
3 608 878 300
Tightening Technology |
Bosch Rexroth AG 309
System 350
| 3 608 878 300/2019-03
6.4.6
Effects stop field bus and communication stop field bus to I/O signals
Table
shows the behavior of the input signals and the output signals at the interface of the
Tightening System 350, if
•
the PLC partner controller stops communicating with the Tightening System 350 suddenly
•
a field bus cable is disconnected
6.4.7
Error messages in connection with field buses
Table 6–56:
Behavior of the I/O signals in case of stop field bus and communication stop field bus
Field bus
Action
Effects on I/O interface
Profibus
1. Commissioning system with
Profibus master
2. Select “
End communication
”
– all inputs are set to LOW, i.e. they
are reset
– the outputs are/remain set
accordingly or are reset
DeviceNet
1. Commissioning system with
DeviceNet master
2. Select “
End communication
”
EthernetIP
1. Commissioning system with
EIPScan test tool
2. Select "
End communication
(RUN MODE)
"
Profinet
1. Commissioning system with
SIMATIC S7 and OPC server
2. Select “
End communication
(disconnect server)
”
ModbusTCP
For ModbusTCP, communication is implemented according to the client
server principle
Stopping the communication has effects on the input and output signals of
the Tightening System 350. The reason for this is that the input signals are
not polled continuously ("polling"). Instead, the input signals are set "once".
They maintain this value until they are reset.
Error
code
Error
class
Message
Possible cause/
consequence
Suggested solution
800
1
Unknown module in <A>
Module is not supported
Use Rexroth modules
801
4
Driver error in <A>
Driver error in module
Check module in slot
Implement system reset
802
1
Driver number in <A> invalid
Driver number incorrect
Implement system reset
803
1
Invalid number of I/O in <A>
Check field bus configuration
Configuration of PLC
assignment table
804
1
Driver exception in <A>
Exception in module driver
Check module in slot
Implement system reset
805
1
Field bus configuration error
Module reports configuration
error
Check field bus configuration
806
4
Field bus <-> Master interrupted
Ensure master connection
820
3
IMpdp: Number of send/receive
errors
Not enough storage space
reserved on module
Check field bus configuration
836
4
IMdev: Serial number error
Read in error of serial
number
Implement system reset
Содержание Rexroth Tightening System 350
Страница 4: ...4 641 Bosch Rexroth AG Schraubtechnik System 350 3 608 878 300 2019 03 ...
Страница 120: ...120 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Страница 194: ...194 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Страница 638: ...638 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...