SELF----DIAGNOSTICS TESTING:

DIAGNOSTICS TESTING:

DIAGNOSTICS TESTING:

DIAGNOSTICS TESTING:    

1)

 

NORMAL OPERATION 

When unit is functioning properly with A.C. power supplied, the status indicator will be green. 

2)

 

TESTING 

The exit performs two types of tests, Contingency and Non-Contingency.   

The  contingency  testing  includes  “Battery  Disconnected  Mode”  and  “Lamp  Failure  Mode”.  When  the  Battery  is 

disconnected,  the  indicator  would  indicate  as  Red  (Steady).  When  the  Lamp  fails,  the  indicator  would  indicate  as  Red 

(Blinking - three times).   

The Non-Contingency test is for testing the Battery for its “discharging” and “recharging” capacity. A 15 minute battery 

discharge  test  is performed every  30 days  to  check  for  the  normal operation  of  the battery  and  the unit. Also  a full  90 

minute discharge test is performed once a year to confirm the same. When the battery is in discharging mode, the LED 

indicator would be a flashing Green (Three/ Four Pulses). Upon completion of the test and after 24 hours battery charging 

(Indicator  on  Red  and  Green  flashing),  the  status  indicator  will  return  to  either  Green  (Steady)  indicating  a  properly 

functioning unit or Red (Double Pulse) to show a battery failure. The following table shows the status indication. 

 

FUNCTION 

LED INDICATION 

Exit is in Emergency Mode 

Off 

Exit is in Normal Mode 

Green (Steady) 

Battery Disconnected 

Red (Steady) 

Lamp Failure 

Red (Flashing 

4

 times) 

Battery Fast Charging 

Red and Green (Flashing Alternately) 

Battery Failure

Red (Flashing 2 times) 

30 Second Battery Discharging Mode

 

Green (Flashing 1 time) 

15 Minute Battery Discharging Mode

**

 

Green (Flashing 2 times) 

90 Minute Battery Discharging Mode

***

 

Green (Flashing 3 times) 

* = Happens only after battery discharges once in every 30 days or 1 year.   

** = Occurs once in every 30 days. *** = Occurs once in a Year.   

MANUAL TESTING

MANUAL TESTING

MANUAL TESTING

MANUAL TESTING

Battery and Lamp test may be manually initiated by pressing the manual test switch. Once the test switch is 

pressed, the unit would be reset and the date of battery self-testing would start counting again. 

ACTION 

REACTION AND LED INDICATION 

Press test button 

on

ce (within 2 seconds) 

30-second test; Green light - Single blinking 

Press test button 

2

 times (within 2 seconds) 

15-minute test; Green light - Double blinking 

Press test button 

3

 times (within 2 seconds) 

90-minute test; Green light - Triple blinking

 

 

OPERATION

OPERATION

OPERATION

OPERATION::::    

During an electrical power failure, the lamps will automatically come on for a minimum of 90 minutes. To test this unit, 

the battery needs to be charged initially for 2 hours before depressing the test switch. On pressing the test switch, the 

emergency lamps will illuminate. When the switch is released, the lamps will turn off. 

 