background image

6 720 220 376

Revised 02-13                                Subject to change without prior notice

27

TSTBM3H2CPH6W-A

SPeCifiCAtionS 
tStBM3H2CPH6W-A thermostat 

The display range of temperature

41ºF to 95ºF (5ºC to 35ºC)

The control range of temperature

44ºF to 90ºF (7ºC to 32ºC)

Load rating

1 amp per terminal, 1.5 amp maximum all terminals combined

Display accuracy

± 1ºF

Swing (cycle rate or differential)

Heating is adjustable from 0.2ºF to 2.0ºF 

 

Cooling is adjustable from 0.2ºF to 2.0ºF

Power source

18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire)

Operating ambient

32ºF to +105ºF (0º to +41ºC)

Operating humidity

90% non-condensing maximum

Dimensions of thermostat

4.7”W x 4.4”H x 1.1”D

Frequency

916 MHz

Base Module

Load rating

1 amp per terminal, 1.5 amp maximum all terminals combined

Power source

18 to 30 VAC, NEC Class II, 50/60 Hz

Operating ambient

32ºF to +150ºF (0º to +65ºC)

Operating humidity

90% non-condensing maximum

Specifications

trouBleSHooting 

troubleshooting the thermostat communication with the base module or remote sensors:

If the thermostat is not 
communicating with the 

base module, follow 

these steps:

1.  Reestablish the communication following the steps on page 13

2.  Confirm that the base module has power from the air handler unit by 

observing that the LED lights are visible. If LED lights are off, verify that there 

is power to the air handler and the wiring between the air handler unit and 
base module are correct.

3.  Ensure that the thermostat has good battery power by checking if the battery 

icon is present or not. If the battery icon is present on the thermostat display, 

replace the batteries and perform the communication setup as described on 
page 13 again.

If the outdoor 
temperature sensor or 
remote room 
temperature sensor are 
not communicating with 

the thermostat, follow 

these steps:

1.  Reestablish the communication for that particular device following the steps 

in the manual for that component.

2.  Ensure that the remote sensor has good battery power by checking if the 

battery icon is present or not. The thermostat will also display “bA” next to the 
components name if the sensor’s batteries are low. If the battery icon is 

present on the sensor’s display, replace the batteries and perform the 

communication setup as described in that sensor’s manual.

Содержание TSTBM3H2CPH6W-A

Страница 1: ...Installation Manual TSTBM3H2CPH6W A 6 720 220 376 Revised 02 13 tTSTBM3H2CPH6W A thermostat and Wireless Communicating Base Module Thermostat Series ...

Страница 2: ...dule 13 Using Multiple TSTBM3H2CPH6W A wireless thermostats 13 Technician Setup Menu 14 Understanding Swing And Staging 22 HUM Terminal 22 DHM Terminal 22 Humidification Dehumidification Recommendation for Bosch Heat Pump 23 Setting Target Humidity Setpoint 23 Ambient Humidity Display 23 Recommended Cooling Settings 24 Set Time 24 Programming 24 Specifications 27 Troubleshooting 27 Contact your lo...

Страница 3: ...w these instructions This thermostat is shipped from the factory to operate a conventional heating and cooling system This thermostat will also operate a heat pump system See the heat pump confi guration step in the Tech Menu setup of this manual to configure the thermostat for heat pump applications THERMOSTAT QUICK REFERENCE Getting to know your thermostat 1 2 7 5 6 3 4 1 LCD Display 2 Glow in t...

Страница 4: ... target setpoint settings and keys Low Battery Indicator Replace batteries when this indicator is shown Programmable Time Period Icons This thermostat has 4 programmable time periods per day Clean Display Pressing CLEAN DISPLAY will allow 30 seconds to clean the display The keys will be inoperable during this time CLEAN will appear if your contractor has programmed a filter change reminder Press CL...

Страница 5: ...e TSTBM3H2CPH6W A and the base module is up to 100 feet with no obstructions and up to 50 feet in standard residential metal brick and concrete construction To extend the range try placing the base unit higher if in a basement or further away from large metal objects Do not install the base module in locations Where temperatures could exceed 150 F That could be exposed to rain or snow That could b...

Страница 6: ...Master Thermostat C terminal connected If you connect an outdoor remote and or indoor remote sensors it is required the thermostat be hardwired Caution To ensure a solid fit between the thermostat and the subbase mount the subbase on a flat wall with the drywall anchors flush to the wall Using the screws and drywall anchors that were provided with the thermostat Caution The TSTBM3H2CPH6W A can be ...

Страница 7: ...gn the 4 tabs on the subbase with corresponding slots on the back of the thermostat or base module Then push gently until the thermostat or base module on To insure a solid fit between the thermostat and the subbase 1 Mount subbase to a flat wall 2 Use screws provided 3 Drywall anchors should be flush with the wall 4 Wires should be pushed into the wall ...

Страница 8: ... BASE MODULE TSTBM3H2CPH6W A THERMOSTAT R C W2 C O W1 E B RH RC Y1 D G Y2 H PACKAGED HEAT PUMP Y1 Y2 R G C O B W2 E W1 2H 1C HEAT PUMP BASE MODULE TSTBM3H2CPH6W A THERMOSTAT R C W2 C O W1 E B RH RC Y1 D G Y2 H PACKAGED HEAT PUMP Y1 Y2 R G C O B W2 E W1 TYPICAL WIRING SCHEMATICS WIRELESS WITH BASE MODULE TSTBM3H2CPH6W A ...

Страница 9: ...EAT PUMP WITH GAS OIL FURNACE HEAT BACKUP G C R Y Y1 Y2 BASE MODULE C O B RH RC Y1 D G Y2 H TSTBM3H2CPH6W A THERMOSTAT R C BASE MODULE TSTBM3H2CPH6W A THERMOSTAT R C C O B RH RC Y1 D G Y2 H COMPRESSOR SECTION Y1 B C R FAN COIL AIR HANDLER R G Y1 Y2 C Y2 O Y1 B C R Y2 O W2 W1 E W2 W1 E W2 E W1 COMPRESSOR SECTION W W1 FAN COIL FURNACE ...

Страница 10: ...H COMPRESSOR SECTION Y1 Y2 C R FAN COIL AIR HANDLER R G Y1 Y2 C W2 W1 2H 2C AIR CONDITIONING W ELECTRIC HEAT BACKUP BASE MODULE TSTBM3H2CPH6W A THERMOSTAT R C W2 C O W1 E B RH RC Y1 D G Y2 H PACKAGED HEAT PUMP Y1 Y2 R G C O B W JUMP E W2 AT THE TSTBM3H2CPH6W A THERMOSTAT WHEN THE HEAT PUMP EQUIPMENT DOES NOT HAVE AN EMERGENCY HEAT TERMINAL Wiring Schematics ...

Страница 11: ...e 11 TSTBM3H2CPH6W A UNIT WITH ACTIVE OR PASSIVE DEHUMIDIFICATION AND HUMIDIFICATION RELAY BASE MODULE HUMIDIFIER SOLENOID W2 C O W E B RH RC Y1 D G Y2 H HVAC EQUIPMENT PASSIVE ACTIVE DEHUMIDIFICATION COMMON FROM HVAC EQUIPMENT HUMIDIFIER EQUIPMENT Wiring Schematics ...

Страница 12: ...midify D Dehumidify Dehumidify Dehumidify If separate transformers for heating and cooling are not present jump RC and RH terminals at the thermostat and connect the HOT lead from the transformer to RC Caution TSTBM3H2CPH6W A Wiring Notes In systems with no emergency heat relay a jumper can be installed between E and W2 Due to the internal circuitry a voltage potential will exist across any termin...

Страница 13: ... TSTBM3H2CPH6W A When a relay is on the corresponding LED relay indicator will be on If the base module does not receive a signal from the TSTBM3H2CPH6W A for 15 minutes it will turn off all relays until communication is reestablished The Blue LED on the base module will also turn off to show communication has been lost If communication has been lost for 1 hour and if the freeze protection feature...

Страница 14: ...tion Technician Setup Menu This thermostat has a technician setup menu for easy installer configuration To set up the thermostat for your particular application 1 Press MENU button 2 Press and hold TECHNICIAN SETUP button for 3 seconds This 3 second delay is designed so that homeowners do not accidentally access the installer settings 3 Configure the installer options as desired using the table be...

Страница 15: ...ng off OFF Compressor Short Cycle Delay min The compressor short cycle delay protects the compressor from short cycling This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off Selecting ON will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on Select OFF to remove this delay ON Cooling Swing The swing sett...

Страница 16: ...re cannot be lowered below this value Use the or keys to select the minmum cool setpoint 44 ºF ºF or ºC Select F for Fahrenheit temperature read out or select C for Celsius read out ºF for Fahrenheit ºC for Celsius ºF 12 or 24 Hour Clock You can select either a 12 or 24 hour clock setting Use the or keys to select 12 or 24 hour clock 12 Hour Clock Morning Recovery This feature turns your system on...

Страница 17: ...character to another See note below on operation OFF Beep When any key is pressed an audible beep will sound You can choose ON or OFF If ON is selected the beep will sound If OFF is selected there is no sound ON Heat Pump When turned on the thermostat will operate a heat pump 1 EM Heat will show as an option in the system switch 2 Y will be first stage of heat cool W E will be emergency heat relay...

Страница 18: ... OFF 15 30 60 or 90 seconds If 15 30 60 or 90 is selected the fan will not turn on for that many seconds when there is a call for cool and will run for that many seconds after satisfying a call for cool This feature is disabled when a TSTBM OTS TW A is used See Balance Point feature setup OFF Outdoor Sensor Enables the use of an outdoor sensor TSTBM OTS TW A Connecting a TSTBM OTS TW A allows for ...

Страница 19: ...ormation 1 Local Temp Sensor Disable the sensor on the master At least one TSTBM RRS TW A indoor remote sensor must be connected to disable the local TSTBM3H2CPH6W A sensor YES enables local TSTBM3H2CPH6W A sensor NO disables local TSTBM3H2CPH6W A sensor YES Freeze Protection Turns on the heat for 10 minutes each hour if unable to communicate with the TSTBM3H2CPH6W A master thermostat if there has...

Страница 20: ...xpired YES 15 30 45 60 75 90 continuous run time minutes NO NO Humidify This feature adds humidity when System key is in Heat Use the or keys to turn off or on If ON is selected the humidity will be displayed on the main screen and Hum terminal will energize when humidity setpoint is above ambient humidity in Heat mode off Dehumidify This feature removes humidity when System key is in Cool Use the...

Страница 21: ...tep Use the or keys to select the maximum number of degrees of over cool Options are 2 3 4 5 3 HUM Terminal Options for how the Hum terminal energizes Use the or key to select one of the four options View the HUM Terminal chart below for an explanation of these options 1 DHM Terminal Option for how DHM terminal energizes Use the or keys to select one of the four options View the DHM Terminal chart...

Страница 22: ...ing call is made or a FAN ON call is made 2 H terminal is energized when a heating call is made 3 H and G terminals are energized with and without a heating call 4 H terminal only is energized without heating call and remains energized with a heating call These setting and condition explanations assume humidity set point has not been satisfied and the equipment is attempting to actively humidify H...

Страница 23: ...equence in which dehumidification and humidification are being addressed to establish the correct thermostat settings Setting Target Humidity Setpoint Follow the steps below to change your target humidity setpoint 1 Press the HUMIDITY key 2 Use the key to select the target humidity setpoint 3 Press DONE when completed D and H Terminalsusethe R Terminalto completethecircuit Thisisanormallyopencircu...

Страница 24: ...P This thermostat has a programmable fan feature which allows you to run the fan continuously during any time period Set 5 1 1 Program Schedule To customize your 5 1 1 program schedule follow these steps Weekday 1 Select HEAT or COOL using the SYSTEM key Caution You have to program heat and cool each separately 2 Press MENU 3 Press SET SCHED Caution Monday Friday is displayed and the WAKE icon is ...

Страница 25: ...Leave 10 a m 62 F 17 C 83 F 28 C System Average Return 6 p m 70 F 21 C 75 F 24 C System Average Sleep 11 p m 62 F 17 C 78 F 26 C System Average Sunday Wake 8 a m 70 F 21 C 75 F 24 C System Average Leave 10 a m 62 F 17 C 83 F 28 C System Average Return 6 p m 70 F 21 C 75 F 24 C System Average Sleep 11 p m 62 F 17 C 78 F 26 C System Average HUM and DHM Terminals You can use the table below to plan y...

Страница 26: ...tem average ambient temperature reading The NEXT ZONE key can be pressed to change the priority The system information area of the display shows the priority For Example There is an TSTBM RRS TW A connected and it is named REMOTE 1 If the NEXT ZONE key is pressed until REMOTE 1 is shown then the REMOTE 1 ambient temperature reading will be used exclusively for that time period All other sensors wi...

Страница 27: ...mostat is not communicating with the base module follow these steps 1 Reestablish the communication following the steps on page 13 2 Confirm that the base module has power from the air handler unit by observing that the LED lights are visible If LED lights are off verify that there is power to the air handler and the wiring between the air handler unit and base module are correct 3 Ensure that the...

Страница 28: ...ior notice Revised 02 13 28 TSTBM3H2CPH6W A Contact your local Bosch Dealer or Installing Contractor for product support Field Technical Support 954 776 5471 Bosch 601 N W 65th Ct Ft Lauderdale FL 33309 www bosch climate us Contact Informaiton ...

Страница 29: ...repair and replacement of the defective component or part 7 Electricity or fuel costs or any increases or unrealized savings in same for any reason whatsoever 8 Damage caused by excessive temperatures or pressures fuel or gas explosion electrochemical reaction water and air impurities electrical failures use during construction flooding or acts of God 9 Any damage or failure resulting from the int...

Страница 30: ...LOSS OF TIME Note that any repaired or replaced product will be warranted for only the unexpired tem of the original warranty Some states do not allow the exclusion of limitation of damages or limitations on how long an implied warranty lasts so the above limitations and exclusions may not apply to you WARRANTY CLAIMS PROCESS If you have a warranty claim you should notify the contractor who instal...

Страница 31: ...6 720 220 376 Revised 02 13 Subject to change without prior notice 31 TSTBM3H2CPH6W A NOTES ...

Страница 32: ...601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www bosch climate us ...

Отзывы: