Page 7
MASCOT LX
1346-NH
Service Mode
(30 min time out)
• Set firing rate in
percentage and
RPM.
• Pressing Up or
Down buttons
allows user to
adjust fan speed to
maximum or
minimum input
allowing
adjustment of CO2
Service Mode
(press and hold Select
button to exit)
Press
Select
Button to
toggle
between
High and
Low Fire
Measuring and Adjusting CO2
GAS TYPE C02 (%) RANGE
Natural 8.8-9.8
Propane 9.8-10.8
High
Fire
Setting
Low Fire
Setting