1.13.2
Connecting the bonding conductor
Connect the bonding conductor to the product:
View
Connection
Signal name Function
Equipment
grounding
conductor
Connection point of bonding conductor
Is used to connect the product to a
grounded part of the installation, e.g. the
machine base
Thread M5 (for ring cable lug)
Unit
min.
max.
Tightening torque
Nm
2.6
3.1
Cable cross section stranded wire
mm
2
4
-
Cable cross section solid wire
mm
2
6
-
1.14
Commissioning
Explosion hazard if acceptance test of the
overall system has not been carried out!
WARNING
Commissioning in potentially explosive atmospheres is prohibited until it has
been ascertained that the overall system corresponds to the demands and
certification conditions for explosion protection.
Personal injury or property damage by errors
in the control of motors and moving parts!
Unclear operating states and product data!
WARNING
Do not carry out commissioning under the following circumstances:
●
Connections, operating states or product data are unclear or faulty
●
Safety devices and monitoring systems of the installation are damaged
or not in operation
Never operate any damaged products.
Contact Rexroth for missing information or support during commissioning.
Preparation
1.
Have the documentations (Operating Instructions, declaration of
conformity, data sheets, …) of all devices used ready at hand.
2.
Check the devices for damage.
3.
Check all mechanical and electrical connections (including the bonding
conductor!).
4.
Record all measures taken in the commissioning log.
5.
Activate the safety devices and monitoring systems of the installation.
Procedure
When all requirements have been met, proceed as follows:
14/29
Operating instructions
KSM02 Motor-Integrated Servo Drives Operation in Potential‐
ly Explosive Atmospheres ATEX Directive 2014/34/EU