IMPORTANT SAFEGUARDS 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

__________________________________________________________________________________________ 

 

BPL ULTRA50 UL 924 Listed Photoluminescent EXIT Sign 

 

NOTICE

 

  

EXTERNAL ILLUMINATION SOURCE REQUIRED 

 

ACTIVATION

     

Minimum 5-foot candles (54 lux) of unfiltered fluorescent, metal halide or mercury vapor lighting. 

 

Install  BPL  ULTRA50  Photoluminescent  EXIT  signs  only  in  locations  where  an  external  illumination 

source  is  present,  is  deemed  reliable  and  is  supplied  by  a  circuit  not  controlled  by  automatic  timers  or 

sensors, and whose controls are accessible only to authorized personnel. This reliable external illumination 

source is to be energized at all times during building occupancy.  

 

BPL ULTRA50 Photoluminescent EXIT signs are for 

INDOOR

 use only. sunlight, liquid spray or 

temperature outside the range 10ºC – 40ºC (70º – 160ºF). 

 

Check with your applicable installation codes (such as NFPA 101 – Life Safety Code) to perform periodic 

visibility tests. 

 

Should any changes in your external lighting types or lighting levels occur, make sure that the BPL 

ULTRA50 EXIT sign is still being illuminated with minimum 5-foot candles (54 lux) of unfiltered 

fluorescent, metal halide or mercury vapor lighting. 

 

Periodically clean sign face with a damp cloth.  Do not use any thinners or solvents on the sign face. 

 

VIEWING DISTANCE

 

50 foot viewing distance

 

 

DIRECTIONAL INDICATORS

   

Two  self-adhesive  photoluminescent  directional  indicators  are  supplied  with  each  sign.  Small  dots  are  also 

provided to the left of the letter E and to the right of the letter T for easy alignment.  If your EXIT sign is to be 

located other than directly over an exit, apply a directional indicator to the left of the E, pointing left, or to the 

right of the T, pointing right, or both, as appropriate. 

Содержание ultra50

Страница 1: ......

Страница 2: ......

Страница 3: ...igns are for INDOOR use only sunlight liquid spray or temperature outside the range 10ºC 40ºC 70º 160ºF Check with your applicable installation codes such as NFPA 101 Life Safety Code to perform periodic visibility tests Should any changes in your external lighting types or lighting levels occur make sure that the BPL ULTRA50 EXIT sign is still being illuminated with minimum 5 foot candles 54 lux ...

Страница 4: ...k the screw hole locations 3 If wall anchors will be required drill 4ea 3 16 holes and install them at this time Supplied 4 Attach the EXIT Sign Bracket to the wall using the supplied 6 screws and anchors 5 Drill two 3 32 holes in the sign face on the where indicated by the alignment dots near the end of the sign 6 Slide the mounting bracket onto the side of the exit sign and align with the drille...

Страница 5: ...nt Slide the frame base onto the top frame piece Center the base and secure it into place by tightening the set screw which is accessible through the center hole in the bottom of the base Go to steps 6 9 Flag Mount continued Remove the set screw from one of the corner angle brackets on the previously removed frame side Remove the corner bracket Slide the frame base onto the frame side Center the b...

Страница 6: ... D E E F 3 16 Set screws 9 pieces Corner Bracket 4 pieces 8 5 Aluminum sides 2 pieces 14 25 Aluminum sides 2 pieces 7 Base Bracket 1 piece Surface Mount Spacers 4 pieces Spacers included with surface mount frames only ...

Отзывы: