24 V Supply Voltage of the Main Circuit U
M
The 24 V voltage for the main circuit supply U
M
on terminal 2.2 is not used for
IndraControl L45/L65/L85.
A main circuit U
M
begins at a power terminal at the IndraControl L45/L65/L85
and is lead to the next power terminal through all following terminals. At the
next power terminal, a new circuit is started; its potential is isolated from the
previous one.
Several power terminals can be used within one station.
Function
Several segments, independent from each other, can be created within the
main circuit. The main circuit provides the voltage potential, from which the
segment voltages (U
S
) are derived. The splitting into segments permits to pro‐
tect or switch e. g. the supply of several actuators separately.
Current carrying capacity
The maximum current carrying capacity is 8 A (total current with the segment
circuit). If the limit value has been reached, a new power terminal must be used.
U
M
U
S
U
L
U
ANA
GNDL
U
LS
U
M
U
M
IndraControl
Rexroth Inline
PWR IN
PWR IN
SEG/F
PWR IN
Voltage terminal at IndraControl L45/L65/L85
R-IL 24
PWR IN
Power terminal
R-IL 24
SEG/F
Segment terminal with fuse
Fig.7-8:
Main circuit
Generation of U
M
In the simplest case, the main voltage U
M
can be supplied at the IndraCon‐
trol L45/L65/L85.
U
M
can also be supplied via a power terminal. A power terminal is to be used
in the following cases:
1.
An electrical isolation is to be set up.
2.
The maximum current carrying capacity of a voltage jumper (
M
, U
S
or GND,
total current of U
S
and U
M
) is reached.
+24 V Voltage of Segment Circuit U
S
Connect the segment circuit U
S
to contact 1.1. The segment circuit supply U
S
is supplied through the following series Rexroth Inline I/O terminals. It forms the
segment circuit or auxiliary circuit (via voltage jumpers) of the Rexroth Inline
terminals and the onboard I/Os.
The segment circuit with the segment voltage U
S
starts at the IndraControl L45/
L65/L85 or a supply terminal (power terminal or segment terminal) and is sup‐
plied through all following terminals up to the next supply terminal.
Function
Several segment terminals within a main circuit can be used and thereby seg‐
ment the main circuit. The reference to ground is the same as that of the main
circuit. Thus, different fused electric circuits can be implemented within the sta‐
tion without any external cross-wiring.
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG
35/81
Connections and Interfaces
Содержание Rexroth IndraControl L45
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 6: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control IV 81 ...
Страница 20: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control 18 81 ...
Страница 26: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control 24 81 ...
Страница 32: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control 30 81 ...
Страница 76: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control 74 81 ...
Страница 80: ...Bosch Rexroth AG DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control 78 81 ...
Страница 83: ...Notes DOK CONTRL ICL45L65L85 PR01 EN P Rexroth IndraControl L45 L65 L85 Control Bosch Rexroth AG 81 81 ...