Trouble Shooting Guide continued-
PROBLEM CAUSE
SOLUTION
Insufficient hot
water
Thermostat setting
too low
Adjust thermostat to higher
setting. See Section VII
Undersized boiler
with no priority to
domestic hot water
Rewire for priority
Peak use of hot
water is greater than
tank storage
capacity
Determine peak usage and
compare to tank capacity
Faulty tank
thermostat
Replace thermostat
Boiler cycles
more than 5
times per day in
summer
Excessive demand
Reduce demand or consider
larger tank
Faulty thermostat
Replace thermostat
Boiler high limit set
too low
Increase boiler high limit
setting