Installation
EFX 60/S19-2200
Bradley
• 215-1289 Rev. P; ECN 18-09-005
2/26/2018
5
Connect Supply Lines and Install Thermometer
Adjust Temperature with Water Running
When the check valves are in
the open (opera ting) position,
the cover screw for the stop/
check stem will be flush with
the valve cap.
Check for leaks by
pressurizing unit SLOWLY.
Install Thermometer using
pipe sealant or teflon tape.
Check the temperature when approximately
10 GPM water flow is reached (equivalent to
two face washes)
Slotted Cover
Screw
Stop/Check
Cover Screw
Check
Stop Nut
Water Recirculation
Plug
Thermometer
Tempered Water
(to Fixture)
HOT
COLD
Test Unit
Shut the hot water supply off by closing hot water inlet valve or supply check valve. While the hot water supply is turned off,
check to make sure the cold water continues to flow. If the cold water is flowing properly, reopen the hot water supply.
Shut the cold water supply off by closing the cold water inlet valve or supply check valve. While the cold water supply is off,
check to make sure that the hot water flow has shut down. If hot water is shut down, reopen cold water supply. Test unit
weekly for proper function and desired set temperature.
DO NOT SKIP THIS STEP!!!
This device must be checked for final temperature and
adjusted as necessary. The standard preset factory
temperature setting is 85°F (29°C). [the range of the valve
is 65°F – 95°F (18°C – 35°C)]. Consult proper medical
and/or safety authorities for the optimum temperature
recommended for your particular application.
2
3
4
Slotted
Cover
Screw
Temperature
Set Screw
C
H
5/32" Allen Wrench