Indirect Fired Water Heaters Installation and Operating Manual  

Installation & Operating  Manual

 

2  Pre-installation

1. The installation must conform to the instructions in this 

manual and all applicable local, state, provincial, and 

national codes, laws, regulations, and ordinances. 

Installations in Canada must conform to B149.2 

Installation Code. 

2. Be certain the domestic water supply to the tank has 

physical and chemical characteristics that fall within the 

limits shown in Table 2A. Where questions exist as to 

the composition of the water on the job, a qualified 

water treatment expert should be consulted.

Water with characteristics outside the limits shown in 

Table 2A may severely shorten the life of the tank due 

to corrosion. Damage to tanks in such cases is not 

covered under warranty.

CAUTION

3. Read and understand all installation requirements in 

this manual.

Water Chemistry Requirements

                 Table 2A

Water used in the tank must have characteristics falling 

within the following limits:

Characteristic

Min.

Max.

Ph

6.0

8.0

Chloride (PPM)

--

80

Locating the Tank

1. Choose a location for your water heater centralized to 

the piping system. You must also locate the SST water 

heater where it will not be exposed to freezing 

temperatures. Additionally, you will need to place the 

water heater so that the controls, drain, and inlet/

outlets are easily accessible. This appliance must not be 

installed outdoors, as it is certified as an indoor 

appliance, and must also be kept vertical on a level 

surface. 

2. Keep distance between boiler and water heater to a  

minimum to: 

a. reduce piping heat loss 

b. provide minimal friction loss 

3. Figure 1-1 on page 6 shows the weights of all the tanks 

filled with water. Make sure that the location chosen for 

the tank is capable of supporting it.

This appliance must be placed where leakage from 

the relief valve, leakage from the related piping, or 

leakage from the tank or connections, will not result 

in damage to the surrounding areas, or to the lower 

floors of the building. A water heater should always 

be located in an area with a floor drain or installed in 

a drain pan suitable for water heaters. The 

manufacturer shall not be held liable for any such 

water damage.

CAUTION

4. The tank may be located some distance from the boiler 

provided the pump is designed to provide the flow 

called for in Table 3B - Pressure Drop Values, through 

the coil. Also, the further the tank is from the boiler, the 

longer the response of the boiler will be to a call from 

the tank zone. Insulate piping between the boiler and 

the tank.

Failure to properly support the tank could result in 

property damage or personal injury.

WARNING

Recommended Clearances

The installation location must provide adequate clearances 

for servicing and proper operation of the water heater. A 

12 inch vertical clearance is recommended from the top of 

the water heater. A zero clearance is allowed for the sides 

of the water heater. However, boiler and servicing 

clearances must be figured when locating the water 

heater.

Содержание SST150-40

Страница 1: ...installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage CAUTION The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Products 5th edition The pressure of the heat transfer medium must be limited to a maximum of 30 PSIG by ...

Страница 2: ...2 Indirect Fired Water Heaters Installation and Operating Manual Installation Operating Manual ...

Страница 3: ...Manual Installation Operating Manual Table of Contents 1 General Information 6 2 Pre installation 7 3 Boiler Side Piping 8 4 Domestic Side Tank Piping 13 5 Wiring 17 6 Start up and Check out 18 7 Maintenance 19 8 Performance Data 21 Limited Lifetime Warranty 25 ...

Страница 4: ...will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury WARNING CAUTION indicates a potentially hazardous situtation which if not avoided may result in minor or moderate injury CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may resul...

Страница 5: ...re all connections are tight Direct water flow away from any person Protection Must Be Taken Against Excessive Temperature and Pressure Installation of a Temperature Pressure T P relief valve is required Failure to adhere to the guidelines on this page can result in severe personal injury death or substantial property damage WARNING If the information in this manual is not followed exactly a fire ...

Страница 6: ...4 BOILER WATER OUT 5 DRAIN COLD WATER INLET 5 4 3 3 4 NPT 1 1 NPT SEE NOTE 1 2 SST150 SST450 PART NO A in B in C in D in E in F in SST150 40 SST250 65 SST300 80 SST450 119 3 3 1 4 3 1 4 3 1 4 8 1 4 9 1 4 9 1 4 9 1 4 25 1 4 28 31 3 4 48 1 2 52 1 2 61 3 4 60 1 4 56 60 70 69 20 24 24 28 WEIGHT FULL OF WATER lbs 515 820 921 1268 28 Figure 1 1 Single Wall Heat Exchanger National Standard Plumbing Code ...

Страница 7: ... as it is certified as an indoor appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on page 6 shows the weights of all the tanks filled with water Make sure that the location chosen for the tank is capable of supporting it This appliance must be placed whe...

Страница 8: ...culator zone piping Zone with Valve to Aquastat As with the circulator zone system this system is just like a standard heating zone system except that one of the zones is connected to the tank coil as shown in FIG 3 3 The system circulator must be large enough to move boiler water through the coil regardless of the flow rate required through the heating zones Pressure Drop Values Table 3B Model Wa...

Страница 9: ...AT HOT WATER OUT CHECK VALVE SST series tank DRAIN POINT Y STRAINER RECOMMENDED GB 142 BOILER AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR PRESSURE RELIEF VALVE Figure 3 1 GB142 Boiler Low Loss Header piping Please note that these illustrations are meant to show system piping concept only the installer is responsible for all equipment and detaili...

Страница 10: ...E 3 ZONE 4 ZONE CIRCULATORS TYPICAL FLOW CHECK VALVE SYSTEM SUPPLY SENSOR WHEN USED TANK SENSOR AQUASTAT PRESSURE RELIEF VALVE Y STRAINER RECOMMENDED DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE GB 142 BOILER BALL VALVE Figure 3 2 Piping diagram zoned with circulators Please note that these illustrations are meant to show system piping concept only the in...

Страница 11: ...NE 4 ZONE VALVES TYPICAL DIFFERENTIAL PRESSURE BYPASS VALVE IF USED SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED TANK SENSOR AQUASTAT PRESSURE RELIEF VALVE DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE SST series tank DRAIN POINT Y STRAINER RECOMMENDED GB 142 BOILER BALL VALVE Figure 3 3 Piping diagram zoned with valves Please note that these illustrations are meant to show system piping c...

Страница 12: ...AQUASTAT TYPICAL CHECK VALVE SST series tank SST series tank FROM SYSTEM DRAIN POINT Y STRAINER RECOMMENDED GB 142 BOILER AIR SEPARATOR EXPANSION TANK BALL VALVE TYPICAL SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR Figure 3 4 Multiple tank connections Please note that these illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing r...

Страница 13: ...w preventer check with the appropriate authority to find out whether one backflow preventer may be used for tanks or each tank must be equipped with its own backflow preventer If each tank must have its own backflow preventer each tank must also have its own expansion tank If a common backflow preventer is permitted an expansion tank must be sized to accommodate the expansion volume of all tanks D...

Страница 14: ...in valve and fittings are supplied by others Standard Installation Install a tee connection at the domestic cold water inlet FIG 4 1 DRAIN VALVE Figure 4 1 Drain valve installed Temperature Pressure T P Relief Valve For protection against excessive temperatures and pressure install temperature and pressure protective equipment required by local codes but not less than a combination temperature and...

Страница 15: ...iceable for a temperature of 250 F or greater directed so that hot water flows away from all persons directed to a suitable place for disposal installed so as to allow complete draining of the T P relief valve and discharge line terminated within 6 of the floor T P relief valve discharge piping must not be excessively long Using more than two 2 elbows or 15 feet of piping can reduce discharge capa...

Страница 16: ...NTER SHUTOFF VALVE SHUTOFF VALVE ANTI SCALD MIXING VALVE DRAIN FIELD SUPPLY RECIRCULATION PUMP TO BOILER FROM BOILER CHECK VALVE TANK SENSOR AQUASTAT SST SERIES TANK Figure 4 2 Recommended domestic water piping Please note that these illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE ...

Страница 17: ...d Zone Circulator Valve 1 Install Aquastat to tank Aquastat control Honeywell L4006 or equivalent can be ordered from your local distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIRECT TANK AQUASTAT CONTROL Honeywell L4006 or equivalent TEMPERATURE ADJUSTMENT WIRE CONNECTIONS ZONE CONTROL BOX OR ZONE VALVE OR ZO...

Страница 18: ...r heater will be unused for an extended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and that no exposed high voltage wiring is present 4 Make sure that each zone valve or circulator operates when and only when its thermostat calls for heat Let each zone oper...

Страница 19: ...ping DANGER Plugging the T P relief valve or discharge piping can cause excessive pressure in the water heater resulting in severe personal injury death or substantial property damage 5 Review homeowner s maintenance responsibilities and their frequencies including any not listed in the following section Homeowner monthly maintenance to include 1 Visually check valves pipes and fittings for leaks ...

Страница 20: ...gy of Commercial Products A maximum 50 50 mixture of inhibited propylene glycol is recommended Follow the antifreeze manufacturer s instructions Do not use automotive ethylene glycol or petroleum based antifreeze Do not use any undiluted antifreeze This can cause severe personal injury death or substantial property damage WARNING ...

Страница 21: ...Heat Source Flow Rate GPM Tank Heat Source Friction Loss Feet W C SST150 40 40 0 1 6 0 7 181 208 115 000 14 0 4 5 SST250 65 67 0 1 9 0 5 263 327 154 000 14 0 5 7 SST300 80 81 5 2 1 0 5 285 358 171 000 14 0 6 1 SST450 119 113 4 3 2 0 4 349 459 216 000 14 0 6 5 These ratings were obtained with a heat source output and heat source flow rate as listed in the chart using the parameters of the Domestic ...

Страница 22: ...ate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour Rating of the STS tank must be equal to or exceed the total first hour requirements Peak Hour Demand Worksheet Description Fill in the Blank Example 40 Gallons for the first 2 people ___________________________ Gals 40 Gals 10 Gallons for each additional person _____________...

Страница 23: ...5 000 122 97 122 97 153 128 153 128 60 000 150 118 150 118 183 149 183 149 75 000 179 138 179 138 213 170 213 170 95 000 217 165 217 165 217 165 252 197 252 197 252 197 115 000 217 165 252 189 252 189 252 189 291 226 291 226 291 226 291 226 140 000 252 189 267 200 282 211 286 208 305 235 319 245 338 259 338 259 338 259 165 000 267 200 282 211 286 213 305 235 319 245 356 271 386 293 388 294 195 000...

Страница 24: ...193 159 226 193 226 193 75 000 222 180 222 180 255 213 255 213 95 000 261 207 261 207 261 207 294 241 294 241 294 241 115 000 300 235 300 235 300 235 300 235 333 268 333 268 333 268 333 268 140 000 304 238 347 268 347 268 347 268 347 268 384 302 382 302 382 302 382 302 382 302 165 000 304 238 349 270 374 288 395 302 395 302 387 306 429 337 429 337 429 337 429 337 195 000 349 270 374 288 409 312 42...

Страница 25: ...mbly upon the payment of a proportional charge based upon the time the TANK has been in service Replacement will be made with the nearest comparable model available from BTC at the time of such replacement The proportional charge will be equal to the appropriate percentage of the current list price of such TANK or the then nearest comparable BTC model at the time the warranty claim is made and wil...

Страница 26: ...ve at the time of installation Any TANK that has a failure or malfunction resulting from failure to keep the tank full of potable water failure to assure that water in the tank is free to circulate at all times failure to keep the tank free of water sediment or scale deposits or failure to inspect the anode rods at intervals of not more than two years Any TANK that is installed where polybutylene ...

Страница 27: ... 27 Indirect Fired Water Heaters Installation and Operating Manual Installation Operating Manual ...

Страница 28: ...United States and Canada Bosch Thermotechnology Corp 50 Wentworth Avenue Londonderry NH 03053 Tel 603 552 1100 Fax 603 584 1681 www bosch us BTC 471003301 A 09 2010 SST I O Rev A ...

Отзывы: