F3145 Error when unlocking the safety door
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive is decelerated according to the setting in
P-0-0119, Best
possible deceleration
- or -
the axis already is in "safety related standstill".
The output stage is switched off via two channels.
Cause
Remedy
Error in mechanical system of safety door
Check mechanical system of safety door
Error in wiring of safety door, e.g. short circuit
between I/O10n and 24 V or O10n and 0 V; driver at
output of O10n defective
Check wiring of safety door
Then start command
S-0-0099, C0500 Reset class 1 diagnostics
in
order to clear error and then set drive enable again.
F3145 - Attributes