Installation
Greenstar Utility
ErP -
6 720 821 751 (2018/04)
25
▶
Fill the condensate trap [6] with 500ml of water via the
condensate collection sump [9].
▶ Check the water is running away and the condensate pipework joints
are water tight.
▶ Check the flue manifold cover seal is undamaged and seated
correctly.
▶ Refit flue manifold access cover [10] and secure with screws [11].
Fire valve
Check that the oil supply pipe has a fire valve fitted externally to the
building with the fire valve sensor located within the appliance case.
A fire valve sensor clip is provided for this purpose on the support bar
between the side panels.
The fire valve label, on the support bar, states that the fire valve should
be rated at 85°C or above to avoid nuisance cut outs.
Fig. 33
[1]
CH Return 28mmØ copper - male
[2]
CH flow /heating vent 1¼ ” Ø BSP female
[3]
90° elbow (not supplied)
[4]
Condensate pipe - not supplied
[5]
Condensate outlet (21.5mmØ) - supplied
[6]
Internal condensate trap
[7]
Oil isolating valve
[8]
Oil supply pipe - not supplied
[9]
Condensate collection sump
[10] Flue manifold access cover
[11] Flue manifold access cover screws
[12] Primary drain
5.6
Oil burner and pump - Riello RDB burners
Oil burner
• RIELLO RDB 3.2 BX (32/50)
• RIELLO RDB 3.2 BT (50/70)
Oil pump - Single pipe connection
Connecting the oil pump for a single pipe system:
▶ The pump is factory set for single pipe operation with the flexible oil
pipe fitted.
▶ Check connections before use.
Oil pump - two pipe connection
Converting the oil pump for a double pipe system:
1. Check the inlet pipe connection.
▶ Unscrew the return plug [1].
▶ Screw in the by-pass screw [2] that is supplied in a plastic bag
attached to the oil pump.
2. Connect the flexible oil pipe return hose [3] (not supplied) to the oil
pump and return pipe fixing and tighten to secure (for routing see
figure 33.
Fig. 34 Converting to double pipe system
[1]
Return plug
[2]
By-pass screw
[3]
Return pipe connection
NOTICE:
The condensate trap must be correctly filled to
prevent the possibility of potentially harmful flue
products escaping via the condensate pipework.
6720821751-22.1W
o
52mm (min.)
5
6
2
4
3
2
1
7
12
9
10
11
8
CAUTION:
▶ Isolate the oil and mains electrical supply before
starting any work and follow all relevant safety
precautions.
6720813344-19.1W
o
1
3
2