background image

1

Thermostat calls for heat.

 The control board sends 24 volts from damper terminal #2 on the control plug

 to the flue damper.

2

Flue damper begins to rotate open. Once the flue damper is fully open, the damper end switch closes and 24 volts

is allowed to continue through damper to damper pin terminal #5.

3

4

Once pilot flame is proven, sparking will stop.

Page 6

Sequence of Operation

Trial for ignition (three 90 second ignition trials,  with 65 second pauses

between trials).

Control Board simultaneously sends:

1. 24 volts from control pin terminal #8, to “MV/PV”

 terminal of gas valve (common terminal).

2. 24 volts from control pin terminal #2, to “PV”

 terminal of gas valve to establish

gas flow at pilot.

3. Low current high voltage from “spark”

 terminal, to generate spark at the pilot and

 ignite pilot gas flow.

4. Pilot flame proving signal (measured in

 micro-amps). from the “sense” terminal, to

 prove pilot flame.

5

Once sparking stops, 24 volts is sent from control pin

terminal #5 on control board, to “MV” terminal on gas valve

to establish main burner gas flow. Main burners ignite from

the pilot flame.
The control board constantly monitors pilot flame through

the flame sensor rod. If pilot flame is lost, pilot and main

burners are shut down. After a 65 second inter-purge

period, the control will attempt to re-light the pilot beginning

at sequence 3 above.

7

Main burner fires until the thermostat is satisfied. The control

board interrupts 24 volts through the damper and the gas valve

circuit. Pilot and main burners are turned off.

8

Flue damper rotates to the closed position.

WIRING DIAGRAM

LOCKOUT CONDITION

Control board will go into “Soft Lockout” if the pilot cannot be lit

after 3 ignition trials. The water heater display indicates a lockout

condition by showing an error code number (62 or 63) with

“Service Needed” in the display window.  Refer to error codes in

the diagnostic section of this Service Manual. In a “Soft Lockout”

condition, the control will wait for 60 minutes and then make 3

more attempts to light the pilot and establish the main burners.

Soft lockout reset is accomplished by depressing the lower right

button under “Reset” for 3 seconds.

If the water heater should reach 200 degrees F, then the high limit

control will shut off the burners and the water heater will go into a

“Hard Lockout”. Error code 65 will be shown in the water heater

display.  The control can only be reset in the “service mode”,

which is detailed in the next section of this Service Manual.

6

Содержание D-38T-155

Страница 1: ...qualified service providers Models Covered by This Manual For The Bradford White D Series Models D38T155 D75T 125 160 300 D65T 370 399 D80T 180 199 250 D80T 425 505 D100T 199 250 D80L 399 450 505 D100...

Страница 2: ...roubleshooting 7 Thermostat Circuit Testing 24 D24 I Pilot Operation Testing 27 D24 II Main Burner Operation Testing 30 D24 III Main Burner Pilot Removal Inspection 32 D24 IV Flue Baffle Removal Inspe...

Страница 3: ...or degrees C Single control board with plug in wiring controls temperature ignition and flue damper operation Reduced number of parts for servicing and wiring Plug in wiring reduces chance of miswiri...

Страница 4: ...available a liquid U tube type or a digital magna helic type This device is used to measure gas and or air pressures and vacuum Multi Meter A digital type is strongly recommended This device is used t...

Страница 5: ...earance for Servicing 24 Front Clearance 20 Top 6 Sides Maximum Water Supply Pressure 150 PSI Thermostat Sensor s Redundant thermister with 11 900 or 0 5 ohms resistance at 70 deg F Sensor inside well...

Страница 6: ...me through the flame sensor rod If pilot flame is lost pilot and main burners are shut down After a 65 second inter purge period the control will attempt to re light the pilot beginning at sequence 3...

Страница 7: ...n to open Increase thermostat setting if tank is warm and make sure the control display status reads Heating Check wire connections of board to display See illustration With the control cover tilted d...

Страница 8: ...isplaying temperature sensors Error code 63 on display See Main Burner Short Cycles Does the flue damper rotate to the fully closed position Error code 56 on display Check for debris limiting damper r...

Страница 9: ...s until Max Setpoint is shown in the display Step 2 Pressing Select button will change display to next mode SELECT SET Status F idle Operational Water Temp The following is the sequence of modes avail...

Страница 10: ...emp Operational 2b Water Temperature Upper Sensor Displays if there is an upper sensor some models SELECT SET Status F idle Operational Upper Sensor 2c Water Temperature Lower Sensor Displays if there...

Страница 11: ...al Flame Current A 4 Setpoint Display Change SELECT SET Status F idle setpoint Operational 5 F C Display Change SELECT SET Status F C idle Operational F setpoint 6 Differential Display only shows the...

Страница 12: ...tep 1 In service mode press the Select button until Max Setpoint is displayed SELECT SET Status F idle Max Operational Setpoint Page 12 Troubleshooting WARNING Setting the water temperature to the max...

Страница 13: ...int value This will limit the maximum setpoint the user can select Note The maximum setpoint is approximately 180 F Step 4 Press Set button to confirm new Max Setpoint value and stop setting mode Page...

Страница 14: ...ice Mode Press the Select button until Water Temp is displayed in the upper right section of the water heater display For water heaters using two temperature sensors in the tank this will be the avera...

Страница 15: ...hen the burners are in operation Step 1 Make sure the status displays Heating or draw enough hot water to start the burners Step 2 Enter the Service Mode described previously Step 3 Press the Select b...

Страница 16: ...nal Setpoint Flashes Troubleshooting WARNING Setting the water temperature to the maximum set point can result in scalding hot water delivered to the faucets It is highly recommended that the maximum...

Страница 17: ...and Change Temperature Format F C To Change Temperature Format in Display from F to C or C to F Step 1 While in Service Mode press Select button until F C is shown in the upper right portion of the wa...

Страница 18: ...atus idle Operational C F C Step 3b Press Temperature Down button to change temperature format to F SELECT SET Status idle Operational F F C Step 4 Press Set button to confirm F or C format F C will s...

Страница 19: ...ce Manual explains the error codes with corrective actions to repair the water heater Example of Error Code in the Display Error Code History In Service Mode pressing the Select button after the Softw...

Страница 20: ...ror code index starting with the most recent error code 10 SELECT SET Status idle Operational Step 3 Press the Select button to view the error code for code 10 If there is a number displayed note what...

Страница 21: ...or code number if any for that index number Continue on to index 1 the oldest error code index The water heater display will store up to 10 error codes with the oldest code starting in code index 1 wi...

Страница 22: ...heater display with Service Needed shown below the error code number Note the error code and the definition in the chart below This label appears on the control box under the water heater display The...

Страница 23: ...ill also go through 3 attempts to relight the burners every hour in the soft lockout condition All other error codes will put the water heater into a Hard Lockout condition in which the water heater w...

Страница 24: ...hands or tools Turn power OFF Draw water to cool tank below 120 deg F Check lower sensor Is the sensor fully inserted into the well Sensor is held in place with a clip fastened to the well see photo...

Страница 25: ...ted Once cause of overheating condition has been diagnosed and corrected the control may be reset Reconnect and switch on power to the water heater Enter service mode on the water heater display see i...

Страница 26: ...Circuit Testing Upper thermister location applicable models Lower thermister access located inside control box Sensor Resistance Testing Upper Sensor 1 Determine resistance value of upper sensor Test...

Страница 27: ...his test Tighten pilot tube connection at the gas valve Check incoming gas pressure to water heater if okay replace gas valve Check for clogged or kinked pilot tube clogged pilot orifice Clean or repl...

Страница 28: ...pilot shield is touching pilot flame sensor or flame sensor touching pilot hood Bend shield to prevent interference or replace pilot shield Check pilot flame sense wire for broken insulation Replace p...

Страница 29: ...res with ohmeter Are ground wires okay Check for loose or damaged flame sense lead from pilot to Control Board see illustration to the right Is flame sense lead okay Repair wire lead or replace pilot...

Страница 30: ...e lead from MV terminal of gas valve Is there 22 27 volts AC across brown wire lead ground see photo 15 Replace control board Be sure control display is showing Heating pilot is lit and control is not...

Страница 31: ...uctions N Check burner tubes for scale or debris build up Clean burner as necessary see Main Burner and Pilot Removal and Inspection Check tank flues for blockage or debris build up causing restrictio...

Страница 32: ...lide complete burner rack out from heater see photo 19 Step 9 To install burner reverse above procedure Step 10 Check for gas leaks and verify proper operation Gas Valve Control Knob Gas Supply Line G...

Страница 33: ...Ground Wire Location Pilot Burner Inspection Step 1 Inspect pilot for the following a Broken or cracked ceramic insulators If found pilot must be replaced b Damaged electrode or flame sense wire If f...

Страница 34: ...wire connections from board Pull out sensor Remove clip Wire connections DANGER 120 volt exposure To avoid personal injury unplug while performing this procedure Page 34 23 25 24 26 Step 3 To remove...

Страница 35: ...ove collector cover from water heater by using pipe wrench as illustrated in photo 30 Step 9 Remove flue baffles from water heater Note it may be necessary to use pliers to loosen and remove baffles f...

Страница 36: ...ox anode locations Step 10 Remove screws from side or top of collector cover Note it may be necessary to chisel away some foam to access screws see photo 34 Step 11 Locate and remove anode rods from t...

Страница 37: ...Page 37 SERVICE PROCEDURE D24 VI Anode Removal and Inspection Approximate Anode Rod Locations 37...

Страница 38: ...cess Cover 16A Cleanout Access Cover ASME 17 Cleanout Cover Screw 17A Cleanout Cover Screw ASME 18 Cleanout Jacket Cover 19 Thermostat Sensor Clip 20 Burner Assembly Complete 21 Brass Drain Valve 22 C...

Страница 39: ...rner 9A Pilot Orifice 10A Pilot Tubing 11A Pilot Mounting Screw 12A Burner Tube Support 13A Manifold Bracket 14A C Cane Manifold 15A Manifold Straight 16A Manifold Bracket 17A 90 Street Elbow Black 18...

Страница 40: ...7 8 Snap Bushing 11B Power Cord Strain Relief 12B Pilot Wire Strain Relief 13B Secondary Transformer Wiring Harness 14B Primary Transformer Wiring Harness 15B Screw 8 18 x PHCR 16B Gas Valve Control W...

Страница 41: ...Energy Cut Off GFI Ground fault interrupt GPM Gallons per Minute Hz Hertz LED Light Emitting Diode NOx Oxides of Nitrogen NPT National Pipe Thread PSI Pounds per Square Inch VA Volt Amps VAC Volts Alt...

Страница 42: ...NOTES Page 34...

Страница 43: ...NOTES Page 34...

Страница 44: ...Email parts bradfordwhite com techserv bradfordwhite com www bradfordwhite com...

Отзывы: