Non-Simultaneous Operation

Non-Simultaneous Mode:

 Allows only one heating element to operate at a time. For example, when the tank is cold,

the upper element is energized first, heating the top of the tank. Only when the upper thermostat is satisfied, the upper

element is de-energized and power is directed to the lower thermostat, energizing the lower element and heating the

bottom portion of the tank until the lower thermostat is satisfied. As hot water is drawn off the tank, it is replaced with

cold water delivered through the dip tube to the bottom of the tank. When the tank cools at the lower thermostat level,

the thermostat will call for heat energizing the lower element. If enough hot water is drawn from the tank, the top portion

of the tank cools and the upper thermostat will call for heat, de-energizing the lower element and allowing only the top

element to energize until the upper thermostat is satisfied.
The lower thermostat in the solar water heater is located above the internal heat exchanger.  This design allows the heat

exchanger to be in cooler water during short draws, providing more heat transfer from the solar heating system.

SEQUENCE OF OPERATION

Sequence of Operation-

 Double Element, Non-Simultaneous Operation, Single Phase.

Line voltage is applied across terminals

L1 & L3 of the upper thermostat. ECO is

closed, so there is voltage at terminal L4

and to one side of the upper and lower

elements.
Tank is cold. Therefore, the  thermostats are closed

at terminals T2 & 2 (calling for heat). The circuit is

complete through the upper thermostat only,

allowing current to flow through the upper element.

1

2

1

2

ECO

Closed

Thermostat closed

at terminal T2

When the upper thermostat is satisfied, it opens at

terminal T2, interrupting current flow through the

upper element. Terminal T4 closes, allowing voltage

to pass to terminal 1 of the lower thermostat. This

completes the circuit through the lower thermostat

and allows current flow through the lower element.

3

3

Thermostat closed

at terminal T4

4

Thermostat open

between terminals

1 and 2

Upper

T’stat

Upper

Element

Upper

T’stat

Upper

Element

Lower

T’stat

Lower

Element

Lower

T’stat

Lower

Element

When the lower thermostat is satisfied, it opens at

terminal 2, interrupting current flow through the

lower element. The system is now in stand-by mode

waiting for the next call for heat

4

The lower thermostat/element

combination will generally

cycle on and off more often

then the upper. In some cases,

such as a cold tank or in high

demand periods, the

upper thermostat will

call for heat (opening at

terminal T4 and closing at

terminal T2) prior to the lower

thermostat being satisfied. This

will interrupt current flow

through the lower thermostat

and element and allow current

to flow through the upper

element only. When the upper

thermostat is satisfied, it

resumes operation as

described in sequence #3

above.

5

5

Thermostat closed

between terminals

1 and 2

Upper

T’stat

Upper

Element

Lower

T’stat

Lower

Element

Upper

T’stat

Upper

Element

Lower

T’stat

Lower

Element

Upper

T’stat

Upper

Element

Lower

T’stat

Lower

Element

Thermostat closed

at terminal 2

Thermostat closed

at terminal T2

Page 5

Solar water heaters with double electric element backup are designed to operate using a single operating mode detailed

as follows:

5

Содержание S-SW2-115R6DS

Страница 1: ...7 00A SERVICE MANUAL Troubleshooting Guide and Instructions for Service To be performed ONLY by qualified service providers Models Covered by This Manual S SW2 60R6DS S SW2 75R6DS S SW2 115R6DS Solar...

Страница 2: ...hould be directed to the system installer or directly to the system component manufacturer System components include such items as the solar controller solar collector and circulator The text and illu...

Страница 3: ...s Example 4500W 240V 18 75A Volts Watts Amps x Volts Example 18 75A x 240V 4500W Ohms Volts Example 240V 4500W 12 8 Ohms Watts 2 2 Commonly Used Formulas Page 3 Wattage Limitation at 240 Volts Solar W...

Страница 4: ...tank Surface mounted thermostats respond to tank surface temperatures to sense a call for heat set point temperature settings and high limit ECO activation It is important that the entire back surfac...

Страница 5: ...er thermostat only allowing current to flow through the upper element 1 2 1 2 ECO Closed Thermostat closed at terminal T2 When the upper thermostat is satisfied it opens at terminal T2 interrupting cu...

Страница 6: ...some cases there may not be enough current draw for the circuit breaker to open This will allow the heating element to be in continuous operation resulting in over heated water limited only by the ECO...

Страница 7: ...e as needed 4 Check terminal block of element for proper voltage and wattage rating 1 Position thermostat flush with tank surface 2 Check heating elements Replace as needed 3 Adjust thermostats to des...

Страница 8: ...see illustration 3 A Rated Voltage IS present ECO is okay B Rated voltage NOT present proceed to step 2 2 Turn power OFF to water heater and firmly press ECO reset button on thermostat Turn power ON...

Страница 9: ...posure Be sure power is turned OFF to water heater prior to performing this procedure Testing For Heating Element Short Circuit To Ground Step 1 TURN OFF POWER TO WATER HEATER Step 2 Remove access cov...

Страница 10: ...ter 1 This procedure assumes line voltage ECO and elements are in working order 2 Turn power ON to water heater and set multi meter to Volts AC 3 Adjust temperature setting of upper thermostat to the...

Страница 11: ...ARNING Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing Page 11 SERVICE PROCEDURE RE III Thermostat Testing Water Temperature In Tank Is Above...

Страница 12: ...thermostat down into thermostat bracket until it snaps into place IMPORTANT Thermostat must set completely flat or flush to tank surface An improperly installed thermostat will cause improper water he...

Страница 13: ...ck see illustration below 2 Apply new element gasket to the new element Be sure gasket is seated flat against element flange without rolls or gaps see illustration below 3 Clean any debris from elemen...

Страница 14: ...d turn power ON to water heater Dip Tube Inspection and Replacement WARNING Heater components and stored water may be HOT when performing the following steps in this procedure Take necessary precautio...

Страница 15: ...g 6 Hot Water Outlet Anode 7 Cold Water Inlet Dip Tube 8 Access Cover 9 Thermostat Protector Large 10 Heating Element 11 Thermostat Mounting Bracket 12 Thermostat w High Limit 89T33 13 Element Gasket...

Страница 16: ...Email parts bradfordwhite com techserv bradfordwhite com www bradfordwhite com...

Отзывы: