BPS YZ102 IOM-R1.0  Page 3 of 14

© 2018 - Best Purging Systems Corporation

Unit Specifications

Purge Time: 

4 Volumes @ 1 minute per 1.0 cf 

 

5 Volumes @ 1 minute per 0.8 cf 

Protective Gas Supply: 

Air or Inert Gas

Gas Supply Pressure: 

80 - 125 psi max.

Unit Supply Connection: 

1/4” tube fitting

Enclosure Supply: 

1/4” tube fitting

Enclosure Reference: 

1/4” tube fitting

Safe Enclosure Pressure: 

0.25” w.c. / 6.22 Kb

Safe Press. Flow Rate: 

* 0.1 - 3.5 scfh per cf

Purge Enclosure Pressure: 

* 5” - 8” w.c.

Purge Press. Flow Rate: 

4 scfm @ 60 psi.

* Enclosure Integrity determines actual Pressure & Flow

Material Specifications

Unit Mounting Plate: 

316 Stainless Steel Brushed 

Regulator body: 

Enamel Finished Zinc

Filter & Handle: 

Polycarbonate

Enclosure Press. Gauge: 

Enameled Aluminum

Injection Press. Gauge: 

Polycarbonate/Brass

Tubing: 

316 Stainless Steel

Tube Fittings: 

316 Stainless Steel

Valves: 

316 Stainless Steel

Valve Handles: 

Polycarbonate

Start up Labels: 

Silkscreened Lexan

Enclosure Warning Label: 

Stainless Steel

Protected Enclosure Criteria

The consumption of protective gas is directly related to the 

integrity of the protected enclosure plus the type of purge 

requirements, i.e. dilution and ventilation. The following 

enclosure recommendations are provided to help minimize 

protective gas consumption and increase purge unit efficiency.

1.  The enclosure should be fabricated to meet NEMA 4 or 

12 / IP66 requirements. 

2. 

Non metallic enclosures should meet ANSI/UL 94 V-O 

or 94 5V.

3.  Enclosure windows should be impact resistant and sized 

as small as possible.

4.  Enclosure surface temperatures must not exceed 80% 

of the area’s auto-ignition temperature.

5.  Avoid obstructions and barriers which could impede 

protective gas flow through the protected enclosure.

Identifying Your Unit

Major Components List

Filter Regulator: 

Enclosure Pressure Valve: 

Purge Valve: 

Purge Press. Indicator: 

Enclosure Press. Indicator: 

Optional Pressure Loss Alarm: 

Enclosure Warning Label: 

EWL-1

General Information

All electrical connections of the protected enclosure and purge unit must be performed by trained and knowledgeable 

personnel. In addition, all connections must be installed in accordance with the National Electrical Code (NEC) NFPA 

70 and all relevant international, nation and local codes. The Authority Having Jurisdiction must approve all electrical 

installations. Failure to follow electrical warnings can cause harm, death or dismemberment to personnel and can cause 

damage to instrumentation.

WARNING

Model Number Designations

This enclosure pressurization unit is offered in various 

styles. For proper installation and operation, examine 

the Unit Model Number Nameplate to identify the Unit 

Style, Area Classification and Type, as noted below.

 

Model # YZ-102-CI-L-U-

¤

Div./Zone Reduction

Y- 

Div.1/Zone1 to Div. 2/Zone 2

Z- 

Div.2/Zone2 to Non-Hazardous

Unit Series

102-

 1/4” Purge Unit

Area Classification

CI-

 Class I Areas

Pressure Switch Option

L- 

Provided Less Switch

W-

 Provided With CI, Gr. C&D EXP Switch

B-

  Provided With CI, Gr. B EXP Switch 

Voltage*

120 VAC 

24 VDC
OR

Optimal Configuration***

PM- 

Panel Mount

Mounting Options

U-

 Universal  

 Mounting**

V-

 Vertical  

 Mounting

H-

 Horizontal  

 Mounting

*  For pressure switch option “B” only

**  Not Available with pressure switch options

*** Panel Mount designed to mount through the wall of protected enclosure. U mounting only.

YZ103-CI-W-V

Purge Unit

Area Classification Reduction:

Type Z - 

Cl I, Div. 2/ Zone 2, Gr. 

C&D, to Non-hazardous

Type Y - 

Cl I, Div. 1/ Zone 1, Gr. 

C&D to Div. 2/ Zone 2, Gr. C&D
Purge Control for use in Hazardous 

Locations.

   In  accordance w ith  the 

National Fire Protection Association 

Standard 

for 

Purged 

and 

Pressurized Enclosures for Electrical 

Equipment. NFPA 496 2003.

23HP

Содержание YZ102

Страница 1: ...ual BPS YZ102 IOM R1 0 9 18 Copyright 2018 Best Purging Systems Corporation All Rights Reserved Model YZ102 CI W or B V With Pressure Switch shown w Mounting Flange Model YZ102 CI W or B H With Pressure Switch shown w Mounting Flange Model YZ102 CI L U Less Pressure Switch shown w Mounting Flange ...

Страница 2: ...NOT intended for dilution applications Please consult factory for more information A copy of this manual must be read and retained by the operator of this unit User s agent s are responsible for transferring this manual to the user prior to installation and start up This unit must be installed and operated per this manual The Authority Having Jurisdiction should be advised before installation of t...

Страница 3: ...fying Your Unit Major Components List Filter Regulator Enclosure Pressure Valve Purge Valve Purge Press Indicator Enclosure Press Indicator Optional Pressure Loss Alarm Enclosure Warning Label EWL 1 General Information All electrical connections of the protected enclosure and purge unit must be performed by trained and knowledgeable personnel In addition all connections must be installed in accord...

Страница 4: ...e 5 Multiple Protected Enclosures must be purged in series and should be connected from the smallest to the largest enclosure 6 Enclosure Supply connections between multiple enclosures must be at least the diameter of the Purge vent exhaust 3 4 1 Protective Gas Supply Header Purge Unit Unit Supply 1 4 Tubing Protected Enclosure Purge Vent Model PV 2 Enclosure Supply 1 4 Tubing Enclosure Reference ...

Страница 5: ...rol Valve Venturi Orifice Model YZ102 CI L U Universal Mount Less Pressure Switch Rear View Model YZ102 CI W or B V Vertical Mount With Pressure Switch Rear View Typical Pneumatic Flow Diagram Denotes Customer Supplied Tubing Required Purge Vent Enclosure Pressure Gauge Optional EXP Pressure Switch Purge Injection Pressure Gauge Enclosure Warning Label Protected Enclosure Enclosure Supply Enclosur...

Страница 6: ...nt Purge Vent 2 5 6 5 Model YZ102 CI W or B Side View C L 4 3 5 Model YZ102 CI W or B Mounting Flange YZ102 CI L U Side View C L 4 1 75 12 Universal Mounting Flange Model YZ102 CI W or B V Front View Model YZ102 CI L U Front View 12 11 5 11 5 12 0 25 Typ 8 0 5 6 6 12 11 5 15 75 0 5 16 25 8 125 0 25 Typ 6 15 75 8 125 11 11 5 0 5 16 25 0 25 Typ 6 0 625 12 4 0 3 375 0 25 Typ 8 11 375 10 3125 1 6875 0...

Страница 7: ...nting flange dimensions and unit layout 5 Based on Enclosure Connection Requirements on page 4 drill and ream a 29 64 hole in protected enclosure install 1 4 Enclosure Supply Bulkhead fitting NOTE Protected Enclosure Supply should be installed at extreme opposite corner from part PV 2 Purge Vent and 8 from the Enclosure Reference Connection 6 Next drill and ream a 29 64 hole in protected enclosure...

Страница 8: ...um 60 psi reading on Purge Injection Pressure Gauge adjust regulator if required 8 Close Purge Control Valve fully The Enclosure Pressure Indicator should return to a Safe 0 25 w c reading 9 Calculate total protected enclosure volume when empty Determine Purge Time required 5 minutes minimum Required Exchange Time Enclosure Volume 4 Volumes 1 minute per 1 0 cf 5 Volumes 1 minute per 0 8 cf 10 Mark...

Страница 9: ...o off scale to the high side this is normal 6 Confirm a Min 60 psi on Purge Injection Pressure Gauge 7 Allow unit to purge protected enclosure for the required time marked on the Unit Start Up Instructions 5 minutes minimum Required Exchange Time Enclosure Volume 4 Volumes 1 minute per 1 0 cf 5 Volumes 1 minute per 0 8 cf 8 Upon completion of the required purge time close the Purge Control Valve f...

Страница 10: ... to Twenty Four 24 Months after date of shipment Regardless of registration the Commencement Date for either warranty period shall be the date of BEST Factory shipment or under prior special written agreement at time of Product purchase no greater than Ninety 90 Days after the BEST Factory shipment date WARRANTY EXTENSIONS An extended warranty shall extend the effective warranty based on the terms...

Страница 11: ... repair shipping damage or any other reason Please note that shipping damage must be claimed promptly with the carrier and is the responsibility of the recipient To procure an RMA number please contact Best Purging Systems Customer Service at 1 844 PURGE IT 787 4348 A Best Purging Systems Customer Service Associate will then work with you to resolve any problems with the Unit if at all possible an...

Страница 12: ...onal Electrical Code NEC ANSI NFPA 70 2017 edition Standard for Purged And Pressurized Enclosures for Electrical Equipment ANSI NFPA 496 2017 edition Recommended Practice for the Classification of Flammable Liquids Gasses or Vapors and of Hazardous Classified Locations for Electrical Installations in Chemical Process Areas NFPA 497 2017 edition ANSI American National Standards Institute 11 West St...

Страница 13: ...BPS YZ102 IOM R1 0 Page 13 of 14 2018 Best Purging Systems Corporation Maintenance Service Notes ...

Страница 14: ...____ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Unit Identification Information Date of Installation __________________...

Отзывы:

Похожие инструкции для YZ102