Figure 7
THROUGH THE WALL VENTING:
Cut a 2 1/2 in.
(6.4 cm)
diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 45° vent terminal provided with the water heater to the vent connector. The
distance between the edge of the 45° vent terminal and the exterior wall (see
Figure 8) must be at least 1 in.
(2.5 cm)
. Use the proper cement and assembly
procedures to secure the vent connector joints between the terminal and the
blower outlet. Provide support brackets for every 3 feet
(.91 m)
of horizontal vent.
Figure 8
Venting (Part II) continued-