8.
.
Thermal
alarm
Thermal
alarm
The temperature inside the UPS is over 55
℃
. If the user does not reduce
the load, the temperature will continue to rise and the UPS will shut down
automatically at 60
℃
.
The temperature inside the UPS is over 55
℃
. If the user does not reduce
the load, the temperature will continue to rise and the UPS will shut down
automatically at 60
℃
.
9.
Fan is in “High
speed”
This symbol is used mainly for long run series and the 5000VA model.
The symbol will display whenever the cooling fan is running (or high speed),
and will disappear when it is off (or low speed).
10.
Silence mode
The audible alarm has been silenced. To reset the alarm in Back-up
mode, push the control button (not available during low battery level or
abnormal condition).
11.
UPS
fault
The UPS has failed and must be repaired. Contact a qualified service
person.
12.
Battery normal
1
) In normal operation, this symbol indicates a charged battery.
Battery
low
2) When the battery charge level is low, the word “LOW” will be added to
the symbol.
13.
Battery
replacement
The battery has failed and must be replaced. The battery is checked each
time the Test Function is executed.
14.
Battery
voltage
level
1) The higher the battery voltage, the more bars will illuminate.
2) When the UPS is charging the battery, the battery symbol and the level
indicator will blink together.
15.
Mode Value
Description
AC
out
V
AC output voltage.
AC
in
V
AC input voltage.
AC
out
Hz
AC output frequency.
BATT.
V
DC battery voltage.
TEMP.
℃
UPS internal temperature.
TIMER
Min. to off
The UPS will turn off when the displayed value reaches zero. For
example, if the timer shows 0.5 Min to off, the UPS will shut down in 30
seconds.
TIMER
Hr. to on
The UPS will turn on when the displayed value reaches zero. For
example, if the timer shows 48 Hr to on, the UPS will turn on in 2 days.
BATT.
Min. to off
The estimated remaining run time in Back-up mode. The accuracy of the
value is influenced by the loading type, ambient temperature and battery
condition (old or new).
Selection Button for mode & value
All the operation data will be displayed on LCD screen. By selecting the required mode (upward or
downward), the related value will be displayed.
HIGH
LOW
5.3 Audible alarm
During a utility failure or fault operation, the UPS emits beep for warning. In back-up mode, the
alarm can be silenced by pushing the button. However, the warning of low battery will still sound for
urging user to leave computer without any data loss.
16