Relay 1 

Menu for changing setting relay 1 
 

Value 

Description 

range 

Factory 
settings 

Level: x %

 

Switching level when the relay is switching 

0 ... 100 % 

50 % 

Hysteresis: x % 

Hysteresis in % 

1 ... 10 % 

1 % 

Delay on: x sec 

Switching delay on 

0 ... 600 sec  1 sec 

Delay off: x sec 

Switching delay off 

0 ... 600 sec  1 sec 

Relay 2 

Menu for changing setting relay 2 
 

Value 

Description 

range 

Factory 
settings 

Level: x %

 

Switching level when the relay is switching 

0 ... 100 % 

50 % 

Hysteresis: x % 

Hysteresis in % 

1 ... 10 % 

1 % 

Delay on: x sec 

Switching delay on 

0 ... 600 sec  1 sec 

Delay off: x sec 

Switching delay off 

0 ... 600 sec  1 sec 

Debug level 

This option is for factory use only. 

Factory defaults 

This option can set all programming values to factory values. 
 

Value 

Description 

N. No 

No values will be set to factory values 

Y. Yes 

All values will be set to factory values 

Factory test 

This option is for factory test only. 
 

 

Содержание JGA2011

Страница 1: ...y JGA2011 is checked before sending for correct operation Therefore Boutronic has a warranty period of 1 year The warranty expires if The defect is caused by gross negligence or by improper installati...

Страница 2: ...ns 3 Connection example 4 Operation 4 Current inputs 4 Potentiometer 5 Relay 5 Switching delay Relay 5 Change settings 6 Potentiometer 6 DIP switches 6 Setting with the serial menu 6 Relay 1 7 Relay 2...

Страница 3: ...Relay1 24VD C IN 24VD C OU T www boutronic nl Made in the Netherlands Li ft front here for ac ces s control P2 Nr Unit Description 1 Connection 7 12 Connection 7 12 see front for type of connections 3...

Страница 4: ...GND Level 0 100 4mA 0 20mA 100 DIP 3 OFF DIP 3 ON Software level 0 100 Delay on 1 sec Delay off 1 sec Hystereis 1 Delay on 1 600 sec Delay off 1 600 sec Hystersis 1 10 Relais 2 4 20 mA Current in 2 4...

Страница 5: ...d is maximum Relay The relay switches when the corresponding input exceeds the switching threshold Input 1 switches relay 1 and input 2 switches relay 2 Switching delay Relay The switching delay with...

Страница 6: ...Use software settings for threshold level Delay and hysteresis 4 Reserved Reserved Setting with the serial menu You can change the settings with the USB port and the Boutronic Studio The Boutronic St...

Страница 7: ...1 sec Relay 2 Menu for changing setting relay 2 Value Description range Factory settings Level x Switching level when the relay is switching 0 100 50 Hysteresis x Hysteresis in 1 10 1 Delay on x sec...

Страница 8: ...otecting range IP20 Power Description Min Typ Max Unit Remarks Power in 20 24 30 VDC 20 24 24 VAC 1 35 mA Power out 20 30 VDC 2 150 mA 3 1 Note one of the phases is directly connected to the GND 2 Thi...

Страница 9: ...1 12 1 2 3 4 5 6 CONTROL Powersupply www boutronic nl GND 24VDC IN Type nummer JGA2011 24VDC OUT 4 20mA in 2 GND Inputs 4 20mA RoHS compliant TA 0 70 C Relay 1 Relay 2 4 20mA in 1 Relay contacts 24VAC...

Отзывы: