Fire damper RABC

E60 / E120

Installation

RABC is installed in horizontal or vertical ducts that pass 
through fire cell separating building elements, according to 
the adjoining installation instructions.

Actuator

RABC is always supplied with an electric safety actua-
tor with spring return complete with thermal sensor with 
pushbutton for local manual operating test. The sensor 
disconnects the power to the actuator if the temperature 
exceeds 72°C inside or outside the damper. 24V actuators 
are always used in connection with the MRB monitoring 
system. Dampers can also be supplied with electric actua-
tor 230V.
Note that the RABC damper is always supplied with an 
actuator.

Activation

According to Boverket’s Building Regulations smoke de-
tectors must be verified according to SS-EN 54-7 to acti-
vate dampers. The mandatory thermal sensor closes the 
damper at 72 °C according to ISO 10294-4.

Control and monitoring

When the damper is used to prevent the spread of fire and 
combustion gases it must be closed via impulses from the 
smoke detector. This must be fitted in the ventilation duct 
in the proximity of the damper or in another suitable loca-
tion. Smoke detectors are monitored by means of Rasch’s 
MRB system or the like. The MRB monitoring system also 
performs automatic operating checks on the damper every 
48 hours and is designed so that faults are indicated im-
mediately and the damper closes.  
See www.bevent-rasch.se for further details.

Quick facts

•  Fire resistance class E60/E120S
•  Sizes from 100 mm to 630 mm 
•  Prefitted safety actuator 24V or 230V
•  Installation in ducts 
•  Available in MagiCAD
•  CE-marked building product according to 15650:2010 

Use

Damper in combination with walls or joist systems for 
fire separation of heating, ventilation and air conditioning 
installations in buildings. In accordance with the harmo-
nised European standard EN 15650:2010. In designs ac-
cording to associated documents, installation instructions 
and when the damper is used in combination with smoke 
detectors and monitoring system (MRB), or the like, the 
spread of combustion gases is prevented. No further ac-
tion against the spread of combustion gases is required.

Performance

EC certificate according  
to EN 15650:2010

402-CPD-SC0058-13

Classification of fire resistance  
according to EN 13501-3

E120 (ve i <–> o) S*

)

 

E120 (ve ho i <–> o)*

)

E60 (ve ho i <–> o)

For complete classification,  
see the Declaration of Performance.

*

)

 Fire class E120 shall be specified when ordering.

Содержание RABC Series

Страница 1: ...ire RABC 05 01 2018 Circular fire damper RABC Fire resistance class E60 E120S Sizes from 100 mm to 630 mm Prefitted safety actuator 24V or 230V Installation in ducts Available in MagiCAD CE marked building product according to 15650 2010 ...

Страница 2: ...n the proximity of the damper or in another suitable loca tion Smoke detectors are monitored by means of Rasch s MRB system or the like The MRB monitoring system also performs automatic operating checks on the damper every 48 hours and is designed so that faults are indicated im mediately and the damper closes See www bevent rasch se for further details Quick facts Fire resistance class E60 E120S ...

Страница 3: ...ng and components of galvanized steel sheet according to environmental class C3 in sizes 400 mm 630 mm Fabric seals EPDM spiral duct connections Accessories RCKB Connection box RCDU MRB system max 2 dampers RCBK4 MRB system max 4 dampers RCMU8 MRB system max 8 dampers RCKD RD Smoke detectors RCTU RCTC MRB3 system max 236 dampers Example Fire damper RABC 400 1 1 Size nom diameter ØD mm Material Gal...

Страница 4: ...75 C 24 hrs guaranteed safety Trigger temperature thermal sensor 72 C End position contacts load 300 mW min 1 mA 5V max 100 mA 250V After exceeding the above values it applies load 300 mW min 100 mA max 3 A 250 Sound level when opening approx 45 dB A Sound level when closing approx 62 dB A Chart indicates in the de energized state Tf1 Tf2 BAE72 S Actuator C O N L1 M 1 2 1 2 3 4 5 6 5 80 Thermal se...

Страница 5: ...315 Size 100 400 630 500 40 dB 45 dB 50 dB 55 dB 60 dB Correction of sound power level LWok in octave band Lwok Lw Kok Sound data Correction Kok Size Ø mm Centre frequency Hz 63 125 250 500 1000 2000 4000 8000 100 3 7 12 19 29 27 33 32 125 4 5 8 13 21 25 31 35 160 3 4 7 13 18 22 29 37 200 2 8 14 20 24 28 35 41 250 2 9 14 19 19 28 35 42 315 3 8 12 12 18 24 31 35 400 5 7 11 6 15 22 27 28 500 2 10 15...

Страница 6: ...n 1 Damper s fire resistance class E60 ve ho i o E120 ve ho i o E120 ve i o S Option 2 Damper s fire resistance class E60 ve ho i o E120 ve ho i o Installation instruction Seal with fire stopping sealant e g Intumex AN Suspension as set out in point 2 RABC RABCR RABC VAP Repair using an approved method that meets the fire class e g caulking and or fire stopping sealant Repair using an approved met...

Отзывы: