In operation
Storage / Transport
Air pressure
Up to 2700 m above MSL
according to DIN 60204
Up to 3000 m above MSL
according to DIN 60204
Mechanical strength
Max. vibration:
Frequency range:
10...150 Hz
Excursion: 0.003 in at
10..0.57 Hz
Acceleration: 1 g at
57...150 Hz
According to EN
60068-2-6
Max. shock:
15 g according to EN 60
068-2-27, no disturbance of
the function
Degree of pollution
2
2
Fig.4-4:
Ambient conditions
The surrounding air must be free from acids, alkaline solutions,
corrosive agents, salts, metal vapors, and other electrically con‐
ductive contaminants in high concentrations.
The ambient air must be free from dust. Housings and installation
compartments must at least comply with degree of protection IP 54
according to DIN VDE 0470-1.
DANGER
Danger of destruction by overheating
Ensure a surrounding air temperature of less than 55 °C.
4.4
Used Standards
The IndraControl L10 complies with the following standards:
Standard
Meaning
DIN EN 60 204-1
Electrical equipment of machines
DIN EN 61,131-2
Programmable logic controllers
Requirements on the equipment and tests
DIN EN 60,529
Degrees of protection (incl. housings and installation
compartments)
DIN EN 50 178
Electronic equipment for use in power installations
Fig.4-5:
Used standards
The IndraControl L10 complies with the CE requirements!
16/54