RADION receiver OP
RADION glassbreak | en
21
Bosch Security Systems, Inc.
Reference Guide
2014.12 | 02 | F.01U.261.835
–
For armor-coated glass installations, mount the sensor no more than 12 ft (3.65 m) from
the glass
–
Mount the detector in the direct line of sight of the glass to be protected
–
On an opposite, or adjoining wall, within a range of 20 ft (6 m) for plate, tempered,
laminated, and wired glass
–
In a suitable environment: temperature between -18 and 50*C (0 and 120*F); and humidity
between 10 and 90% non-condensing
Avoid mounting the detector in:
–
Glass airlocks and glass vestibule areas
–
Humid rooms
–
Small utility rooms
–
Rooms with noisy equipment (white noise) such as air compressors, bells, and power
tools
–
Rooms smaller than 10 ft x 10 ft (3 m x 3 m)
–
Rooms with lined, insulating, or sound supressing drapes
–
A corner of a room
Avoid locations that expose the detector to possible false-alarm sources such as:
–
Glass airlocks and vestibule areas;
–
Kitchens;
–
Corner mounting;
–
Residential car garages;
–
Stairwells
–
Bathrooms; and
–
Small acoustically live rooms
Notice!
Glassbreak detectors are intended only as a component of a perimeter protection system.
Use glassbreak detectors in conjunction with motion detectors.
5.2
Testing
Test the detector at least once yearly. Use the Sentrol 5709C hand-held tester to enter the
sensor into test mode and to test the alarm.
Test the sensor alarm
To test the sensor functionality, enter the detector into test mode. In normal mode, the sensor
does not generate an alarm on sound signals from the tester unless the tester is held next to
the sensor.
Each time the sensor alarms, it also goes into test mode for one minute.
Initiating test mode with the Sentrol 5709C hand-held tester:
1.
Set the tester for tempered or laminated glass, unless the protected glass is plate glass.
2.
Hold the tester on top of the detector.
3.
Activate the tester. The detector alarms and goes into test mode for one minute. During
test mode, the LED blinks continuously. To extend test time, activate the tester within the
range of the sensor at least once each minute.
Performing the alarm test with Sentrol 5709C hand-held tester:
1.
Hold the tester near the surface of the glass to be protected and aim the speaker at the
sensor. Be sure the tester is at the point on the glass farthest from the detector.