SSB
16 | Control Panel (LCD Display)
Below is a list of parameters:
Number
Description
Unit
Default
Min
Max
Step
3
CH Setpoint
°C / °F
176 °F
68 °F
194 °F
0.9 °F
19
Design Supply Temp
°C / °F
176 °F
68 °F
194 °F
1.8 °F
21
Baseline Supply Temp
°C / °F
104 °F
68 °F
194 °F
1.8 °F
48
DHW/Tank Setpoint
°C / °F
120.2 °F
104 °F
140 °F
0.9 °F
64
Preheat Mode
-
Comfort
Eco
Comfort
-
72
Permit emergency mode
-
Yes
No
Yes
-
Tab. 6 Level 1 parameters (USER)
Number
Description
Unit
Default
Min
Max
Step
1
Central Heating (CH) Mode
-
1
0
5
1
2
Pump Mode
-
0
0
4
1
4
System Pump Overrun
Seconds
300
0
900
10
5
Boiler Pump Overrun
Seconds
300
0
900
10
7
CH Hysteresis
°C / °F
5.4 °F
0
36 °F
0.9° F
9
Anti Cycle Period
Seconds
180
10
900
10
10
Anti Cycle Temp Diff
°C / °F
12.6 °F
0°F
36 °F
0.9° F
11
Ramp Delay Step Mod.
On / Off
Disabled
14
Max Power CH
%
100
50
100
1
15
Min Power CH/DHW
%
1
1
30
1
20
Design Outdoor Temp
°C / °F
24.8 °F
-13 °F
77 °F
1.8 °F
22
Baseline Outdoor Temp
°C / °F
69.8 °F
35.6 °F
86 °F
1.8 °F
23
Design Supply Min Limit
°C / °F
68 °F
39.2 °F
179.6 °F
1.8 °F
24
Design Supply Max Limit
°C / °F
194 °F
80.6 °F
194 °F
1.8 °F
25
Warm Weather Shutdn
°C / °F
69.8 °F
35.6 °F
95 °F
1.8 °F
26
Boost Temp Increment
°C / °F
0 °F
0 °F
54 °F
0.9 °F
27
Boost Time Delay
Minutes
20
1
120
1
28
Night Setback Temp.
°C / °F
18 °F
0 °F
90 °F
0.9 °F
29
Weather Setpoint
°C / °F
68 °F
32 °F
122 °F
0.9 °F
35
DHW Mode
-
0
0
2
1
36
DHW Tank Hyst. Down
°C / °F
7.2 °F
0 °F
36 °F
0.9 °F
37
DHW Tank Hyt. Up
°C / °F
0 °F
0 °F
36 °F
1.8 °F
38
DHW Tank Supply Extra
°C / °F
54 °F
0 °F
54 °F
0.9 °F
42
DHW Priority
-
0
0
2
1
43
DHW Max Priority Time
Minutes
30
1
255
1
44
DHW Pump Overrun
Seconds
15
0
255
1
73
Boiler Address
-
0
0
16
1
74
Emergency Setpoint
°C / °F
113 °F
68 °F
149 °F
0.9 °F
75
Delay Per Start Next Dep.
Seconds
15
5
300
5
76
Delay Per Stop Next Dep.
Seconds
15
5
300
5
77
Hyst Down Start Boiler
°C / °F
9 °F
0 °F
36 °F
0.9 °F
78
Hyst Up Stop Boiler
°C / °F
3.6 °F
0 °F
36 °F
0.9 °F
79
Max Setp Offset Down
°C / °F
7.2 °F
0 °F
36 °F
0.9 °F
80
Max Setp Offset Up
°C / °F
18 °F
0 °F
36 °F
0.9 °F
81
Start Mod Delay Fact
Minutes
5
0
60
1
82
Next Boiler Start Rate
%
80
10
100
1
83
Next Boiler Stop Rate
%
30
10
100
1
84
Boiler Rotation Interval
Days
1
0
30
1
85
DHW Boiler Assign
-
0
0
16
1
Tab. 7 Level 2 parameters (INSTALLER)
(*) Depend on appliance type
(**) The value for this parameter is:
•
4 for SSB160
•
5 for SSB120
•
6 for SSB85