Operation 49/60
RE 30028-B/09.13, VT-VPCD,
Bosch Rexroth AG
Analog I/O
Inputs
Level 1
Level 2
Level 3
Level 4
Level 5
Pressure CMD
Max Unit
[450] bar
Fig. 29: Configuration example
The menu tree “Parameters” was selected in this example.
5.
Press the control keys “ENT” and “ESC” simultaneously and hold them down
(for at least 2 seconds) until “Setup” is shown on the display of the control
electronics.
The control electronics is now in the configuration mode.
6.
Use the control key “UP” or “DOWN” to navigate to menu item “Analog I/O”.
7.
Press the control key “ENT”.
The control electronics is now at the second level of the configuration menu
“Analog I/O”.
8.
Use the control key “UP” or “DOWN” to navigate to the menu item “Inputs”.
9.
Press the control key “ENT”.
10.
Use the control key “UP” or “DOWN” to navigate to the menu item “Pressure
CMD“.
11.
Press the control key “ENT”.
12.
Use the control key “UP” or “DOWN” to navigate to the menu item “Max Unit”.
13.
Press the control key “ENT”.
The value currently set is displayed.
14.
Press control key “UP”. This will create a positive sign. To create a negative sign,
press the “DOWN“ key.
15.
Press the “UP” control key repeatedly until “4” appears on the display.
16.
Press the control key “ENT”.
17.
Press the “UP” control key repeatedly until “5” appears on the display.
18.
Press the control key “ENT”.
19.
Press the “UP” control key repeatedly until “0” appears on the display.
20.
Press the control key “ENT”.
21.
Press the “UP” control key repeatedly until “.” appears on the display.
22.
Press control key “ENT”.
23.
Press the “UP” control key repeatedly until “0” appears on the display.
24.
Press the control key “ENT”.