Fig. 10-15:
Correlation between duty cycle and torque.
10.3.2
Determining the duty cycle
The approximate determination of the relative duty cycle ED
ideal
is performed
via the correlation:
ED
ideal
Cyclic duration factor in %
M
N
Continuous rated torque in Nm
M
max
Maximum torque in Nm
Fig. 10-16:
Approximate determination of duty cycle ED
Prerequisites: Linear correlation between torque and current.
For MBT motors acc. to
, only an approximate duty cycle calcula‐
tion is possible since there is a non-linear correlation between torque and
current.
To roughly determine potential duty cycles in case of short-time duty forces
with M
KB
≤ 1.5 M
N
, this calculation is valid.
For an exact determination of the relative duty cycle of the syn‐
chronous torque motors MBT, use
or
.
The non-linearity of the characteristic curve torque via current of synchronous
torque motors leads to an increased rise of power loss at higher torque
forces. This increased power loss leads - in particular at a high percentage of
acceleration and deceleration processes - to a possible duty cycle that is re‐
296/409
Motor dimensioning
MBT High Synchronous Torque Motors
Bosch Rexroth AG R911298798_Edition 08
Содержание rexroth MBT
Страница 1: ...MBT High Synchronous Torque Motors Project Planning Manual R911298798 Edition 08 ...
Страница 18: ...6 409 MBT High Synchronous Torque Motors Bosch Rexroth AG R911298798_Edition 08 ...
Страница 32: ...20 409 MBT High Synchronous Torque Motors Bosch Rexroth AG R911298798_Edition 08 ...
Страница 240: ...228 409 MBT High Synchronous Torque Motors Bosch Rexroth AG R911298798_Edition 08 ...
Страница 298: ...286 409 MBT High Synchronous Torque Motors Bosch Rexroth AG R911298798_Edition 08 ...
Страница 416: ...404 409 MBT High Synchronous Torque Motors Bosch Rexroth AG R911298798_Edition 08 ...
Страница 421: ...Notes MBT High Synchronous Torque Motors 409 409 ...