Bradford White ECO-DEFENDER U130S*FRN Скачать руководство пользователя страница 5

Page 5

LED Status

Control Status

Probable Cause

Service Procedure

None (LED not on

or flashing)

Gas valve is operating 

normally. Pilot flame

may not be present.

Check for pilot flame

through sight glass and 

light if necessary.

1. Gas valve is

functioning normally

2. Gas valve is not

powered. Light pilot

If the pilot will not stay lit 

replace thermopile, see 

page 10. If problem

persists replace gas

valve, see page 16.

One flash and 

three second

pause.

If set point knob is in

"PILOT" position then

pilot flame is detected.

Turn set point knob to

desired setting

Gas valve is powered 

and waiting for the set 

point knob to be turned 

to a water temperature 

setting. 

Normal operation. Adjust

thermostat to desired 

temperature level.

LED on

continuously.

Set point knob has

been recently turned to

the "OFF" position. 

Wait until LED goes out

before attempting to

relight

Set point knob was 

turned to "OFF"

position.

LED will go out and the 

control will function

normally when the pilot is

lit. 

Two flashes and 

three second

pause.

Weak pilot flame 

detected. System will

reset when pilot flame 

is sufficient. 

1. Thermopile failure      

2. Unstable pilot.             

3. Pilot tube block or

restricted.                        

4. Resettable thermal

switch has opened.

1. See page 10.

2&3. See page 12.

4. See page 21.

Three flashes and 

three second

pause.

Insufficient water 

heating. System will

reset.

1. Thermowell sensor

and chamber

temperature sensor out

of calibration.

2. Possible short.

1&2. See pages 14 and 

18.

Four flashes and 

three second

pause.

Excessive tank

temperature. System

must be reset.

1. Thermowell sensor

out of calibration.

2. Faulty gas valve.

1. See page 14.

2. See page 16.

Observe red LED indicator on 

gas control. Error flash codes are 

displayed with a three second 

pause before repeating. Check 

and repair the system as noted in

the troubleshooting table below. 

Gas Control Troubleshooting

Red LED 

Indicator

5

Содержание ECO-DEFENDER U130S*FRN

Страница 1: ...ers Save this manual for future reference Manual 47132A The Bradford White R U150L FRN U1504S FRN U430T FRN U440T FRN U4403S FRN U4503 FRN U1XR403S FRN Denotes Warranty Years U130T FRN U130S FRN U140T...

Страница 2: ...0 ED II Pilot Assembly Inspection Cleaning and Replacement 12 ED III Igniter and Electrode Testing and Replacement 13 ED IV Gas Control Replacement Thermal Well and Chamber Door Sensor Testing and Rep...

Страница 3: ...s Additional air is drawn through the openings in the jacket This air travels down and around the combustion chamber and enters through holes in the bottom of the corrosion resistant combustion chambe...

Страница 4: ...al values The meter you select must have the capability to measure volts AC volts DC Amps micro amps and ohms Electronic Probes In some cases standard multi meter probes will damage or simply not be e...

Страница 5: ...ut before attempting to relight Set point knob was turned to OFF position LED will go out and the control will function normally when the pilot is lit Two flashes and three second pause Weak pilot fla...

Страница 6: ...Possible electrical short See page 18 Seven flashes and three second pause Gas valve electronic fault detected 1 Control needs to be reset 2 Control is wet or physically damaged 1 Turn gas control kno...

Страница 7: ...e piece g Remove burner and inner door and inspect per step 4 Step 4 Fully inspect burner and inner door gaskets for the following Tears Other imperfections that will inhibit proper seal Missing Mater...

Страница 8: ...ws with the built in washer to secure the left side of the burner door in place DO NOT OVER TIGHTEN SCREWS Step 9 Position thermopile wires pilot tube and igniter wire against burner door flange gaske...

Страница 9: ...e to resettable thermal switch See photo in step 3 Note the white wire needs to be connected to the thermal switch and the red wire needs to be connected to the red wire from the thermopile Step 13 Re...

Страница 10: ...fe the thermopile should be replaced with a genuine Honeywell thermopile BWC P N 233 47063 00 CLOSED CIRCUIT THERMOPILE TESTING Honeywell Control SERVICE PROCEDURE ED II Thermopile Testing and Replace...

Страница 11: ...ten the nut to the pilot bracket 7 16 wrench Position thermopile wire against left side inner door flange at its original position Connect the red thermopile wire to the red lead from the wire harness...

Страница 12: ...the pilot must be replaced Step 7 Inspect pilot orifice a Remove 7 16 nut from bottom of pilot assembly b Remove pilot tube and pilot orifice c inspect pilot orifice for blockage must be cleaned or re...

Страница 13: ...thru the sight glass If a spark is present the circuit is OK If there is no spark proceed to step 3 Step 3 Remove white wire from igniter Hold the igniter lead from the gas valve to an unpainted surfa...

Страница 14: ...OCEDURE ED V Gas Control Replacement Thermal Well and Chamber Door Sensor Testing and Replacement Page 14 Once the thermal well resistance values are known the water temperature must also be known to...

Страница 15: ...le If temperature of water is 84 F then the resistance through the sensor would be 8449 see shaded area NOTE Sensor resistance increases as the temperature falls WARNING Stored water may be HOT when p...

Страница 16: ...ontrol service tool 239 45991 00 available from your BWC parts supplier Insert tool into back of gas control see photos below Follow the steps below allows removal gas control from thermal well withou...

Страница 17: ...tioned as shown in photo 3 for proper control alignment Step 2 Route wire leads back into relief opening see photo 3 Step 3 Align slots located on thermal well flange with tabs located on back of gas...

Страница 18: ...139 59 68 173 112 68 77 137 90 77 86 110 72 86 104 89 59 104 113 73 48 113 122 60 39 122 131 49 32 Sensor Resistance at Various Temperatures SERVICE PROCEDURE ED V Gas Control Replacement Thermal Wel...

Страница 19: ...heater With the inner door removed the Bradford White Defender Safety System will be inactivated If flammable vapors are present a fire or explosion may result causing property damage personal injury...

Страница 20: ...Step 8 Reassemble burner Step 9 Inspect combustion chamber area of heater prior to reinstallation of burner assembly If cleaning is required refer to SERVICE PROCEDURE ED VIII Step 10 Reinstall burne...

Страница 21: ...witch is designed to open at predetermined temperatures An open switch can be reset by depressing the red colored button located at the center of the switch The overheating condition must be determine...

Страница 22: ...sure contact surface of resettable thermal switch and manifold mount are free of any debris Secure resettable thermal switch into place using screws from step 6 DO NOT OVER TIGHTEN SCREWS Step 8 Bend...

Страница 23: ...he areas that are not covered by the secondary air restrictor plate Using a soft brush clear jacket openings of any dirt dust restrictions or other obstructions Step 5 Remove any debris from burner as...

Страница 24: ...the bottom of the dip tube should be open and free of any blockage Anti siphon hole located approximately 6 from the bottom of nipple should be free of any blockage Any damage such as cracks restrict...

Страница 25: ...normal If depletion is of the original anode diameter approximately diameter replacement is recommended If any of thesteel core of the anode is exposed replacement is recommended Step 6 Upon completio...

Страница 26: ...ble Gas Feed Line 16 Pilot Assembly 17 Screw 8 18 x Hex Washer Head 18 Resettable Thermal Switch 19 Screw 6 20 x 3 8 PHCR 20 Screw 8 18 x Hex Washer Head 21 Manifold Mount 22 Complete Right Side Inner...

Страница 27: ...27...

Страница 28: ...Email parts bradfordwhite com techserv bradfordwhite com www bradfordwhite com...

Отзывы: