21

2.

 

Direct vented – Take a draft reading from the inspection port of the boiler.  This over-fire reading will 
be a positive pressure.  Approximate over- fire draft readings can be found in the burner settings table. 

3.

 

Pump pressure – Install a pump pressure gauge in the oil pump following the oil burner manufacturer’s 
recommendations.   Adjust the pump pressure as per the preliminary burner settings. 

4.

 

Combustion Set-up – The air settings shown in the table are approximate.  The burner must be adjusted 
during actual field installed conditions.  Failure to do so will result in poor boiler performance and 
nuisance service calls.  After proper draft and oil pressure have been established: 

a.

 

Begin to close the air band to create a slight trace of smoke as noted on the Bacharach or 
equivalent smoke tester scale. 

b.

 

Take a flue gas sample and note the CO

2

 reading.  It will be about 13% to 14% 

c.

 

Open the air band to reduce the CO

2

 approximately 2%. 

d.

 

Check for “0” smoke. Head settings and/or air band may be altered to obtain the above results.  
Lock the air band and head setting screws in place. 

 
The above procedure will give a built in margin to ensure clean operation throughout the heating season.  
Should draft conditions vary, lint accumulate in the fan, heavier oil delivered, or other adverse conditions be 
encountered you will have a reasonable margin of built in protection before smoke generation begins. 

 

Preliminary Burner Settings 

 

Boiler Burner 

Nozzle 

Air 

Setting 

Turbulator/ 

Head 

Pump Press

CO

2

Draft 

Overfire 

Smoke 

SL375 Riello 

F5  .65x80

o

B 2.50 

0.5 

150 

PSI 

11.0% +.02  #0 

 Beckett 

AFG 

.60x70

o

B 6/0 

N/A  160 

PSI 

11.4% 

+.02  #0

 

 Beckett 

NX 

.60x60

o

B N/A 

1.50  160 

PSI 

11.0% +.02  #0

 

 HeatWise 

P1 

.60x60

o

A 8.00 

4.0 

150 

PSI 

11.0% +.02  #0 

SLD375 Riello 

BF5  .65x80

o

B 3.25 

0.5 

150 

PSI 

11.0% +.05  #0 

 Beckett 

NX 

.60x60

o

B N/A 

1.50  160 

PSI 

12.0% +.05  #0 

SL4100 Riello 

F5 

.85x80

o

B 3.25 

0.5 

150 

PSI 

11.0% +.04  #0 

 Beckett 

AFG 

.75x60

o

B 7/1 

N/A  160 

PSI 

11.3% 

+.04  #0

 

 Beckett 

NX 

.85x60

o

B N/A 

3.00  140 

PSI 

11.0% +.04  #0

 

 HeatWise 

P2 

.85x80

o

B 7.50 

4.0 

150 

PSI 

10.5% +.04  #0 

SLD4100 Riello 

BF5 

.85x80

o

B 4.75 

1.0 

150 

PSI 

11.0% +.08  #0 

 Beckett 

NX 

.85x60

o

B N/A 

3.00  140 

PSI 

11.0% +.08  #0 

SL5125 Riello 

F5  1.00x80

o

B 3.00 

4.0 

150 

PSI 11.0% +.07  #0 

 HeatWise 

P2 

1.00x80

o

B 4.00 

6.0 

160 

PSI 10.5% +.07  #0 

 Beckett 

NX 

1.00x60

o

B N/A 

4.00 

150 

PSI 11.0% +.07  #0 

SLD5125 Riello 

BF5  1.00x80

o

B 4.75 

4.0 

150 

PSI 11.0% +.11  #0 

 Beckett 

NX 

1.00x60

o

B N/A 

4.00 

150 

PSI 11.5% +.11  #0 

SL6150 Riello 

F5  1.25x80

o

B 5.75 

4.0 

150PSI 11.0% +.09  #0 

 Beckett 

NX 

1.25x45

o

B N/A 

2.00 

140 

PSI 11.1% +.09  #0 

 HeatWise 

P2 

1.25x70

o

B 5.50 

8.0 

150 

PSI 11.5% +.09  #0 

SL7175 HeatWise 

P2 

1.75x70

o

B 8.00 

12.0 

100PSI 12.0% +.11  #0 

 Beckett 

NX 

1.35x45

o

B N/A 

3.00 

150 

PSI 12.0% +.11  #0 

 
 
 

Control Circuit Safety Checks  

 

Check the safety controls on the boiler after completing the oil burner adjustments. A safety control check 
for satisfactory performance must be performed. 

   

Содержание Solaia SL375

Страница 1: ...MANUAL SL375 THRU SL7175 OIL FIRED CAST IRON BOILERS Keep these instructions with the boiler at all times for future reference BOYERTOWN FURNACE CO PO Box 100 BOYERTOWN PA 19512 1 610 369 1450 www bo...

Страница 2: ...n No 1 and No 2 heating oil only Never use gasoline or a mixture of gasoline and oil Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance The area...

Страница 3: ...elief Valves Expansion Tanks Venting Systems 10 Chimney Venting Direct Venting Burner Installation 14 Oil Tank and Piping 15 Wiring 15 Swing Door 18 Opening the Door Closing the Door Door Hinge Revers...

Страница 4: ...07 707 887 887 1 067 1 207 AFUE Rating 85 5 85 5 86 5 86 5 86 9 86 9 86 9 85 0 Water Capacity 3 6 3 6 4 3 4 3 5 1 5 1 5 8 6 5 Approx Shipping Weight 300 300 350 350 390 390 430 470 Cabinet Height 28 7...

Страница 5: ...ed at all times Ventilation of boiler room must be adequate enough to provide sufficient air for combustion When a boiler is located in an unconfined space in a building of conventional frame or mason...

Страница 6: ...reens used shall not be smaller than inch mesh If free area through a design of louver of grill is known it should be used in calculating the size opening required to provide the free area specified I...

Страница 7: ...anel The sensor wires should be run through the bottom knockout in the aquastat The rubber grommet provided with the sensor wires is to be securely inserted into the aquastat knockout 2 Connect the se...

Страница 8: ...upper brackets and insert into immersion well Fasten the wires into the well using the wire clamp provided Snap sensor wires into control b Honeywell L7248C1022 Run the sensor wires through the Heyco...

Страница 9: ...volume standing cast iron systems A thermostatic bypass valve will consistently ensure that return temperatures to the boiler exceed 130o F at all times See Figure 1 for Thermostatic Bypass valve pip...

Страница 10: ...t chimney shall be brought up to current requirements Chimneys which are relined shall be done so with an approved liner that will resist corrosion softening or cracking from the flue gasses All chimn...

Страница 11: ...e gasses Tees may be used in a straight section in conjunction with a barometric draft regulator however they must not be used for a 90 turn No device that will obstruct the free flow of flue gasses s...

Страница 12: ...nd sealed with high temperature sealant WARNING External vent surfaces are hot Surface discoloration of the building may occur due to improper burner or boiler adjustment We will not accept any liabil...

Страница 13: ...oles in the termination end Install the flexible vent piping with the provided connector between the boiler and the termination end The joints at the boiler vent connectors and termination end should...

Страница 14: ...installed in a level position and adjusted to lightly close while burner is operating Be sure to lock the balancing weight after adjustment ALL JOINTS IN THE AIR INTAKE ASSEMBLY MUST BE SECURELY FAST...

Страница 15: ...ll conditions Post purge is provided to ensure that the boiler fires at maximum efficiency and dependability throughout the heating season Post purge of the oil burner is controlled through the electr...

Страница 16: ...TE FUSSED DISCONNECT SWITCH ELECTRICAL SHOCK IS HAZARDOUS TURN OFF ALL POWER SUPPLIES AT SERVICE ENTRANCE BEFORE STARTING TO MAKE WIRING CONNECTIONS OR REPAIRS Refer to wiring diagrams in rear of manu...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...s must be removed from the holes in the right side and placed in the holes on the left side of the upper brackets 4 The aquastat immersion well must be moved to the upper left rear tapping and the rel...

Страница 20: ...ystem To bleed attach a clear plastic tube to the oil pump bleed port and allow oil to run until all the air is out of the oil suction line feeding the oil burner See burner and fuel pump manufacturer...

Страница 21: ...you will have a reasonable margin of built in protection before smoke generation begins Preliminary Burner Settings Boiler Burner Nozzle Air Setting Turbulator Head Pump Press CO2 Draft Overfire Smoke...

Страница 22: ...lex plug at burner 3 Remove the boiler front jacket panel by lifting vertically 4 Open the swing door following previously described procedure 5 If required remove scale and any soot deposits with a f...

Страница 23: ...Vent Inspect and clean vent and air intake piping Replace and reseal joints as required Inspect vent hood air inlet and discharge for obstruction Domestic Hot Water Storage Tank 1 Sizing of the hot wa...

Страница 24: ...Volts at Burner Refer to Oil Burner Manual Adjust Thermostat Adjust High Limit Check Fuses and Safety Switches Aquastat in Fault Condition Refer to Aquastat Manual Remove Thermostat Wires From Aquast...

Страница 25: ...Open All Supply Valves Oil Filter Clean Pump Strainer Clean Replace Oil Filter Clean or Replace Strainer Check All Fitting Connections Adjust Pressure to Burner Specs Ignition Electrode Shorted or Cr...

Страница 26: ...1 Reducing Coupling 3 4 x 1 2 328001 328001 328001 328001 328001 11 1 Drain Valve 1 2 328000 328000 328000 328000 328000 12 1 Street Elbow 3 4 328002 328002 328002 328002 328002 13 1 Relief Valve 3 4...

Страница 27: ...osits or corrosion in or on the cast iron sections 6 This warranty applies only to boilers installed in the United States 7 In order for this warranty to be effective a The boiler must have been insta...

Страница 28: ...tem inspected to NFPA 211 and in good condition Vent size checked against furnace manual and codes B r Operation urne Burner Model __________________ Nozzle _______GPH _______Deg ____Type_______ Burne...

Страница 29: ...____________________________________________________________________ Purchaser s Address ________________________________________________________________________ ______________________________________...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32...

Отзывы: