19
EN
Pressure drop diagram (calculated with P1 = 50 mbar)
Table 3
SIL LEVEL
Parameter
Value
Hardware Failure Tolerance - HFT
0
Common Cause Failure - CCF in points
75
Safe Failure Fraction - SFF in %
65%
Expected Lifetime Cycles - B
10d
251278
Expected Lifetime - T
10d
[years]
87
Probability of Dangerous Failures - PFH
D
[1/h]
1.33E-07
Performance Level - PL
d
Safety Integity Level - SIL
2
Mean Time to Dangerous Failure - MTTF
D
[years]
860
DESIGNED LIFETIME
Designed operating cycles (According to EN 161)
Time (years)
from 100.000 to 200.000 depends on diameter
10
Table 4
Vite / Screw
M5
M6
M8
M10
M12
Max. torque (N.m)
Galvanised
6
10
25
49,5
84,5
Stainless Steel
4,5
7,5
18,5
37
63,5
dv = density relative
to the air
1) methane
2) air
3) town gas
4) lpg