069, 1070 &cUPC certified

Содержание Navigator S59-4016 Series

Страница 1: ...6X PEX Connections S59 4016N NPT Connections S59 4016S Sweat Connections S59 4016Y PEX Connections Table of Contents Supplies and Tools Required 3 Installation 3 Maintenance and Troubleshooting 4 Assembly of Components and Parts List 5 Temperature Range 59 140 F Maximum Pressure 125 PSIG Inlet Temperature Hot 120 180 F Inlet Temperature Cold 33 80 F Minimum Temperature Differential from valve set ...

Страница 2: ...maximum life and proper product function Periodic Inspection and Yearly Maintenance by a licensed contractor is required Corrosive water conditions and or unauthorized adjustments or repairs could render the valve ineffective for its intended service Frequency of cleaning and inspection depends upon local water conditions IMPORTANT Read this entire installation manual to ensure proper installation...

Страница 3: ...1 Connect Supply Lines DO NOT solder with inlet and outlet tubes attached to the valve Excessive heat will damage the rubber and plastic components of the valve Pipe supports must be placed a minimum of 16 away from valve DO NOT overtighten unions Adjustable Wrench Phillips Head Screwdriver This valve is NOT factory preset Upon installation the temperature of this valve must be checked and adjuste...

Страница 4: ...and reopen the valves after inspection and repair is complete Problem Cause Solution External leaks Damaged cartridge or O rings Replace cartridge with part number 269 2000S Improper water temperature or temperature fluctuation Hot water supply is not 10 above desired set point Increase hot water supply temperature Valve temperature is not properly set Adjust the temperature as shown on page 2 ste...

Страница 5: ...1 1 1 1 1 5 198 015 Check Valve 2 2 2 2 2 6 132 055 Retaining Ring 2 2 2 2 2 7 125 001CP Rubber Washer 3 3 3 3 3 8 146 081 U Clip 1 1 1 1 1 9 110 245 Tailpiece Nut 3 3 3 3 3 10 S45 2456 Mounting Bracket Kit optional 1 1 1 1 1 11 129 067 Sweat Tailpiece 3 12 129 068 NPT Sweat Tailpiece 3 13 129 066 NPT Tailpiece 3 14 129 070 PEX Tailpiece 3 15 129 069 PEX Tailpiece 3 Included with Prepack S65 380 1...

Отзывы: