Page 12
4:8.1 Oil Filter
It is essential for reliable operation that an Oil Filter is fitted in the Oil Pipe supplying Oil from the Tank
to the Burner.
The filter should be fitted as close to the Boiler as practicable but not fitted to or inside the boiler.
It is a condition of the guarantees that a suitable Filter is fitted correctly.
4:8.2 Fire Check Valve (Not Supplied)
A remote acting FIRE VALVE must be fitted in the suction line at the time of installation - see BS 5410 Part 1.
The valve must be fitted external to the Boiler. The sensor should be located above the Burner in the clip
provided.
FIRE VALVE SENSOR LOCATION
R.A.F. FIRE VALVE BODY
Remote Acting Fire Valves are available from
Boulter Buderus
, through your merchant or installer.
Ref:
Capillary
Length
Operating
Temperature
RAF9015C
1.5m
90
o
C
RAF9030C
3.0m
90
o
C
RAF9060C
6.0m
90
o
C
Page 17 of 40