Control unit
31
Uni Condens 8000 F – 6720867056 (2016/10)
▶ Plug the user interface [1] into the base of the casing.
Fig. 36 Plug the user interface into the base of the casing
[1]
HMI
[3]
Separate the back panel from the base of the casing.
▶ Mount the cover hood [2] on the control unit (
▶ Secure the control unit cover hood [2] by tightening the screws
(
Fig. 37 Fit the cover hood to the control unit
Adjusting the high limit safety cut-out for the CC 8000
The default setting of the high limit safety cut-out is 99 °C. It can be set to
110 °C.
▶ Observe service instructions of the control unit.
7.3.3
Control unit settings
If a control unit from the CC 8000 series is used, burner modulation in
standard mode is not enabled for 2.5 minutes.
Regulator settings
Table 14 Adjustable parameters for CC 8311 and CC 8312
00100117
8
4-001
1
3
Adjustable parameter
(max. temperature)
CC 8311/8312 CC 8311/8312
High limit safety cut-out (STB)
1)
1) Set the high limit safety cut-out as high as possible.
99 °C
110 °C
at least 5 K
Max. boiler water temperature
94 °C
105 °C
at least 7 K
Max. temperature demand of
heating circuit
2)
and DHW
3)
2) The temperature demand of heating circuits equipped with an actuator is
composed of the set flow temperature and the "boiler temperature increase"
parameter in the heating circuit data menu.
3) The temperature demand of DHW heating is composed of the set DHW
temperature and parameter "boiler temperature increase" in the DHW menu.
87 °C
98 °C
00100117
8
5-001
2
2.
2.
1.