18. Fault Finding
NOTE
: This fault finding information is for guidance only. Worcester Heat systems cannot be held responsible for costs incurred by
persons not deemed to be competent.
To use this guide, operate the boiler and follow the observations down the left hand column until the boiler fails. The associated tests
will help find the fault.
This guide assumes a component failure has occured following a period of normal runing. It is not intended to solve installation errors.
PRELIMINARY CHECKS
Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of the
Service/Fault-finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY,
(b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH.
Switch on the mains
electrical supply.
Is the facia
indicator
illuminated?
Is there mains
230V
at connector X1?
Has fuse
F1
blown?
Replace fuse and
investigate cause.
Suggestions: Cable
damage, connections to (or
faults within) pump, fan,
external system controls.
Refer to
BOILER DEMAND TEST
Replace control board
(Section 15.4.9)
Check electrical
supply to boiler
FACIA INDICATOR TEST
No
Yes
Yes
Yes
No
No