Boston gear Ratiotrol P-3026-BG Скачать руководство пользователя страница 6

Mounting Instructions

See Figures 1 & 2, pages 17 & 18

1. The enclosure is designed for vertical surface

mounting in a dry location. It should not be used

where a water-tight or weatherproof enclosure

is required.

Never mount the enclosure

immediately beside or above

heat-generating equipment, or directly below

water and steam pipes.

Comply with the following mounting

requirements:

a. Mount the enclosure in a vertical

position, allowing four (4) inches

minimum clearance on all sides, for

maximum cooling efficiency.

b. Fasten the enclosure securely on a level

surface with the mounting tabs provided.

See Figure 1 for enclosure dimensions.

c. Shock and excessive vibration are

detrimental to controller performance and

life. Vibration can cause general

deterioration of connections, and

component damage. Therefore, shock-

mount the controller if it is subjected to

external vibrations.

2. If the motor is to be foot mounted, bolt the

motor to a firm, flat foundation. If the

foundation is not flat, use shims to prevent

strain when tightening the bolts. If the motor

is to be connected directly to a machine, be

sure of correct alignment. Pulleys and

couplings must slip freely onto the motor

shaft.

Never hammer the pulleys,

couplings, or motor shaft, nor

overtighten drive belts or timing chains. Bearing

damage could result.

Wiring Instructions

Refer to the data label inside the enclosure

cover and be sure the input voltage and

frequency to the controller complies with its

rating. A surge suppressor (varistor) protects

the controller from normal line transients and

surges. However, to prevent problems from

high-energy transients and large surges,

observe the following:

1. Place the controller on a feeder line separate

from that supplying large inductive loads.

2. If the input power to the controller comes

directly from a transformer, always switch

power ON and OFF between the transformer

secondary and the controller.

Never make or break power

in the transformer primary.

Transients could be generated which could

damage the controller.

3. If the controller must be fed from an AC

circuit which also supplies highly inductive

loads, additional suppression may be

required to limit transients or surges to 150%

of peak line voltage.

Never use power factor

correction capacitors on the

input line to the controller. These capacitors can

damage the solid-state components.

The wire size of the input power and motor

wiring can be determined from Table 1 and the

controller data label.

1. Do not use wire larger than

#12 AWG. Oversize or solid

wire, as well as oversize screwdrivers for

electrical connections, can break terminal board

barriers.

2. All wiring must comply with the national and

local electrical codes.

Use the 3/4-14 NPT tapped conduit holes in the

enclosure to facilitate wiring.

All external wiring for low voltage signal

sources, e.g., potentiometers, tachometer

generators, transducers, should be run in

separate conduit from all other wiring. Use

twisted wire (5 to 6 twists per foot) or shielded

cable. Maintain the separation of power and

signal wiring within the enclosure.

Pickup from unwanted

signals can cause erratic

operation and/or controller damage.

6

P-3026 • Doc. No. 60881 • Boston Gear

®

Ratiotrol

®

DC Motor Speed Control

Installation

Section II

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

Содержание Ratiotrol P-3026-BG

Страница 1: ...Boston Gear Ratiotrol DC Motor Speed Control Doc No 60881 VEL Series 1 6 1 HP VEH Series 1 3 HP Installation and Operation P 3026 BG An Altra Industrial Motion Company...

Страница 2: ...Controller 9 Section IV Maintenance 10 General 10 Adjustment Instructions 10 Troubleshooting 12 Section V Parts List 15 Section VI Options 16 Section VII Illustrations 17 List of Illustrations Figure...

Страница 3: ...AC VEL16 1 6 HP VEL25 1 4 HP VEL33 1 3 HP VEL50 1 2 HP VEL75 3 4 HP VEL100 1 HP 2 VEH100 VEH500 230VAC VEH100 1 HP VEH150 1 1 2 HP VEH200 2 HP VEH300 3 HP Basic Units Standard VEL and VEH Controllers...

Страница 4: ...should not exceed 55 degrees C Performance Characteristics 1 Speed Range controlled 0 to motor base speed 2 Speed Range At Rated Torque and Regulation 30 1 3 Efficiency maximum speed a Controller SCR...

Страница 5: ...when the motor armature current exceeds 120 for 80 seconds An optional current load monitor Option Kit Cat No 60177 is available which provides an adjustable trip range and an adjustable time delay r...

Страница 6: ...ents and surges However to prevent problems from high energy transients and large surges observe the following 1 Place the controller on a feeder line separate from that supplying large inductive load...

Страница 7: ...on selection table on the controller data label The controller has been factory tested and adjusted with a motor under simulated operating conditions Therefore startup adjustments should not be needed...

Страница 8: ...s the RUN button and the motor will accelerate to the setting of the MOTOR SPEED potentiometer Stop To stop the motor depress the STOP button and the motor will stop at a rate proportional to the moto...

Страница 9: ...interlock which requires a momentary relaxation of pressure before the reverse position can be engaged This center position causes a Stop function and an antiplug circuit prevents the motor from bein...

Страница 10: ...d result stop the motor turn off the AC input power and refer to the Troubleshooting Table Table 5 Refer to Figure 4 for the location of the internal adjustment potentiometers Preliminary 1 Be sure th...

Страница 11: ...and 6 until desired speed regulation is attained Current Limit The current limit prevents excessive armature current and resulting excessive line current by limiting armature current at 150 of rated S...

Страница 12: ...wiring terminating trips immediately when in the controller Correct accordingly turned on Circuit component or wiring grounded Remove unwanted ground Power Bridge BR1 shorted Replace BR1 Power board f...

Страница 13: ...d Check shunt field current Insufficient shunt field current causes excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely repla...

Страница 14: ...uses excessive armature current If field current is OK check for mechanical overload If unloaded motor shaft does not rotate freely replace motor bearings Also check for shorted armature Correct accor...

Страница 15: ...Motor Speed 60246 All 1 Allen Bradley 72A1G Pot Jog Speed 60246 Jog Option No 9 1 Allen Bradley 72A1G048D5024 Knob Pot 60245 All 1 Rogan RB672AML T1 Transformer 60259 All 1 Inelco P 1883 APR Relay An...

Страница 16: ...aking R Reversing Selector Switch MR Reversing Auto magnetic 9 Jog Selector Switch B Input Options 14 Master Override Board 17 Adj Linear Accel Decel 22 Tach Follower 25 Ext MA Signal Isolated 33 Spee...

Страница 17: ...trations Section VII Max Control Proj 65 1 35 Circuit Breaker Operator Panel Mounting Slot Width 25 8 59 9 34 12 00 1 33 1 20 1 75 6 00 10 55 6 30 25 9 06 16 81 Conduit Entrance 3 4 14 N P T 4 Places...

Страница 18: ...5 1 75 6 00 1 20 Conduit Entrance 3 4 14 N P T 6 Places 25 00 Approx 9 34 3 75 Approx 9 34 1 33 8 59 1 35 8 Mounting Slots 25 Wide 9 06 16 81 10 55 Figure 2 Approximate Weights VEL Controls 30 Pounds...

Страница 19: ...19 P 3026 Doc No 60881 Boston Gear Ratiotrol DC Motor Speed Control Illustrations Section VII Ratiotrol D C Systems Figure 3 VEL VEH Series...

Страница 20: ...2 AC1 11 8 9 E3 E19 E20 VEL 50VDC Field VEH 100VDC Field F F CB1 30A RV1 L1 L2 115V 230V 115V 115V Blk Wht T1 Power Bd Blk Red Blk Wht 24V 20V 20V 2 1 5 4 3 K1 E10 E13 13 E11 E12 12 14 15 D1 D2 D4 D3...

Страница 21: ...action for direct or consequential damages to property or person The foregoing limited warranty is expressly made in lieu of all other warranties whatsoever express implied and statutory and includin...

Отзывы: