Inverter - Routing the Motor Power Cables
With cable duct
Without cable duct
B
Area B
C
Area C
1
Cable duct for mains connection lines
2
Shield connection of motor power cable via
clips at least at one point; alternatively, at the
device or on mounting plate at control cabinet
3
Cable duct for motor power cables
Fig.6-3:
Routing of Motor Power Cables With Cable
Duct
B
Area B
C
Area C
1
Cable duct for mains connection lines
2
Shield connection of motor power cable via
clips at least at one point; alternatively, at the
device or on mounting plate at control cabinet
3
Control cabinet outlet of motor power cables
Fig.6-4:
Routing of Motor Power Cables Without Cable
Duct
Fig.6-5:
Routing of Cables for Inverter
6.3
Ground Connections
Housing and Mounting Plate
By means of appropriate ground connections, it is possible to avoid the emis‐
sion of interference, because interference is discharged to ground on the
shortest possible way.
Ground connections of the metal housings of EMC-critical components (such
as filters, devices of the drive system, connection points of the cable shields,
devices with microprocessor and switching power supply units) have to be well
contacted over a large surface area. This also applies to all screw connections
between mounting plate and control cabinet wall and to the mounting of a
ground bus to the mounting plate.
The best solution is to use a zinc-coated mounting plate. Compared to a lac‐
quered plate, the connections in this case have a good long-time stability.
Connection Elements
For lacquered mounting plates, always use screw connections with tooth lock
washers and zinc-coated, tinned screws as connection elements. At the con‐
nection points, remove the lacquer so that there is safe electrical contact over
a large surface area. You achieve contact over a large surface area by means
of bare connection surfaces or several connection screws. For screw connec‐
tions, you can establish the contact to lacquered surfaces by using tooth lock
washers.
Metal Surfaces
Always use connection elements (screws, nuts, plain washers) with good elec‐
troconductive surface.
Bare zinc-coated or tinned metal surfaces have good electroconductive prop‐
erties.
Bosch Rexroth AG
DOK-INDRV*-HMS02*UL***-IB03-EN-P
Rexroth IndraDrive Drive Controllers Power Sections HMS02
54/67
EMC Measures for Design and Installation
Содержание Rexroth IndraDrive HMS02
Страница 2: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 13: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 X 67 ...
Страница 29: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 26 67 ...
Страница 63: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 60 67 ...