MPH-02, MPB-02, MPD-02
Drive Control
6-63
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
value 1 and the actual position value 2, in cyclic operation (phase 4),
are monitored for a maximum allowed actual position value difference
indicated in parameter
S-0-0391, Monitoring window feedback 2
. If
the absolute value of the difference is greater than the value of the
monitoring window, the
F2036 Excessive position feedback
difference
error message is generated.
•
The output of the position loop (P-0-0048) is limited to a maximum
absolute velocity value. The output signal of the position loop is a
velocity command value that already contains the additive component
for velocity feedforward, plus a possibly preset additive velocity
command value (S-0-0037). The limitation therefore has an effect on
the sum of the different command values.
6.5 Limitations
Overview
Limitations in Open-Loop Operation (U/f Operation)
To protect the device or motor the following parameterizable limitations
have been implemented in open-loop operation:
•
current and torque limitation
•
current
limitation
•
torque/force
limitation
•
stall protection loop for current limitation
•
current limitation loop
•
position
limitation
•
travel range limit switch
•
software limit switch
Limitations in Closed-Loop Operation
To protect the device or motor the following parameterizable limitations
have been implemented in closed-loop operation:
•
current and torque limitation
•
current
limitation
•
torque/force
limitation
•
velocity
limitation
•
position
limitation
•
travel range limit switch
•
software limit switch
Limiting the Velocity Command
Value