Fig.7-17:
Digital outputs
Observe the color-coding of the connectors.
Number of outputs
8
Connection method
2-wire connection
Output type
●
Semiconductor
out‐
puts, non-saving
●
Protected, with auto‐
matic restart
●
Current-carrying
Electrical isolation to U
S
No
Electrical isolation to U
L
Yes
Output voltage, nominal value
24 V
Rated output current:
Nominal value
Maximum value acc. to DIN EN 61131-2
Signal 1
Signal 0 (leakage current)
UL rating:
General Purpose
Tungsten
0.5 A
≤ 0.6 A
2 mA ... 0.6 A
≤ 0.5 mA
0.5 A
5 W
Maximum total current of outputs
2 A
Project Planning Manual | Rexroth IndraControl L10
Electric Drives
and Controls
| Bosch Rexroth AG
31/54
Connections and Interfaces
Courtesy
of
CMA/Flodyne/Hydradyne
▪
Motion
Control
▪
Hydraulic
▪
Pneumatic
▪
Electrical
▪
Mechanical
▪
(800)
426-5480
▪
www.cmafh.com