IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
__________________________________________________________________________________________
BPL ULTRA50 UL 924 Listed Photoluminescent EXIT Sign
NOTICE
EXTERNAL ILLUMINATION SOURCE REQUIRED
ACTIVATION
Minimum 5-foot candles (54 lux) of unfiltered fluorescent, metal halide or mercury vapor lighting.
Install BPL ULTRA50 Photoluminescent EXIT signs only in locations where an external illumination
source is present, is deemed reliable and is supplied by a circuit not controlled by automatic timers or
sensors, and whose controls are accessible only to authorized personnel. This reliable external illumination
source is to be energized at all times during building occupancy.
BPL ULTRA50 Photoluminescent EXIT signs are for
INDOOR
use only. sunlight, liquid spray or
temperature outside the range 10ºC – 40ºC (70º – 160ºF).
Check with your applicable installation codes (such as NFPA 101 – Life Safety Code) to perform periodic
visibility tests.
Should any changes in your external lighting types or lighting levels occur, make sure that the BPL
ULTRA50 EXIT sign is still being illuminated with minimum 5-foot candles (54 lux) of unfiltered
fluorescent, metal halide or mercury vapor lighting.
Periodically clean sign face with a damp cloth. Do not use any thinners or solvents on the sign face.
VIEWING DISTANCE
50 foot viewing distance
DIRECTIONAL INDICATORS
Two self-adhesive photoluminescent directional indicators are supplied with each sign. Small dots are also
provided to the left of the letter E and to the right of the letter T for easy alignment. If your EXIT sign is to be
located other than directly over an exit, apply a directional indicator to the left of the E, pointing left, or to the
right of the T, pointing right, or both, as appropriate.