Effect of the Settings in the Device
Fig.5-11:
Internal Effect of the Settings
5.2.4
X5, Connection of Motor Cable (PE, U, V, W)
The motor cable can have a total length of 100 m if it is a standard type. If
you use a shielded cable or run the cable in a well-grounded metallic cable
duct, the total length should not exceed 30 m.
See also chapter 6 "EMC Measures for Design and Installation"
For operation with several motors, the total motor cable length is
the sum of all individual cable lengths.
Fig.5-12:
Motor Cable
5.2.5
X5, Connection of Braking Resistor (+B, -B)
The terB/-B are provided for connection of a suitable braking resis‐
tor. For the connection, select a twisted and shielded line which is as short as
possible (maximum allowed length 2 x 5 m).
DOK-INDRV*-FCS01******-IT01-EN-P
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
Bosch Rexroth AG
41/69
Instructions for Use